SKU
MPN
MACX MCR-SL-UI-REL
Weight
0.255 kg
MACX MCR-SL-UI-REL - Limit value switch
Limit value switch with input for active current and voltage signals and a limit-value relay output (changeover contact). Can be set via DIP switch and potentiometer, galvanic 3-way electrical isolation, up to SIL2 (SC3), PLc Cat.1, screw connection.
Technical Specifications
Product properties
Product family | MACX Analog |
Type | Signal conditioners with SIL and PL Functional Safety |
Configuration | DIP switches |
Insulation characteristics: GB Standard
Overvoltage category | II |
Pollution degree | 2 |
Functionality
Configuration | DIP switches |
Electrical properties
Electrical isolation | 3-way isolation |
Switching point accuracy | < 0.1 % |
Step response (0–99%) | ≤ 22 ms |
Maximum temperature coefficient | 0.01 %/K |
Maximum transmission error | 0.1 % |
Electrical isolation Output/supply
Rated Insulation Voltage | 250 V AC (IEC/EN 60079-7) |
Electrical isolation Input/output/power supply
Rated Insulation Voltage | 300 V AC (EN 61010-1) |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
Electrical isolation Input/output, power supply
Rated Insulation Voltage | 375 V AC (IEC/EN 60079-7) |
Supply
Nominal Supply Voltage | 24 V DC |
Supply Voltage Range | 9.6 V DC ... 30 V DC (12 V DC ... 24 V DC (-20 % ... +25 %)) |
Typical current consumption | 38 mA (24 V DC) |
Max. current consumption | 90 mA (10 V DC) |
Power dissipation | < 0.9 W |
Power consumption | ≤ 1.2 W |
Signal: Voltage/current
Voltage input signal | 0.1 V ... 10 V |
Voltage input signal | 0.1 V ... 10.5 V (Maximum range) |
Total error of the voltage input maximum | ± 10 mV |
Current Input Signal | 0.2 mA ... 20 mA |
Current Input Signal | 0.18 mA ... 21 mA (Maximum range) |
Total error of the current input maximum | ± 20 µA |
Input resistance of voltage input | > 100 kΩ |
Input resistance current input | < 28 Ω |
Switching threshold "0" signal current | Configurable via DIP switch (in 1.25% increments) and potentiometer (linearly up to 2% of the switching threshold set via the DIP switch) |
Switching hysteresis | off: approx. 0.5 %, on: approx. 1 % |
Line fault detection | < 0.1 mA (Line break) |
Line fault detection | > 21.1 mA (Short circuit) |
Switching: Relay
Contact switching type | 1 changeover contact |
Contact Material | AgSnO2, hard gold-plated |
Max. switching current | ≤ 4 A AC (cos phi = 1) |
Max. switching current | ≤ 1 A DC (ohmic load, 24 V DC, 50 mW) |
Max. switching current | ≤ 0.2 A DC (ohmic load, 120 V DC) |
Connection data
Connection Method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Test socket
Max. diameter | 2 mm |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Signaling
Status display | Green LED (supply voltage) |
Status display | Yellow LED (switching output) |
Status display | Red LED, flashing (line, sensor error, ERR) |
Dimensions
Width | 12.5 mm |
Height | 112.5 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing Material | PA 6.6-FR |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -20 °C ... 65 °C (Any mounting position) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX
Identification | II 3G Ex ec nC IIC T4 Gc |
Certificate | TÜV 18 ATEX 8222 X |
UKCA Ex (UKEX)
Identification | II 3 G Ex ec nC IIC T4 Gc |
Certificate | PxCIF21UKEX2906169X |
IECEx
Identification | Ex ec nC IIC T4 Gc |
Certificate | IECEx TUR 18.0014X |
CCC / China-Ex
Identification | Ex ec nC IIC T4 Gc |
Certificate | 2022122304115959 |
INMETRO
Identification | Ex ec nC IIC T4 Gc |
Certificate | DNV 21.0089 X |
UL, USA/Canada
Identification | UL 61010 Listed |
Identification | Class I, Div. 2, Groups A, B, C, D T4 |
Identification | Class I, Zone 2, Group IIC T4 |
Shipbuilding approval
Certificate | DNV GL TAA000020C |
EAC
Identification | 2Ex e nC IIC T4 Gc X |
Certificate | RU C-DE.HB49.B.00145/21 |
Safety Integrity Level (SIL, IEC 61508)
Identification | 2 |
Certificate | TÜV Rheinland 968/FSP 1481.00/17 |
Note | Single-channel |
Identification | 3 |
Certificate | TÜV Rheinland 968/FSP 1481.00/17 |
Note | Two-channel |
Systematic Capability
Identification | 3 |
Performance Level (ISO 13849)
Identification | c |
DNV GL data
Temperature | B |
Humidity | B |
Vibration | A |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Standards and Regulations
Electrical isolation | 3-way isolation |
GB Standard
Standards/regulations | GB 3836.1 |
Standards/regulations | GB 3836.3 |
Standards/regulations | GB 3836.8 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2906169?
Proax is an authorized distributor of Phoenix Contact 2906169 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended