MACX MCR-SL-NAM-2RO - Isolation amplifier

NAMUR signal conditioner for operating proximity sensors and switches. The signals are transferred to the control level using 2 isolated relay outputs (N/O contact). Line fault detection (LFD), 3-way electrical isolation, SIL 2, screw connection.

  • Power supply and error indication possible via DIN rail connector
  • Installation in zone 2, protection type "n" (EN 60079-15) permitted
  • Up to SIL 2 in accordance with EN 61508
  • Line fault detection (LFD), can be activated/deactivated, error indicated by flashing red LED with de-excitation of output relay
  • Input for NAMUR proximity sensors (EN 60947-5-6), floating contacts or contacts with resistance circuit
  • 4-way electrical isolation
  • Direction of operation can be selected (operating or closed circuit current behavior)
  • 2 relay signal outputs (N/O contact); output 2 can also be used as an error signaling output
  • LED indicators for supply voltage, switching state, and malfunction in accordance with NAMUR NE 44
Technical Specifications

Product properties

Product familyMACX Analog
ApplicationDigital IN
No. of channels1
TypeSignal conditioners with SIL functional safety
ConfigurationDIP switches

Functionality

ConfigurationDIP switches

Electrical properties

Electrical isolation3-way isolation
Electrical isolation between input and outputyes

Electrical isolation Input/supply, DIN rail connector IEC/EN 61010-1

Standards/regulationsIEC/EN 61010-1
Rated Insulation Voltage300 Vrms
Overvoltage categoryII
Pollution degree2
InsulationSafe isolation

Electrical isolation Output 1/output 2/input, power supply, DIN rail connector IEC/EN 61010-1

Standards/regulationsIEC/EN 61010-1
Rated Insulation Voltage300 Vrms
Overvoltage categoryIII
Pollution degree2
InsulationSafe isolation

Electrical isolation Output 1/output 2/input/power supply, DIN rail connector

Test voltage2.5 kV AC (50 Hz, 60 s)
Overvoltage categoryIII
Pollution degree2

Supply

Nominal Supply Voltage24 V DC -20 % ... +25 %
Supply Voltage Range19.2 V DC ... 30 V DC
Max. current consumption30 mA (24 V DC)
Power dissipation< 950 mW
Power consumption< 950 mW

Signal: NAMUR

Number of Inputs1
Available Input SourcesNAMUR proximity sensors (IEC/EN 60947-5-6)
Available Input SourcesFloating switch contacts
Available Input SourcesSwitch contacts with resistance circuit
Switching threshold "0" signal current< 1.2 mA (blocking)
Switching threshold "1" signal, current> 2.1 mA (conductive)
Short-circuit current8 mA
Switching hysteresis< 0.2 mA
Line fault detection< 0.05 mA ... 0.35 mA (Line break)
Line fault detection< 100 Ω ... 360 Ω (Short circuit)
Line fault detectionActivated /deactivated via DIP switch
Non-load voltage8 V DC

Switching: Relay

Contact switching type2 N/O contacts
Contact MaterialAgSnO2, hard gold-plated
Maximum Switching Voltage250 V AC (2 A)
Maximum Switching Voltage120 V DC (0.2 A)
Maximum Switching Voltage30 V DC (2 A)
Maximum switching capacity500 VA
Recommended minimum load5 V / 10 mA
Switching frequency≤ 20 Hz (without load)

Signal

Number of Outputs2

Connection data

Connection MethodScrew connection
Stripping length7 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Tightening torque0.5 Nm ... 0.6 Nm

Test socket

Max. diameter2 mm

Ex data

Ex installation (EPL)Gc
Ex installation (EPL)Div. 2

Data

No. of channels0

Signaling

Status displayGreen LED (supply voltage)
Status displayLED yellow (switching state)
Status displayRed LED (line errors)

Dimensions

Width12.5 mm
Height112.5 mm
Depth113.7 mm
Depth NS 35/7,5114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)

Material specifications

Colorgray (RAL 7042)
Flammability rating according to UL 94V0 (Housing)
Housing MaterialPA 6.6-FR

Safety data

Safety Integrity Level (SIL)2

Safety data: IEC 61508 - Low demand

Safety Integrity Level (SIL)2
Safety Integrity Level (SIL)2

Ambient conditions

Degree of ProtectionIP20 (not assessed by UL)
Ambient Temperature (Operation)-40 °C ... 60 °C (Any mounting position)
Ambient Temperature (Operation)-40 °C ... 70 °C (Derating)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)5 % ... 95 % (non-condensing)

Altitude range (≤ 2000 m)

Altitude≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.)
Ambient Temperature (Operation)-40 °C ... 60 °C
Ambient Temperature (Operation)-40 °C ... 70 °C (Derating)
Rated Insulation Voltage253 V AC (Power supply, input / output)
Rated Insulation Voltage125 V DC (Power supply, input / output)

Altitude range (≤ 3000 m)

Height Range> 2000 m ... 3000 m
Ambient Temperature (Operation)-40 °C ... 54 °C
Ambient Temperature (Operation)-40 °C ... 63 °C (Derating)
Rated Insulation Voltage190 V AC (Power supply, input / output)
Rated Insulation Voltage110 V DC (Power supply, input / output)

Altitude range (≤ 4000 m)

Height Range> 3000 m ... 4000 m
Ambient Temperature (Operation)-40 °C ... 48 °C
Ambient Temperature (Operation)-40 °C ... 56 °C (Derating)
Rated Insulation Voltage60 V AC/DC (Power supply, input / output)

Altitude range (≤ 5000 m)

Height Range> 4000 m ... 5000 m
Ambient Temperature (Operation)-40 °C ... 42 °C
Ambient Temperature (Operation)-40 °C ... 49 °C (Derating)
Rated Insulation Voltage60 V AC/DC (Power supply, input / output)

CE

CertificateCE-compliant
Noteand EN 61326-1

ATEX

Identification II 3G Ex ec nC IIC T4 Gc
CertificateIBExU 07 ATEX 1069 X

UKCA Ex (UKEX)

Identification II 3G Ex ec nC IIC T4 Gc
CertificatePxCIF21UKEX2865049X

IECEx

IdentificationEx ec nC IIC T4 Gc
CertificateIBE 08.0001 X

CCC / China-Ex

IdentificationEx ec nC IIC T4 Gc
Certificate2021122304114179

UL, USA/Canada

IdentificationUL 508 Listed
IdentificationUL 61010 Listed
IdentificationClass I, Div. 2, Groups A, B, C, D T4
IdentificationClass I, Zone 2, Group IIC T4

Shipbuilding approval

CertificateDNV GL TAA00000AG

Safety Integrity Level (SIL, IEC 61508)

Identification2

INMETRO

IdentificationEx ec nC IIC T4 Gc
CertificateDNV 18.0114 X

EAC Ex

Identification 2Ex ec nC IIC T4 Gc
CertificateBY/112 02.01 TP012 103.01 00078

DNV GL data

TemperatureB
HumidityB
VibrationA
EMCB
EnclosureRequired protection according to the Rules shall be provided upon installation on board

EMC data

Noise immunityEN 61000-6-2
Noise immunityEN 61326
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4

Standards and Regulations

Electrical isolation3-way isolation

GB Standard

Standards/regulationsGB/T 3836.1
Standards/regulationsGB/T 3836.3
Standards/regulationsGB/T 3836.8

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact 2865010?

Proax is an authorized distributor of Phoenix Contact 2865010 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability