MACX MCR-SL-RPSSI-I-SP - Power/input isolating amplifier
Repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active 0/4 … 20 mA signals to a load (active or passive). 3-way electrical isolation, SIL 2 in accordance with IEC 61508.
- Power supply possible via DIN rail connector
- Up to SIL 2 in accordance with EN 61508
- Installation in zone 2, protection type "n" (EN 60079-15) permitted
- Input: 0/4 mA ... 20 mA (powered or not powered)
- Output: 0/4 mA ... 20 mA (active or passive)
- Terminal point with 250 Ω resistor to increase HART impedance for low-resistance systems
- 3-way electrical isolation
- Plug-in screw or spring-cage connection technology (Push-in technology), with integrated sockets for HART communicators
- Bidirectional transmission of digital HART communication signals
Technical Specifications
Product properties
| Product family | MACX Analog |
| Application | Analog IN |
| No. of channels | 1 |
| Type | Signal conditioners with SIL functional safety |
Electrical properties
| Electrical isolation | 3-way isolation |
| Electrical isolation between input and output | yes |
| Signal transmission behavior | In = Out |
| Step response (10-90%) | < 200 µs (for jump 4 mA ... 20 mA, load 600 Ω) |
| Step response (10-90%) | < 600 µs (for jump 0 mA ... 20 mA, load 600 Ω) |
| Maximum temperature coefficient | < 0.01 %/K |
| Maximum transmission error | < 0.1 % (of final value) |
| Transmission error, typical | < 0.05 % (of final value) |
Electrical isolation
| Test voltage | 2.5 kV AC (50 Hz, 60 s) |
| Overvoltage category | II |
| Pollution degree | 2 |
Electrical isolation Input/output/power supply IEC/EN 61010-1
| Standards/regulations | IEC/EN 61010-1 |
| Rated Insulation Voltage | 300 Vrms |
| Insulation | Safe isolation |
Electrical isolation Input/output IEC/EN 60079-11
| Standards/regulations | IEC/EN 60079-11 |
| Rated Insulation Voltage | 265 Vrms |
Electrical isolation Input/power supply IEC/EN 60079-11
| Standards/regulations | IEC/EN 60079-11 |
| Rated Insulation Voltage | 265 Vrms |
Electrical isolation Output/supply IEC/EN 60079-7
| Standards/regulations | IEC/EN 60079-7 |
| Rated Insulation Voltage | 265 Vrms |
Supply
| Designation | Repeater power supply operation |
| Nominal Supply Voltage | 24 V DC -20 % ... +25 % |
| Supply Voltage Range | 19.2 V DC ... 30 V DC |
| Max. current consumption | < 76 mA (24 V DC / 20 mA / 1000 Ω) |
| Max. current consumption | < 55 mA (24 V DC / 20 mA / 250 Ω) |
| Power dissipation | < 1.1 W (24 V DC / 20 mA / 1000 Ω) |
| Power dissipation | < 0.95 W (24 V DC / 20 mA / 250 Ω) |
| Power dissipation | < 1.2 W (24 V DC / 20 mA / 0 Ω) |
| Power consumption | < 1.8 W (20 mA / 1000 Ω) |
| Power consumption | < 1.3 W (20 mA / 250 Ω) |
| Designation | Signal conditioner operation |
| Nominal Supply Voltage | 24 V DC -20 % ... +25 % |
| Supply Voltage Range | 19.2 V DC ... 30 V DC |
| Max. current consumption | < 44 mA (24 V DC / 20 mA / 1000 Ω) |
| Max. current consumption | < 27 mA (24 V DC / 20 mA / 250 Ω) |
| Power dissipation | < 0.75 W (24 V DC / 20 mA / 1000 Ω) |
| Power dissipation | < 0.65 W (24 V DC / 20 mA / 250 Ω) |
| Power dissipation | < 0.95 W (24 V DC / 20 mA / 0 Ω) |
Signal: Repeater power supply operation
| Description of the input | Active current input |
| Number of Inputs | 1 |
| Input Signal | Current |
| Current Input Signal | 4 mA ... 20 mA |
| Current limitation | 25 mA |
| Transmitter supply voltage | > 21.5 V (20 mA) |
| Transmitter supply voltage | > 20.8 V (24 mA) |
| Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Signal: Signal conditioner operation
| Description of the input | Passive current input |
| Current Input Signal | 0 mA ... 20 mA |
| Current Input Signal | 4 mA ... 20 mA |
| Voltage drop | < 3.5 V (in input isolating amplifier operation) |
| Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Signal: Repeater power supply operation
| Output description | Current output (active and passive) |
| Number of Outputs | 1 |
| Current Output Signal | 4 mA ... 20 mA (active) |
| Current Output Signal | 4 mA ... 20 mA (14 ... 26 V ext. source voltage) |
| Load/Output Load Current Output | < 1000 Ω (20 mA) |
| Load/Output Load Current Output | < 825 Ω (24 mA) |
| Output ripple | < 20 mVrms |
| Output behavior in the event of an error | 0 mA (Cable break in the input) |
| Output behavior in the event of an error | ≥ 22.5 mA (Cable short-circuit in the input) |
| Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Signal: Signal conditioner operation
| Output description | Current output (active and passive) |
| Current Output Signal | 0 mA ... 20 mA (active) |
| Current Output Signal | 4 mA ... 20 mA (active) |
| Current Output Signal | 0 mA ... 20 mA (14 ... 26 V ext. source voltage) |
| Current Output Signal | 4 mA ... 20 mA (14 ... 26 V ext. source voltage) |
| Load/Output Load Current Output | < 1000 Ω (20 mA) |
| Load/Output Load Current Output | < 825 Ω (24 mA) |
| Output ripple | < 20 mVrms |
| Output behavior in the event of an error | 0 mA (Cable break in the input) |
| Output behavior in the event of an error | 0 mA (Cable short-circuit in the input) |
| Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Connection data
| Connection Method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible (2 conductors with same cross section) | 0.25 mm² ... 0.34 mm² (TWIN ferrule without plastic sleeve) |
| Conductor cross section flexible (2 conductors with same cross section) | 0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) |
| Conductor cross section AWG | 24 ... 14 |
| Conductor cross section AWG | 24 ... 22 (TWIN ferrule without plastic sleeve) |
| Conductor cross section AWG | 20 ... 16 (TWIN ferrule with plastic sleeve) |
Ex data
| Ex installation (EPL) | Gc |
| Ex installation (EPL) | Div. 2 |
Data communication (bypass)
| HART Function | Yes |
| Protocols Supported | HART-transparent |
Signaling
| Status display | Green LED (supply voltage) |
Dimensions
| Width | 12.5 mm |
| Height | 107.9 mm |
| Depth | 113.7 mm |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Housing Material | PA 6.6-FR |
Ambient conditions
| Degree of Protection | IP20 (not assessed by UL) |
| Ambient Temperature (Operation) | -40 °C ... 60 °C (Any mounting position) |
| Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m)
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
| Ambient Temperature (Operation) | -40 °C ... 60 °C |
| Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
| Rated Insulation Voltage | 375 VPP (Power supply, input / output) |
Altitude range (≤ 3000 m)
| Height Range | > 2000 m ... 3000 m |
| Ambient Temperature (Operation) | -40 °C ... 54 °C |
| Ambient Temperature (Operation) | -40 °C ... 63 °C (Derating) |
| Rated Insulation Voltage | 190 V AC (Power supply, input / output) |
| Rated Insulation Voltage | 110 V DC (Power supply, input / output) |
Altitude range (≤ 4000 m)
| Height Range | > 3000 m ... 4000 m |
| Ambient Temperature (Operation) | -40 °C ... 48 °C |
| Ambient Temperature (Operation) | -40 °C ... 56 °C (Derating) |
| Rated Insulation Voltage | 60 V AC/DC (Power supply, input / output) |
Altitude range (≤ 5000 m)
| Height Range | > 4000 m ... 5000 m |
| Ambient Temperature (Operation) | -40 °C ... 42 °C |
| Ambient Temperature (Operation) | -40 °C ... 49 °C (Derating) |
| Rated Insulation Voltage | 60 V AC/DC (Power supply, input / output) |
CE
| Certificate | CE-compliant |
| Note | and EN 61326 |
ATEX
| Identification | II 3 G Ex ec IIC T4 Gc |
| Certificate | PxCIF08ATEX2865955X |
UKCA Ex (UKEX)
| Identification | II 3 G Ex nA IIC T4 Gc X |
| Certificate | PxCIF21UKEX2865955X |
IECEx
| Identification | Ex ec IIC T4 Gc |
| Certificate | IECEx BVS 08.0016X |
CCC / China-Ex
| Identification | Ex ec IIC T4 Gc |
| Certificate | 2022122304115127 |
UL, USA/Canada
| Identification | UL 61010 Listed |
| Identification | UL 508 Listed |
| Identification | Class I, Div. 2, Groups A, B, C, D T4 |
| Identification | Class I, Zone 2, Group IIC T4 |
Shipbuilding approval
| Certificate | DNV GL TAA000020C |
Safety Integrity Level (SIL, IEC 61508)
| Identification | 2 |
| Certificate | IN-AT-AS-MRL-2300149 |
Systematic Capability
| Identification | 3 |
INMETRO
| Identification | Ex ec IIC T4 Gc |
| Certificate | DNV 18.0136 X |
DNV GL data
| Temperature | B |
| Humidity | B |
| Vibration | A |
| EMC | A |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
| Noise immunity | EN 61000-6-2 |
| Note | When being exposed to interference, there may be minimal deviations. |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
Standards and Regulations
| Electrical isolation | 3-way isolation |
GB Standard
| Standards/regulations | GB/T 3836.1 |
| Standards/regulations | GB/T 3836.3 |
Mounting
| Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2924207?
Proax is an authorized distributor of Phoenix Contact 2924207 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended