Official Distributor
SKU
MPN
MINI MCR-2-TC-UI
Weight
0.124 kg
This product is Not Cancellable/Not Returnable
Series MINI-MCR
MINI MCR-2-TC-UI - Thermocouple measuring transducer
Configurable temperature transducer with plug-in connection technology for connecting thermocouples. Configurable via DIP switch or software. Screw connection technology, standard configuration
Technical Specifications
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
Product family | MINI Analog Pro |
Type | Signal conditioner |
Configuration | DIP switches |
Configuration | Software |
Configuration | App |
Insulation characteristics
Overvoltage category | II |
Pollution degree | 2 |
Electrical properties
Electrical isolation | 3-way isolation |
Typical cold point errors | 2 K (2 K + (0.2 K * ΔT)) |
Protective circuit | Transient protection |
Step response (0–99%) | 300 ms |
Step response (0–99%) | 570 ms |
Maximum temperature coefficient | ≤ 0.01 %/K |
Transmission error thermocouples | 0.1% * 600 K / set measuring range; 0.1% > 600 K (C, E, J, K, N, T, L, U, M Gost, L Gost) |
Transmission error thermocouples | 0.2 % * 600 K / set measuring range; 0.2 % > 600 K (B, R, S, A1, A2, A3) |
Transmission error thermocouples | 0.2% * 600 K / set measuring range; 0.2% > 600 K (E, J, K, N, T, L, U, M Gost, L Gost); Highspeed Mode |
Transmission error thermocouples | 0.4% * 600 K / set measuring range; 0.4% > 600 K (B, R, S, A1, A2, A3); Highspeed Mode |
Electrical isolation Input/output/power supply
Rated Insulation Voltage | 300 Vrms |
Test voltage | 3 kV AC (50 Hz, 60 s) |
Insulation | Reinforced insulation according to IEC/EN 61010-1 |
Supply
Supply Voltage Range | 9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
Typical current consumption | 32.7 mA (24 V DC) |
Typical current consumption | 66.8 mA (12 V DC) |
Power consumption | ≤ 850 mW (at IOUT = 20 mA, 9.6 V DC, 600 Ω load) |
Signal
Number of Inputs | 1 |
Measurement
Number of Inputs | 1 |
Configurable/programmable | Yes |
Input voltage range | - 500 mV ... 500 mV (can be set via software) |
Sensor types that can be used (TC) | B, C, E, J, K, N, R, S, T, L, U, A-1, A-2, A-3, M, L |
Temperature measuring range | -250 °C ... 2500 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 1350°C via DIP switches) |
Temperature measuring range | ≥ 50 K |
Voltage measuring range | 3 mV |
Sensor type: | 500 °C ... 1820 °C |
Sensor type: | -230 °C ... 1000 °C |
Sensor type: | -210 °C ... 1200 °C |
Sensor type: | -250 °C ... 1372 °C |
Sensor type: | -200 °C ... 1300 °C |
Sensor type: | -50 °C ... 1768 °C |
Sensor type: | -50 °C ... 1768 °C |
Sensor type: | -200 °C ... 400 °C |
Sensor type: | -200 °C ... 900 °C |
Sensor type: | -200 °C ... 600 °C |
Sensor type: | 0 °C ... 2500 °C |
Sensor type: | 0 °C ... 1800 °C |
Sensor type: | 0 °C ... 1800 °C |
Sensor type: | -200 °C ... 100 °C |
Sensor type: | -200 °C ... 800 °C |
Signal: Voltage/current
Number of Outputs | 1 |
Configurable/programmable | Yes |
Voltage output signal | 0 V ... 5 V (via DIP switch) |
Voltage output signal | 1 V ... 5 V (via DIP switch) |
Voltage output signal | 0 V ... 10 V (via DIP switch) |
Voltage output signal | 10 V ... 0 V (via DIP switch) |
Voltage output signal | 0 V ... 10.5 V (can be set via software) |
Max. voltage output signal | 12.3 V |
Non-load voltage | < 17.5 V |
Current Output Signal | 0 mA ... 20 mA (via DIP switch) |
Current Output Signal | 4 mA ... 20 mA (via DIP switch) |
Current Output Signal | 20 mA ... 0 mA (via DIP switch) |
Current Output Signal | 20 mA ... 4 mA (via DIP switch) |
Current Output Signal | 0 mA ... 21 mA (can be set via software) |
Max. current output signal | 24.6 mA |
Short-circuit current | < 31.5 mA |
Load/output load voltage output | ≥ 10 kΩ |
Load/Output Load Current Output | ≤ 600 Ω (20 mA) |
Ripple | < 10 mVrms |
Ripple | < 10 mVrms (600 Ω) |
Resolution, outputs (voltage) | 1 mV |
Resolution, outputs (current) | 2 µA |
Connection data
Connection Method | Screw connection |
Stripping length | 10 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² (with ferrule) |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² (without ferrule) |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 (flexible) |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Data: IFS interface
Connection Method | Micro USB type B |
Signaling
Status display | Green LED (supply voltage) |
Error indication | Red LED |
Dimensions
Width | 6.2 mm |
Height | 109.81 mm |
Depth | 119.2 mm |
Material specifications
Color | gray (RAL 7042) |
Housing Material | PBT |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Ambient conditions
Degree of Protection | IP20 (not assessed by UL) |
Ambient Temperature (Operation) | -40 °C ... 70 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE
Certificate | CE-compliant |
ATEX
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | BVS 20 ATEX E 024 X |
UKCA Ex (UKEX)
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | PxCIF21UKEX2902049X |
IECEx
Identification | Ex ec IIC T4 Gc |
Certificate | IECEx BVS 20.0017X |
UL, USA/Canada
Identification | UL 508 Listed |
Identification | Class I, Div. 2, Groups A, B, C, D T6 |
Identification | Class I, Zone 2, Group IIC T6 |
Shipbuilding approval
Certificate | DNV GL TAA00002UA |
EAC Ex
Identification | 2Ex ec IIC T4 Gc |
Certificate | BY/112 02.01 TP012 103.01 00079 |
DNV GL data
Temperature | B |
Humidity | B |
Vibration | A |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Comments | Safety measures must be taken to prevent electrostatic discharge. |
Electromagnetic HF field
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 0.06 % |
Fast transients (burst)
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 0.1 % |
Surge current load (surge)
Standards/regulations | EN 61000-4-5 |
Conducted interference
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 0.05 % |
Standards and Regulations
Electrical isolation | 3-way isolation |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail. |
Mounting Position | any |
Accessories
Why Proax for Phoenix Contact 2902055?
Proax is an authorized distributor of Phoenix Contact 2902055 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended