SKU
MPN
MACX MCR-IDS-I-I
Weight
0.171 kg
MACX MCR-IDS-I-I - Output signal conditioner
Output signal conditioner, HART-transparent. Isolates and transmits 0/4 mA ... 20 mA signals to a load in the safe area. 3-way electrical isolation, line fault detection (can be switched off via DIP switch), SIL 2 (SC3) in accordance with IEC 61508, screw connection.
Technical Specifications
Product properties
Product family | MACX Analog |
No. of channels | 1 |
Type | Signal conditioners with SIL functional safety |
Configuration | DIP switches |
Functionality
Configuration | DIP switches |
Electrical properties
Electrical isolation | 3-way isolation |
Signal transmission behavior | In = Out |
Step response (10-90%) | < 140 µs (for 4 mA ... 20 mA step) |
Maximum temperature coefficient | 0.01 %/K |
Temperature coefficient, typical | ≤ 0.005 %/K |
Maximum transmission error | 0.1 % (of final value) |
Transmission error, typical | ≤ 0.05 % (of final value) |
Electrical isolation
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation Input/output IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation |
Electrical isolation Input/power supply IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 50 Vrms |
Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Insulation | Basic insulation |
Electrical isolation Output/supply IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation |
Supply
Nominal Supply Voltage | 24 V DC -20 % ... +25 % |
Supply Voltage Range | 19.2 V DC ... 30 V DC |
Max. current consumption | < 45 mA (24 V DC / 20 mA) |
Power dissipation | < 0.8 W (24 V DC / 20 mA) |
Power consumption | ≤ 1.1 W (24 V DC / 20 mA) |
Signal: Current
Current Input Signal | 0 mA ... 20 mA (Function (short-circuit detection off)) |
Current Input Signal | 0.2 mA ... 20 mA (Function (short-circuit detection on)) |
Current Input Signal | 4 mA ... 20 mA (Safety) |
Current Input Signal | 0 mA ... 24 mA (Underload/overload range) |
Input Current | ≤ 30 mA |
Input Impedance | > 1 MΩ (If there is a line fault) |
Line fault detection | > 0.2 mA (Response threshold of input current) |
Voltage drop | < 2.4 V (at 20 mA) |
Number of Outputs | 1 |
Current Output Signal | 0 mA ... 20 mA (Function (short-circuit detection off)) |
Current Output Signal | 0.2 mA ... 20 mA (Function (short-circuit detection on)) |
Current Output Signal | 4 mA ... 20 mA (Safety) |
Current Output Signal | 0 mA ... 24 mA (Underload/overload range) |
Load | 100 Ω ... 700 Ω (20 mA (short-circuit detection on)) |
Load | 100 Ω ... 650 Ω (20.5 mA (short-circuit detection on)) |
Load | 100 Ω ... 500 Ω (24 mA (short-circuit detection on)) |
Load | 0 Ω ... 700 Ω (20 mA (short-circuit detection off)) |
Load | 0 Ω ... 650 Ω (20.5 mA (short-circuit detection off)) |
Load | 0 Ω ... 500 Ω (24 mA (short-circuit detection off)) |
Output ripple | < 20 mVrms |
Non-load voltage | ≤ 27 V |
Line fault detection | > 10 kΩ (Line break) |
Line fault detection | < 50 Ω (Short circuit) |
Connection data
Connection Method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
COMBICON connection
Max. diameter | 2 mm |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Data communication (bypass)
HART Function | Yes |
Protocols Supported | HART-transparent |
Signaling
Status display | Green LED (supply voltage) |
Dimensions
Width | 12.5 mm |
Height | 112.5 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing Material | PA 6.6-FR |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Any mounting position) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m (Ex))
Description | Ex applications |
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient Temperature (Operation) | -40 °C ... 70 °C |
Rated Insulation Voltage | 320 V (Power supply, input / output) |
Altitude range (≤ 3000 m (Ex))
Description | Ex applications |
Height Range | > 2000 m ... 3000 m |
Ambient Temperature (Operation) | -40 °C ... 60 °C |
Rated Insulation Voltage | 190 V (Power supply, input / output) |
Altitude range (≤ 4000 m (Ex))
Description | Ex applications |
Height Range | > 3000 m ... 4000 m |
Ambient Temperature (Operation) | -40 °C ... 55 °C |
Rated Insulation Voltage | 63 V (Power supply, input / output) |
Altitude range (≤ 5000 m (Ex))
Description | Ex applications |
Height Range | > 4000 m ... 5000 m |
Ambient Temperature (Operation) | -40 °C ... 45 °C |
Rated Insulation Voltage | 63 V (Power supply, input / output) |
Altitude range (≤ 2000 m)
Description | Non-Ex applications (EN 61010-1) |
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient Temperature (Operation) | -40 °C ... 70 °C |
Rated Insulation Voltage | 300 V (Power supply, input / output) |
Altitude range (≤ 3000 m)
Description | Non-Ex applications (EN 61010-1) |
Height Range | > 2000 m ... 3000 m |
Ambient Temperature (Operation) | -40 °C ... 60 °C |
Rated Insulation Voltage | 150 V (Power supply, input / output) |
Altitude range (≤ 4000 m)
Description | Non-Ex applications (EN 61010-1) |
Height Range | > 3000 m ... 4000 m |
Ambient Temperature (Operation) | -40 °C ... 55 °C |
Rated Insulation Voltage | 150 V (Power supply, input / output) |
Altitude range (≤ 5000 m)
Description | Non-Ex applications (EN 61010-1) |
Height Range | > 4000 m ... 5000 m |
Ambient Temperature (Operation) | -40 °C ... 45 °C |
Rated Insulation Voltage | 150 V (Power supply, input / output) |
CE
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | BVS 20 ATEX E 003 X |
UKCA Ex (UKEX)
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | PxCIF21UKEx2908065X |
IECEx
Identification | Ex ec IIC T4 Gc |
Certificate | IECEx BVS 20.0003X |
CCC / China-Ex
Identification | Ex ec IIC T4 Gc |
Certificate | 2021122304114079 |
UL, USA/Canada
Identification | UL 61010 Listed |
Identification | Class I, Div. 2, Groups A, B, C, D T4 |
Identification | Class I, Zone 2, Group IIC T4 |
Shipbuilding approval
Certificate | DNV GL TAA00000AG |
Safety Integrity Level (SIL, IEC 61508)
Identification | 2 |
Systematic Capability
Identification | 3 |
INMETRO
Identification | Ex ec IIC T4 Gc |
Certificate | DNV 21.0092 X |
EAC
Identification | 2Ex e IIC T4 Gc X |
Certificate | RU C-DE.HB49.B.00145/21 |
DNV GL data
Temperature | B |
Humidity | B |
Vibration | A |
EMC | B |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Standards and Regulations
Electrical isolation | 3-way isolation |
GB Standard
Standards/regulations | GB/T 3836.1 |
Standards/regulations | GB/T 3836.3 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2908063?
Proax is an authorized distributor of Phoenix Contact 2908063 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- MACX MCR-EX-IDS-I-I-SP - Ex i output signal conditioner, HART-transparent. Isolates and transmits 0/4 mA … 20 mA signals with intrinsic safety to a load in the Ex area. 3-way electrical isolation, line fault detection (can be switched off via DIP switch), SIL 2 (SC3) in accordance with IEC 61508, Push-in connection.