2865997
SKU
PHX2865997
MPN
MACX MCR-SL-NAM-R
MACX MCR-SL-NAM-R - Isolation amplifier
NAMUR signal conditioners for operating proximity sensors and switches. The signals are transmitted to the control level via relay output (changeover contact). Line fault detection (LFD), 3-way electrical isolation, SIL 2, with screw connection.
- Power supply and error indication possible via DIN rail connector
- Installation in zone 2, protection type "n" (EN 60079-15) permitted
- Up to SIL 2 in accordance with EN 61508
- Line fault detection (LFD), can be activated/deactivated, error indicated by flashing red LED with de-excitation of output relay
- LED indicators for supply voltage, switching state, and malfunction in accordance with NAMUR NE 44
- 3-way electrical isolation
- Input for NAMUR proximity sensors (EN 60947-5-6), floating contacts or contacts with resistance circuit
- Signal output relay (changeover contact)
- Direction of operation can be selected (operating or closed circuit current behavior)
Technical Specifications
Product properties
| Product family | MACX Analog |
| Application | Digital IN |
| No. of channels | 1 |
| Type | Signal conditioners with SIL functional safety |
| Configuration | DIP switches |
Functionality
| Configuration | DIP switches |
Electrical properties
| Electrical isolation | 3-way isolation |
| Electrical isolation between input and output | yes |
| Maximum power dissipation for nominal condition | < 650 mW |
Electrical isolation
| Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Electrical isolation Input/output IEC/EN 60079-11
| Standards/regulations | IEC/EN 60079-11 |
| Rated Insulation Voltage | 375 VPP |
| Overvoltage category | II |
| Pollution degree | 2 |
Electrical isolation Input/output/supply, DIN rail connector IEC/EN 61010-1
| Standards/regulations | IEC/EN 61010-1 |
| Rated Insulation Voltage | 300 Vrms |
| Overvoltage category | II |
| Pollution degree | 2 |
| Insulation | Safe isolation |
Electrical isolation Output/input, supply, TBUS IEC/EN 61010-1
| Standards/regulations | IEC/EN 61010-1 |
| Rated Insulation Voltage | 300 Vrms |
| Overvoltage category | III |
| Pollution degree | 2 |
| Insulation | Safe isolation |
Electrical isolation Input/supply, DIN rail connector IEC/EN 60079-11
| Standards/regulations | IEC/EN 60079-11 |
| Rated Insulation Voltage | 375 VPP |
| Overvoltage category | II |
| Pollution degree | 2 |
Supply
| Nominal Supply Voltage | 24 V DC -20 % ... +25 % |
| Supply Voltage Range | 19.2 V DC ... 30 V DC |
| Max. current consumption | 21 mA (24 V DC) |
| Power dissipation | < 650 mW |
| Power consumption | < 650 mW |
Signal: NAMUR
| Number of Inputs | 1 |
| Available Input Sources | NAMUR proximity sensors (IEC/EN 60947-5-6) |
| Available Input Sources | Floating switch contacts |
| Available Input Sources | Switch contacts with resistance circuit |
| Switching threshold "0" signal current | < 1.2 mA (blocking) |
| Switching threshold "1" signal, current | > 2.1 mA (conductive) |
| Short-circuit current | 8 mA |
| Switching hysteresis | < 0.2 mA |
| Line fault detection | < 0.05 mA ... 0.35 mA (Line break) |
| Line fault detection | < 100 Ω ... 360 Ω (Short circuit) |
| Line fault detection | Activated /deactivated via DIP switch |
| Non-load voltage | 8 V DC |
Switching: Relay
| Contact switching type | 1 changeover contact |
| Contact Material | AgSnO2, hard gold-plated |
| Maximum Switching Voltage | 250 V AC (2 A) |
| Maximum Switching Voltage | 120 V DC (0.2 A) |
| Maximum Switching Voltage | 30 V DC (2 A) |
| Maximum switching capacity | 500 VA |
| Recommended minimum load | 5 V / 10 mA |
| Switching frequency | ≤ 20 Hz (without load) |
Signal
| Number of Outputs | 1 |
Connection data
| Connection Method | Screw connection |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
Test socket
| Max. diameter | 2 mm |
Ex data
| Ex installation (EPL) | Gc |
| Ex installation (EPL) | Div. 2 |
Data
| No. of channels | 0 |
Signaling
| Status display | Green LED (supply voltage) |
| Status display | LED yellow (switching state) |
| Status display | Red LED (line errors) |
Dimensions
| Width | 12.5 mm |
| Height | 112.5 mm |
| Depth | 113.7 mm |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Housing Material | PA 6.6-FR |
Safety data
| Safety Integrity Level (SIL) | 2 |
Safety data: IEC 61508 - Low demand
| Safety Integrity Level (SIL) | 2 |
| Safety Integrity Level (SIL) | 2 |
Ambient conditions
| Degree of Protection | IP20 (not assessed by UL) |
| Ambient Temperature (Operation) | -40 °C ... 60 °C (Any mounting position) |
| Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m)
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
| Ambient Temperature (Operation) | -40 °C ... 60 °C |
| Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
| Rated Insulation Voltage | 253 V AC (Power supply, input / output) |
| Rated Insulation Voltage | 125 V DC (Power supply, input / output) |
Altitude range (≤ 3000 m)
| Height Range | > 2000 m ... 3000 m |
| Ambient Temperature (Operation) | -40 °C ... 54 °C |
| Ambient Temperature (Operation) | -40 °C ... 63 °C (Derating) |
| Rated Insulation Voltage | 190 V AC (Power supply, input / output) |
| Rated Insulation Voltage | 110 V DC (Power supply, input / output) |
Altitude range (≤ 4000 m)
| Height Range | > 3000 m ... 4000 m |
| Ambient Temperature (Operation) | -40 °C ... 48 °C |
| Ambient Temperature (Operation) | -40 °C ... 56 °C (Derating) |
| Rated Insulation Voltage | 60 V AC/DC (Power supply, input / output) |
Altitude range (≤ 5000 m)
| Height Range | > 4000 m ... 5000 m |
| Ambient Temperature (Operation) | -40 °C ... 42 °C |
| Ambient Temperature (Operation) | -40 °C ... 49 °C (Derating) |
| Rated Insulation Voltage | 60 V AC/DC (Power supply, input / output) |
CE
| Certificate | CE-compliant |
| Note | and EN 61326-1 |
ATEX
| Identification | II 3G Ex ec nC IIC T4 Gc |
| Certificate | IBExU 07 ATEX 1069 X |
UKCA Ex (UKEX)
| Identification | II 3G Ex ec nC IIC T4 Gc |
| Certificate | PxCIF21UKEX2865049X |
IECEx
| Identification | Ex ec nC IIC T4 Gc |
| Certificate | IBE 08.0001 X |
CCC / China-Ex
| Identification | Ex ec nC IIC T4 Gc |
| Certificate | 2021122304114179 |
UL, USA/Canada
| Identification | UL 508 Listed |
| Identification | UL 61010 Listed |
| Identification | Class I, Div. 2, Groups A, B, C, D T4 |
| Identification | Class I, Zone 2, Group IIC T4 |
Shipbuilding approval
| Certificate | DNV GL TAA00000AG |
Safety Integrity Level (SIL, IEC 61508)
| Identification | 2 |
INMETRO
| Identification | Ex ec nC IIC T4 Gc |
| Certificate | DNV 18.0114 X |
EAC Ex
| Identification | 2Ex ec nC IIC T4 Gc |
| Certificate | BY/112 02.01 TP012 103.01 00078 |
DNV GL data
| Temperature | B |
| Humidity | B |
| Vibration | A |
| EMC | B |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
| Noise immunity | EN 61000-6-2 |
| Noise immunity | EN 61326 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
Standards and Regulations
| Electrical isolation | 3-way isolation |
GB Standard
| Standards/regulations | GB/T 3836.1 |
| Standards/regulations | GB/T 3836.3 |
| Standards/regulations | GB/T 3836.8 |
Mounting
| Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2865997?
Proax is an authorized distributor of Phoenix Contact 2865997 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended