
SKU
MPN
MACX MCR-SL-RTD-I-NC
Weight
0.17 kg
This product is Not Cancellable/Not Returnable
MACX MCR-SL-RTD-I-NC - Temperature measuring transducer
Temperature transducer, converts signals from resistance temperature detectors and resistors into 0/4 – 20 mA analog signals. Freely programmable, 3-way electrical isolation. Replacement item: 1050192 MACX MCR-RTD-I.
- Power supply possible via DIN rail connector
- Installation in zone 2, protection type "n" (EN 60079-15) permitted
- Status indicator for supply voltage, cable, sensor, and module errors
- Configuration via software (FDT/DTM): sensor type, connection technology, measuring range, measuring unit, filter, alarm signal, and output range
- Programming during operation and also voltage-free using IFS-USB-PROG-ADAPTER programming adapter
- 3-way electrical isolation
- Input for resistance thermometers and resistance-type sensors
- Output: 0 mA ... 20 mA or 4 mA ... 20 mA
Technical Specifications
Product properties
Application | Temperature |
Type | Signal conditioner |
Insulation characteristics
Overvoltage category | II |
Pollution degree | 2 |
Electrical properties
Alignment span | ± 5 % |
Alignment zero | ± 5 % |
Step response (0–99%) | 700 ms |
Step response (0–99%) | ≤ 1100 ms |
Temperature coefficient, typical | 0.01 %/K |
Electrical isolation Input/output/power supply
Rated Insulation Voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
Electrical isolation Input/output
Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
Electrical isolation Input/power supply
Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
Supply
Nominal Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
Max. current consumption | < 40 mA (24 V DC) |
Power dissipation | < 1 W |
Signal
Number of Inputs | 1 |
Input Signal | Temperature |
Input Signal | Resistor |
Measurement
Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire |
Temperature measuring range | -200 °C ... 850 °C (Range depending on the sensor type) |
Linear resistance measuring range | 0 Ω ... 2000 Ω |
Max. permissible overall conductor resistance | 50 Ω (Per cable) |
Sensor input current | 200 µA ... 1 mA |
Temperature measuring range | > 50 K |
Switching:
Configurable/programmable | no |
Signal
Output description | Current output |
Number of Outputs | 1 |
Configurable/programmable | Yes |
Current Output Signal | 0 mA ... 20 mA |
Current Output Signal | 4 mA ... 20 mA |
Load/Output Load Current Output | ≤ 500 Ω |
Output ripple (current) | < 50 µAPP |
Output ripple (current) | < 10 µArms |
Behavior in the event of a sensor error | As per NE 43 or can be freely defined |
Connection data
Connection Method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Signaling
Status display | Green LED (supply voltage, PWR) |
Status display | Red LED, flashing 2.4 Hz (cable error, sensor error on input or output, ERR) |
Status display | Red LED, flashing 1.2 Hz (service operation, ERR) |
Status display | Red LED, permanently on (module error, ERR) |
Dimensions
Width | 12.5 mm |
Height | 112.5 mm |
Depth | 114.5 mm |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing Material | PA 6.6-FR |
Ambient conditions
Degree of Protection | IP20 (not assessed by UL) |
Ambient Temperature (Operation) | -20 °C ... 60 °C (Any mounting position) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE
Certificate | CE-compliant |
Note | and EN 61326-1 |
ATEX
Identification | II 3G Ex nA ic IIC T4 Gc X |
UL, USA/Canada
Identification | UL 508 Listed |
Identification | UL 61010 Listed |
Identification | Class I, Div. 2, Groups A, B, C, D T4 |
Identification | Class I, Zone 2, Group IIC T4 |
Shipbuilding approval
Certificate | GL 86 644-10HH |
GL
Identification | C, EMC1 |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Noise emission | EN 61000-6-4 |
Electromagnetic HF field
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Fast transients (burst)
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Conducted interference
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2865078?
Proax is an authorized distributor of Phoenix Contact 2865078 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended