Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
AXL SE DO4/2 2A EF
Weight
0.038 kg
Series AXL-SE-DO

AXL SE DO4/2 2A EF - Digital module

Axioline Smart Elements, Digital output module, Digital outputs: 4, 24 V DC, 2 A, connection technology: 2-conductor, degree of protection: IP20

  • 4 digital outputs
  • 24 V DC, 2 A
  • Connection of actuators in 2-conductor technology
  • Substitute value behavior of the outputs can be parameterized for the Smart Element
  • Feed-in of the I/O supply on the Smart Element
  • Single-channel diagnostics
  • Mapping of the channel status in the input process data
  • Device rating plate stored
Technical Specifications

Dimensions

Width14.9 mm
Height62.2 mm
Depth62 mm

Utilization restriction

EMC noteEMC: class A product, see manufacturer's declaration in the download area

Smart Element interface

Number of interfaces1
Connection MethodCard edge connector
Transmission SpeedSee system in which you use the Smart Element.
Start time until ready to operate< 500 ms

Module

ID code (hex)none
Process data channel8 bit
Input address area1 Byte
Output address area1 Byte
Required parameter data 3 Byte
Required configuration data 7 Byte

Digital:

Output nameDigital outputs
Connection MethodPush-in connection
Connection technology2-conductor
Number of Outputs4
Protective circuitShort-circuit and overload protection; electronic
Output Voltage24 V DC
Maximum Output Current per modulemax. 8 A (provide external fuse protection; observe the derating.)
Nominal Output Voltage24 V DC
Load min.10 kΩ
Output voltage when switched offmax. 1 V
Output current when switched offmax. 300 µA
Nominal load, inductive48 VA (1.2 H, 12 Ω, at 24 V DC)
Nominal load, lamp24 W (at 24 V DC)
Nominal load, ohmic48 W (12 Ω, in the supply voltage range)
Switching frequencymax. 1200 per second (With resistive load, at least 50 mA load current)
Switching frequencymax. 1 per second (with inductive load)
Switching frequencymax. 4 per second (with nominal lamp load)
Behavior with overloadShutdown with automatic restart
Behavior with inductive overloadOutput can be destroyed
Signal delaymax. 100 µs (when switched on)
Signal delaymax. 100 µs (when switched off, with at least 50 mA load current)
Overcurrent shut-downmin. 2.8 A
Output current with ground connection interrupt when switched off< 1 mA

Product properties

Product familyAxioline Smart Elements
Typemodular
Mounting PositionSee the system in which the Smart Element is used.

Insulation characteristics

Overvoltage categoryII (IEC 60664-1, EN 60664-1)
Pollution degree2 (IEC 60664-1, EN 60664-1)

Electrical properties

Maximum power dissipation for nominal condition2.05 W

Potentials: I/O supply (UO)

Supply Voltage24 V DC
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 8 A (provide external protection)
Power consumptionmax. 240 W (of which 2 W constitute internal losses)
Protective circuitSurge protection; electronic (35 V, 0.5 s)
Protective circuitReverse polarity protection; parallel diode

Potentials: Communications power supply of the Smart Elements (USE)

Supply Voltageusing card edge connectors

Electrical isolation/isolation of the voltage ranges

Test voltage: Communications power supply / 24 V supply UO (I/O)500 V AC, 50 Hz, 1 min.
Test voltage: Communications power supply / 24 V supply UP500 V AC, 50 Hz, 1 min.
Test voltage: Communications supply / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply UO (I/O) / 24 V supply UP500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply UO (I/O) / functional ground500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply UP / functional ground500 V AC, 50 Hz, 1 min.

Connection technology

Connection nameI/O
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline Smart Elements” user manual.

Conductor connection

Connection MethodPush-in connection
Conductor cross section rigid0.25 mm² ... 1.5 mm²
Conductor cross section flexible0.25 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm² ... 1.5 mm²
Conductor cross section, flexible, with ferrule, with plastic sleeve0.25 mm² ... 1.5 mm²
Stripping length8 mm

I/O

Connection MethodPush-in connection
Note on the connection methodPlease observe the information provided on conductor cross sections in the “Axioline Smart Elements” user manual.
Conductor cross section, rigid0.25 mm² ... 1.5 mm²
Conductor cross section, flexible0.25 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16
Conductor cross section, flexible, with ferrule, with plastic sleeve0.25 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm² ... 1.5 mm²
Stripping length8 mm

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 60 °C
Degree of ProtectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)5 % ... 95 % (non-condensing)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeSmart Element slot
Mounting PositionSee the system in which the Smart Element is used.

Why Proax for Phoenix Contact 1181790?

Proax is an authorized distributor of Phoenix Contact 1181790 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability