Official Distributor
SKU
Weight
0.035 kg
This product is Not Cancellable/Not Returnable
AXL SE CNT1 - Function module
Axioline Smart Elements, Function module, Counter input: 1, Control input: 1, Counting direction input: 1, Digital output: 1, 24 V DC, 100 mA, degree of protection: IP20
- 32-bit counter (up and down)
- Maximum input frequency: 150 kHz
- Activation of an output is based on a comparative value
- Counter control using a hardware or software gate
- Single or periodic count
- Protected 24 V sensor/actuator supply
- Device rating plate stored
Technical Specifications
Dimensions
Width | 14.9 mm |
Height | 62.2 mm |
Depth | 62 mm |
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Smart Element interface
Number of interfaces | 1 |
Connection Method | Card edge connector |
Transmission Speed | See system in which you use the Smart Element. |
Start time until ready to operate | < 500 ms |
Module
ID code (hex) | none |
Process data channel | 48 bit |
Input address area | 6 Byte |
Output address area | 6 Byte |
Required parameter data | 20 Byte |
Required configuration data | 7 Byte |
Counter:
Input name | Counter input |
Description of the input | EN 61131-2 type 1 |
Connection Method | Push-in connection |
Number of Inputs | 1 (Source) |
Input Voltage | 24 V DC |
Input voltage range "0" signal | -3 V DC ... 5 V DC |
Input voltage range "1" signal | 15 V DC ... 30 V DC |
Input Frequency | max. 150 kHz |
Input Current | typ. 2.3 mA |
Resolution | 32 bits |
Digital:
Output name | Digital output |
Output description | Push-pull output (switches to GND at level 0) |
Connection Method | Push-in connection |
Number of Outputs | 1 (OUT) |
Protective circuit | Short-circuit and overload protection; electronic |
Protective circuit | Surge protection; Suppressor diode |
Output Voltage | 24 V DC |
Product properties
Product family | Axioline Smart Elements |
Type | modular |
Mounting Position | See the system in which the Smart Element is used. |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Electrical properties
Maximum power dissipation for nominal condition | 1.75 W |
Potentials: Communications power supply of the Smart Elements (USE)
Supply Voltage | using card edge connectors |
Potentials: I/O supply (UP)
Supply Voltage | 24 V DC (using card edge connectors) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 700 mA |
Current draw | typ. 620 mA |
Current consumption | min. 20 mA (without connected peripherals) |
Power consumption | max. 21 W (of which 1.48 W internal losses) |
Power consumption | min. 480 mW |
Protective circuit | Surge protection; See the system in which the Smart Element is used. |
Protective circuit | Reverse polarity protection; Polarity protection diode |
Supply:
Designation | Sensor/actuator supply US |
Supply Voltage | 24 V DC |
Electrical isolation/isolation of the voltage ranges
Test voltage: Communications supply / 24 V supply (I/O) | 500 V AC, 50 Hz, 1 min. |
Test voltage: Communications supply / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | I/O |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline Smart Elements” user manual. |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.25 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Stripping length | 8 mm |
I/O
Connection Method | Push-in connection |
Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline Smart Elements” user manual. |
Conductor cross section, rigid | 0.25 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.25 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | Smart Element slot |
Mounting Position | See the system in which the Smart Element is used. |
Accessories
Why Proax for Phoenix Contact 1088131?
Proax is an authorized distributor of Phoenix Contact 1088131 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 1079231 - Axioline Smart Elements, Digital output module, Functional safety, PROFIsafe, only for connection to Phoenix Contact or Siemens controller, Safe digital outputs: 2 (2-channel assignment), 4 (1-channel assignment), 24 V DC, 2 A, connection technology: 2-conductor, degree of protection: IP20