Official Distributor
SKU
MPN
MINI-PS- 10- 42AC/15-60DC/3
Weight
0.211 kg
Series MINI-PS
MINI-PS- 10- 42AC/15-60DC/3 - Power module
The AC feed module supplies the MINI DC/DC converter with a rectified and filtered supply voltage.
- Enables the operation of the MINI DC/DC converters in an AC network.
- AC voltage of a transformer is rectified and filtered
Technical Specifications
Product properties
MTBF (IEC 61709, SN 29500) | > 18175000 h (40 °C) |
Insulation characteristics
Protection class | III |
Degree of pollution | 2 |
Electrical properties
Number of phases | 1.00 |
DC operation
Input Voltage | 24 V AC |
Nominal input voltage range | 10 V AC ... 42 V AC |
Input voltage range | 10 V AC ... 42 V AC |
Wide-range input | yes |
Input Voltage Range AC | 0 V AC ... 42 V AC |
Voltage type of supply voltage | AC |
Inrush Current | < 45 A (typical) |
Inrush current integral (I2t) | 8 A2s |
AC frequency range | 45 Hz ... 65 Hz |
Current consumption | 6.5 A |
Permissible backup fuse | C16 1 x circuit breaker |
Recommended breaker for input protection | 16 A (Characteristic C) |
Output data
Efficiency | > 95.7 % (For 42 V AC and nominal values) |
Nominal Output Voltage | 28 V DC ±1 % |
Nominal Output Voltage | 60 V DC |
Output voltage range | 15 V DC ... 60 V DC |
Nominal output current (IN) | 3 A (-25 °C ... 60 °C) |
Derating | 60 °C ... 70 °C (2.5 %/K) |
Residual ripple | < 3.6 VPP |
Output Power | 72 W |
Maximum no-load power dissipation | < 0.04 W |
Power loss nominal load max. | < 6.9 W |
Connection in series | No |
Input
Connection Method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Output
Connection Method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Dimensions
Width | 22.5 mm |
Height | 99 mm |
Depth | 107 mm |
Installation dimensions
Installation distance right/left | 0 mm / 0 mm (≤ 70 °C) |
Installation distance top/bottom | 50 mm / 50 mm (≤ 70 °C) |
Material specifications
Housing Material | Plastic |
Housing Material | Polyamide (PA) |
Type of housing | Polyamide PA, color: green |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
Vibration (Operation) | 15 Hz ... 150 Hz, 2.3g |
Approvals
UL approvals | UL/C-UL listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
Conformity/Approvals
SIL in accordance with IEC 61508 | 0 |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Noise immunity | EN 61000-6-2:2005 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 55011 (EN 55022) |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Housing | > Level 3 |
Contact discharge | 8 kV (Contact discharge) |
Discharge in air | 8 kV (Air discharge) |
Comments | Criterion B |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 3 GHz |
Test field strength | 10 V/m |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | 4 kV (level 4 - asymmetrical: conductor to ground) |
Output | 2 kV (level 3 - asymmetrical: conductor to ground) |
Signal | 1 kV (Level 2 - asymmetrical cable to ground) |
Comments | Criterion B |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 2 kV (Level 3) |
Input | 1 kV (Level 3) |
Standards and Regulations
Rail applications | EN 50121-4 |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Mounting
Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
With protective coating | No |
Why Proax for Phoenix Contact 2320199?
Proax is an authorized distributor of Phoenix Contact 2320199 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended