Official Distributor
SKU
MPN
MINI-PS-100-240AC/24DC/1.5/EX
Weight
0.289 kg
Series MINI-PS
MINI-PS-100-240AC/24DC/1.5/EX - Power supply unit
Please use the following item in new systems: 2904614Primary-switched MINI POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/1.5 A, for potentially explosive areas
- Easy-maintenance connection technology thanks to keyed COMBICON connectors
- For supplying the supply voltage via the foot element (DIN rail connector) where AC voltages are available
- 100 V AC ... 240 V AC nominal input voltage range
- 24 V DC output voltage
- For up to 60 MINI Analog modules
- For up to 1.5 A, secondary
- Status and error indication via diagnostic LEDs
Technical Specifications
AC operation
Nominal input voltage range | 100 V AC ... 240 V AC |
Input voltage range | 85 V AC ... 264 V AC |
Input Voltage Range AC | 85 V AC ... 264 V AC |
Voltage type of supply voltage | AC |
Inrush Current | < 15 A (typical) |
Inrush current integral (I2t) | 0.6 A2s |
AC frequency range | 45 Hz ... 65 Hz |
Mains buffering time | typ. 35 ms (120 V AC) |
Mains buffering time | typ. 150 ms (230 V AC) |
Current consumption | 0.75 A (120 V AC) |
Current consumption | 0.45 A (230 V AC) |
Nominal Power Consumption | 88 VA |
Typical response time | < 0.5 s |
Input fuse | 3.15 A (slow-blow, internal) |
Permissible backup fuse | B6 B10 B16 AC: |
Permissible DC backup fuse | DC: Connect a suitable fuse upstream |
Recommended breaker for input protection | 6 A ... 16 A (AC: Characteristics B, C, D, K) |
Output data
Efficiency | > 84 % (for 230 V AC and nominal values) |
Output characteristic | U/I |
Nominal Output Voltage | 24 V DC ±1 % |
Nominal output current (IN) | 1.5 A (-25 °C ... 60 °C) |
POWER BOOST (IBoost) | 2 A (-25 °C ... 40 °C) |
Derating | 60 °C ... 70 °C (2.5 %/K) |
Feedback voltage resistance | 35 V DC |
Residual ripple | < 40 mVPP (with nominal values) |
Output Power | 36 W |
Peak switching voltages nominal load | < 20 mVPP (20 MHz) |
Maximum no-load power dissipation | 1.5 W |
Power loss nominal load max. | 6.5 W |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Signal: DC OK active
Output description | UOUT > 0.9 x UN: High signal |
Maximum Switching Voltage | ≤ 24 V |
Output Voltage | + 24 V DC (Signal) |
Maximum Inrush Current | max. 44 mA |
Continuous load current | ≤ 40 mA |
Signal: DC OK floating
Output description | Relay contact, UOUT > 0.9 x UN: Contact closed |
Input
Connection Method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Output
Connection Method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signal
Conductor cross section, rigid min. | 0.5 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Screw thread | M4 |
Signaling
Types of signaling | LED |
Types of signaling | Relay contact |
Signal output: DC OK active
Status display | "DC OK" LED green |
Note on status display | UOUT < 0.9 x UN: LED flashing |
Signal output: DC OK floating
Status display | "DC OK" LED green |
Note on status display | UOUT > 21.5 V DC: LED ON |
Electrical properties
Insulation voltage input/output | 4 kV AC (type test) |
Insulation voltage input/output | 3 kV AC (routine test) |
Insulation voltage input / PE | 4 kV AC (type test) |
Insulation voltage input / PE | 3 kV AC (routine test) |
Product properties
Product family | MINI POWER |
MTBF (IEC 61709, SN 29500) | > 2789000 h (40 °C) |
Insulation characteristics
Protection class | II (in closed control cabinet) |
Overvoltage category | III |
Degree of pollution | 2 |
Dimensions
Width | 35 mm |
Height | 99 mm |
Depth | 95 mm |
Installation dimensions
Installation distance right/left | 0 mm / 0 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Mounting
Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
Material specifications
Type of housing | Polyamide PA, color: green |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Max. permissible relative humidity (operation) | 100 % (condensation permitted) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
Vibration (Operation) | 15 Hz ... 150 Hz, 2.3g, 90 min. |
Standards and Regulations
Rail applications | EN 50121-4 |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Standard – Safety extra-low voltage | EN 60950-1 (SELV) and EN 60204-1 (PELV) |
Standard - Safe isolation | DIN VDE 0100-410 |
Standards/specifications | EN 60079-0 |
Approvals
UL approvals | UL/C-UL listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
Conformity/Approvals
ATEX | II 3 G Ex nA nC IIC T4 Gc X |
SIL in accordance with IEC 61508 | 0 |
EMC data
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Accessories
Why Proax for Phoenix Contact 2866653?
Proax is an authorized distributor of Phoenix Contact 2866653 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended