Official Distributor
SKU
MPN
AXL SE IOL4
Weight
0.04 kg
AXL SE IOL4 - Communication module
Axioline Smart Elements, IO-Link master, IO-Link ports Class A: 4, connection method: Push-in connection, connection technology: 3-conductor, degree of protection: IP20
- Connection of 4 IO-Link devices
- Alternatively: connection of one digital sensor or actuator per port
- Connection of IO-Link devices in 3-conductor technology
- Connection of sensors in 3-conductor technology
- Connection of actuators in 2- and 3-conductor technology
- Parameter data storage on the master
- IO-Link specification V1.1.2
- Substitute value behavior of inputs and outputs can be parameterized for each port
- IOL-CONF supported
- Device rating plate stored
Technical Specifications
Dimensions
Width | 14.9 mm |
Height | 62.2 mm |
Depth | 62 mm |
Smart Element interface
Number of interfaces | 1 |
Connection Method | Card edge connector |
Transmission Speed | See system in which you use the Smart Element. |
Start time until ready to operate | < 500 ms |
Module
ID code (hex) | none |
Process data channel | 512 bit |
Input address area | 64 Byte |
Output address area | 64 Byte |
Digital
Description of the input | IO-Link ports in digital input (DI) mode |
Number of Inputs | max. 4 (EN 61131-2 type 1) |
Connection Method | Push-in connection |
Connection technology | 3-conductor |
Nominal input voltage UIN | 24 V DC |
Input voltage range "0" signal | -0.3 V DC ... 5 V DC |
Input voltage range "1" signal | 11 V DC ... 30 V DC |
Nominal input current | typ. 2.5 mA |
Sensor current per channel | max. 500 mA (from L+/L-) |
Input filter time | 1 µs |
IO-Link
Number of Ports | 4 |
Connection Method | Push-in connection |
Connection technology | 3-conductor |
Port Type | Class A |
Digital
Output description | IO-Link ports in digital output (DO) mode |
Connection Method | Push-in connection |
Connection technology | 2-, 3-conductor |
Number of Outputs | max. 4 |
Nominal Output Voltage | 24 V DC |
Nominal current per channel | 200 mA |
Product properties
Product family | Axioline Smart Elements |
Type | modular |
Mounting Position | See the system in which the Smart Element is used. |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Electrical properties
Maximum power dissipation for nominal condition | 1.85 W |
Supply: IO-Link
Nominal voltage for I/O supply | 24 V DC |
Supply Voltage Range | 18 V DC ... 30 V DC (including all tolerances, including ripple) |
Nominal current for every IO-Link port | 500 mA (at L+/L-) |
Nominal current for every IO-Link port | 200 mA (at C/Q) |
Protective circuit | Overload protection for L+; electronically limited to 0.6 A |
Protective circuit | Short-circuit protection for L+; by switching off after 55 ms |
Potentials: Communications power supply of the Smart Elements (USE)
Supply Voltage | using card edge connectors |
Potentials: I/O supply (UP) incl. IO-Link port supply
Supply Voltage | 24 V DC (using card edge connectors) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 2030 mA (Internal current consumption + full load of the 4 IO-Link ports (4 x 500 mA)) |
Current draw | typ. 2020 mA |
Current consumption | min. 18 mA (without connected peripherals) |
Power consumption | max. 61 W (of which 1.45 W internal losses) |
Power consumption | min. 432 mW |
Protective circuit | Surge protection; See the system in which the Smart Element is used. |
Protective circuit | Reverse polarity protection; Polarity protection diode |
Electrical isolation/isolation of the voltage ranges
Test voltage: Communications supply / 24 V supply (I/O) | 500 V AC, 50 Hz, 1 min. |
Test voltage: Communications supply / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | I/O |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline Smart Elements” user manual. |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.25 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Stripping length | 8 mm |
I/O
Connection Method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline Smart Elements” user manual. |
Conductor cross section, rigid | 0.25 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.25 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | Smart Element slot |
Mounting Position | See the system in which the Smart Element is used. |
Accessories
Why Proax for Phoenix Contact 1088132?
Proax is an authorized distributor of Phoenix Contact 1088132 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 1079231 - Axioline Smart Elements, Digital output module, Functional safety, PROFIsafe, only for connection to Phoenix Contact or Siemens controller, Safe digital outputs: 2 (2-channel assignment), 4 (1-channel assignment), 24 V DC, 2 A, connection technology: 2-conductor, degree of protection: IP20