Official Distributor
SKU
Weight
0.041 kg
This product is Not Cancellable/Not Returnable
AXL SE UTH4 EF - Temperature module
Axioline Smart Elements, Temperature recording module, Analog inputs: 4 (Inputs for thermocouples or linear voltage), connection technology: 2-conductor (shielded, twisted pair), External cold junction (can also be used as an additional Pt 100 sensor input): 1, connection technology: 4-conductor, degree of protection: IP20
- 4 analog input channels to connect thermocouples or linear voltages from -100 mV to +100 mV
- Connection of sensors in 2-conductor technology
- A Pt 100 sensor with 4-conductor technology can be connected as an external cold junction sensor or additional RTD measuring channel
- Internal detection and compensation of cold junction temperature (can be parameterized)
- Device rating plate stored
Technical Specifications
Dimensions
Width | 14.9 mm |
Height | 62.2 mm |
Depth | 62 mm |
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Smart Element interface
Number of interfaces | 1 |
Connection Method | Card edge connector |
Transmission Speed | See system in which you use the Smart Element. |
Start time until ready to operate | < 500 ms |
Module
ID code (hex) | none |
Process data channel | 80 bit |
Input address area | 10 Byte |
Output address area | 10 Byte |
Required parameter data | 21 Byte |
Required configuration data | 6 Byte |
Analog
Input name | Analog inputs |
Description of the input | Inputs for thermocouples or linear voltage |
Number of Inputs | 4 (Inputs for thermocouples or linear voltage) |
Connection Method | Push-in connection |
Connection technology | 2-conductor (shielded, twisted pair) |
Sensor types that can be used (TC) | B, C, E, J, K, L, N, R, S, T, U, W, HK, mV input |
Measured value representation | 16 bits (15 bits + sign bit) |
Input filter time | 40 ms |
Input filter time | 60 ms |
Input filter time | 100 ms |
Input filter time | 120 ms (adjustable) |
Protective circuit | Surge protection |
Protective circuit | Transient protection |
Input name | External cold junction (can also be used as an additional Pt 100 sensor input) |
Number of Inputs | 1 |
Connection Method | Push-in connection |
Connection technology | 4-conductor |
Sensor types (RTD) that can be used | Pt 100 |
Input filter time | 120 ms |
Product properties
Product family | Axioline Smart Elements |
Type | modular |
Mounting Position | See the system in which the Smart Element is used. |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Electrical properties
Maximum power dissipation for nominal condition | 0.75 W |
Potentials: Communications power supply of the Smart Elements (USE)
Supply Voltage | using card edge connectors |
Potentials: I/O supply (UP)
Supply Voltage | 24 V DC (using card edge connectors) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 28 mA |
Current draw | typ. 22 mA |
Current consumption | min. 16 mA (without connected peripherals) |
Power consumption | max. 0.67 W |
Power consumption | min. 0.38 W (without connected peripherals) |
Protective circuit | Surge protection; See the system in which the Smart Element is used. |
Protective circuit | Reverse polarity protection; Polarity protection diode |
Electrical isolation/isolation of the voltage ranges
Test voltage: Communications supply / 24 V supply (I/O) | 500 V AC, 50 Hz, 1 min. |
Test voltage: Communications supply / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | I/O |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline Smart Elements” user manual. |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.25 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Stripping length | 8 mm |
I/O
Connection Method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline Smart Elements” user manual. |
Conductor cross section, rigid | 0.25 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.25 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | Smart Element slot |
Mounting Position | See the system in which the Smart Element is used. |
Why Proax for Phoenix Contact 1182068?
Proax is an authorized distributor of Phoenix Contact 1182068 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 1079231 - Axioline Smart Elements, Digital output module, Functional safety, PROFIsafe, only for connection to Phoenix Contact or Siemens controller, Safe digital outputs: 2 (2-channel assignment), 4 (1-channel assignment), 24 V DC, 2 A, connection technology: 2-conductor, degree of protection: IP20