AXL SE RS232 - Communication module
Axioline Smart Elements, Communication module, interface RS-232: 1, Process data width: 20 bytes, Transparent protocol, degree of protection: IP20
- One serial RS-232 input and output channel
- Data is transmitted in transparent mode
- Transmission speed can be set up to 230,400 bps
- Number of data bits, stop bits and parity can be set
- Device rating plate stored
Technical Specifications
Dimensions
Width | 14.9 mm |
Height | 62.2 mm |
Depth | 62 mm |
Smart Element interface
Number of interfaces | 1 |
Connection Method | Card edge connector |
Transmission Speed | See system in which you use the Smart Element. |
Start time until ready to operate | < 500 ms |
RS-232
Number of interfaces | 1 |
Connection Method | Push-in connection |
Note on the connection method | Use shielded cables. Connect both ends of the shield. |
Transmission Speed | 100 bps ... 230400 bps (can be parameterized) |
Transmission physics | Copper |
Protocols Supported | Transparent |
Data bits | 7 or 8 |
Stop bits | 1 or 2 |
Input buffer | 4 kByte |
Output buffer | 1 kByte |
Module
ID code (hex) | none |
Process data channel | 160 bit |
Input address area | 20 Byte |
Output address area | 20 Byte |
Required parameter data | 11 Byte |
Required configuration data | 7 Byte |
Product properties
Product family | Axioline Smart Elements |
Type | modular |
Mounting Position | See the system in which the Smart Element is used. |
Special Properties | Process data width: 20 bytes |
Special Properties | Transparent protocol |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Electrical properties
Maximum power dissipation for nominal condition | 0.3 W |
Potentials: Communications power supply of the Smart Elements (USE)
Supply Voltage | using card edge connectors |
Potentials: I/O supply (UP)
Supply Voltage | 24 V DC (using card edge connectors) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 9 mA |
Current draw | typ. 7 mA |
Current consumption | min. 6 mA (without connected peripherals) |
Power consumption | max. 174 mW |
Power consumption | min. 154 mW |
Protective circuit | Surge protection; See the system in which the Smart Element is used. |
Protective circuit | Reverse polarity protection; Polarity protection diode |
Electrical isolation/isolation of the voltage ranges
Test voltage: Communications supply / 24 V supply (I/O) | 500 V AC, 50 Hz, 1 min. |
Test voltage: Logic supply / RS-232 interface | 500 V AC, 50 Hz, 1 min. |
Test voltage: Communications supply / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O) / RS-232 interface | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: RS-232 interface/functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | I/O |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline Smart Elements” user manual. |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.25 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Stripping length | 8 mm |
I/O
Connection Method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline Smart Elements” user manual. |
Conductor cross section, rigid | 0.25 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.25 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | Smart Element slot |
Mounting Position | See the system in which the Smart Element is used. |
Why Proax for Phoenix Contact 1181787?
Proax is an authorized distributor of Phoenix Contact 1181787 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 1079231 - Axioline Smart Elements, Digital output module, Functional safety, PROFIsafe, only for connection to Phoenix Contact or Siemens controller, Safe digital outputs: 2 (2-channel assignment), 4 (1-channel assignment), 24 V DC, 2 A, connection technology: 2-conductor, degree of protection: IP20
- Axioline Smart Elements, Module de détermination de la température, Entrées analogiques: 4 (Entrées pour thermocouples ou tension linéaire), connectique: à 2 fils (blindés, torsadés par paires), Point de comparaison externe (également utilisable comme entrée supplémentaire du capteur Pt 100): 1, connectique: 4 fils, indice de protection: IP20