SKU
MPN
MACX MCR-S-MUX
MACX MCR-S-MUX - HART multiplexer
HART Multiplexer for online configuration and diagnostics of HART-compatible field devices, as well as for continuous documentation of process variables and states with a PC or management system for mounting on NS 35/7.5 or NS 32
- Supports online configuration and diagnostics for the connected HART-compatible field devices
- Communication via software tool (e.g., HART OPC server) using RS-485 interface
- Up to 128 HART multiplexers on one PC interface
- 32 HART channels per multiplexer
- Continuous documentation of process variables and states
- Electrical isolation between auxiliary voltage, RS-485 bus, and the HART channels
- HART field devices are accessed parallel to the transmission of the measurement signal without affecting measured value processing
- HART field devices connected via universal HART connection boards; direct connection if processing non-Ex signals, with separate Ex i signal isolator connected upstream if processing Ex signals
- Power supply via HART connection board
Technical Specifications
Electrical properties
Error monitoring | Processor error: The "PWR" LED flashes; error in the HART communication: the "ERR" LED flashes |
Electrical isolation HART signal/RS-485
Electrical isolation | 350 V AC |
Electrical isolation HART signals/HART signals
Electrical isolation | 100 V DC (capacitive) |
Electrical isolation Supply/HART signal/RS-485
Electrical isolation | 300 V AC |
Supply
Supply Voltage | 24 V DC |
Supply Voltage Range | 18 V ... 31.2 V |
Typical current consumption | 55 mA |
Nominal Power Consumption | 1.35 W |
Undervoltage monitoring | Yes (no faulty devices / output states) |
HART
Designation | HART FSK |
Channels | 16 or 32; adjustable using a switch |
Connection Method | Flat-ribbon cable, 14-pos. (inclusive) |
HART specification | HART Field Communication Protocol Rev. 6.0 (downward compatible up to Rev 4.0); FSK Physical Layer Specification (Rev. 8.1) |
Data transmission display | Two yellow "Tx" and "Rx" "HART" LEDs |
Display error | Red "ERR" LED (flashes in case of an error in the HART bus) |
RS-485
Number | 1 |
Connection Method | D-SUB-9 female connector |
Designation | RS-485 |
Data flow control/protocols | Compatible with OPC HART server, PDM, PRM, and FDT/DTM |
Number of HART multiplexers per bus segment | Max 31 |
Address setting | 0...127; using a rotary switch at the front |
Serial transmission speed | 9600 / 19200 / 38400 / 57600 [bps]; via rotary switch at the front |
Transmission length | ≤ 1200 m |
Display | Two yellow "Tx" and "Rx" "RS-485" LEDs |
Signaling
Operating voltage display | Green "PWR" LED |
Dimensions
Width | 35.2 mm |
Height | 108.8 mm |
Depth | 114.5 mm |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Ambient conditions
Ambient Temperature (Operation) | -20 °C ... 60 °C (aligned) |
Ambient Temperature (Operation) | -20 °C ... 70 °C (Stand-alone device) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (non-condensing) |
CE
Certificate | CE-compliant |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2865599?
Proax is an authorized distributor of Phoenix Contact 2865599 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended