Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
MINI-PS- 10- 42AC/15-60DC/3
Weight
0.211 kg
Series MINI-PS

MINI-PS- 10- 42AC/15-60DC/3 - Power module

The AC feed module supplies the MINI DC/DC converter with a rectified and filtered supply voltage.

  • Enables the operation of the MINI DC/DC converters in an AC network.
  • AC voltage of a transformer is rectified and filtered
Technical Specifications

Product properties

MTBF (IEC 61709, SN 29500)> 18175000 h (40 °C)

Insulation characteristics

Protection classIII
Degree of pollution2

Electrical properties

Number of phases1.00

DC operation

Input Voltage24 V AC
Nominal input voltage range10 V AC ... 42 V AC
Input voltage range10 V AC ... 42 V AC
Wide-range inputyes
Input Voltage Range AC0 V AC ... 42 V AC
Voltage type of supply voltageAC
Inrush Current< 45 A (typical)
Inrush current integral (I2t)8 A2s
AC frequency range45 Hz ... 65 Hz
Current consumption6.5 A
Permissible backup fuseC16 1 x circuit breaker
Recommended breaker for input protection16 A (Characteristic C)

Output data

Efficiency> 95.7 % (For 42 V AC and nominal values)
Nominal Output Voltage28 V DC ±1 %
Nominal Output Voltage60 V DC
Output voltage range15 V DC ... 60 V DC
Nominal output current (IN)3 A (-25 °C ... 60 °C)
Derating60 °C ... 70 °C (2.5 %/K)
Residual ripple< 3.6 VPP
Output Power72 W
Maximum no-load power dissipation< 0.04 W
Power loss nominal load max.< 6.9 W
Connection in seriesNo

Input

Connection MethodPluggable screw connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length7 mm
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Output

Connection MethodPluggable screw connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length7 mm
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Dimensions

Width22.5 mm
Height99 mm
Depth107 mm

Installation dimensions

Installation distance right/left0 mm / 0 mm (≤ 70 °C)
Installation distance top/bottom50 mm / 50 mm (≤ 70 °C)

Material specifications

Housing MaterialPlastic
Housing MaterialPolyamide (PA)
Type of housingPolyamide PA, color: green

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Climatic class3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (Operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (Operation)15 Hz ... 150 Hz, 2.3g

Approvals

UL approvalsUL/C-UL listed UL 508
UL approvalsUL/C-UL Recognized UL 60950-1

Conformity/Approvals

SIL in accordance with IEC 615080

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
Noise immunityEN 61000-6-2:2005
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Noise emissionEN 55011 (EN 55022)

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Housing> Level 3
Contact discharge8 kV (Contact discharge)
Discharge in air8 kV (Air discharge)
CommentsCriterion B

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 3 GHz
Test field strength10 V/m
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input4 kV (level 4 - asymmetrical: conductor to ground)
Output2 kV (level 3 - asymmetrical: conductor to ground)
Signal1 kV (Level 2 - asymmetrical cable to ground)
CommentsCriterion B

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Input2 kV (Level 3)
Input1 kV (Level 3)

Standards and Regulations

Rail applicationsEN 50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard - Electrical safetyEN 60950-1/VDE 0805 (SELV)

Mounting

Assembly instructionsalignable: horizontally 0 mm, vertically 50 mm
Mounting Positionhorizontal DIN rail NS 35, EN 60715
With protective coatingNo

Why Proax for Phoenix Contact 2320199?

Proax is an authorized distributor of Phoenix Contact 2320199 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability