SKU
MPN
MACX MCR-EX-I20
Weight
0.03 kg
MACX MCR-EX-I20 - Plug
Connection terminal block for current signals +20 mA ...-20 mA for safe switching of limit values, in combination with MACX...EX-T-UI... temperature transducers.
Technical Specifications
Electrical properties
Maximum transmission error | 1.1 % |
Connection data
Connection Method | Screw connection |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Safety data
Input voltage Ui | 30 V |
Input current Ii | 112 mA |
Input power Pi | 840 mW |
Max. internal inductance Li | negligible |
Max. internal capacitance Ci | 44 nF |
Max. output voltage Uo | 6 V |
Max. output current Io | 7.4 mA |
Max. output power Po | 11 mW |
Ambient conditions
Ambient Temperature (Operation) | -20 °C ... 65 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | typ. 5 % ... 95 % (non-condensing) |
CE
Certificate | CE-compliant |
ATEX
Identification | II (1) G [Ex ia] IIC |
Identification | II (1) D [Ex ia Da] IIIC |
Identification | II 3 G Ex nA nC ic IIC T4 Gc X |
Certificate | IBExU 10 ATEX 1044 |
Why Proax for Phoenix Contact 2905679?
Proax is an authorized distributor of Phoenix Contact 2905679 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- MACX MCR-EX-IDS-I-I-SP - Ex i output signal conditioner, HART-transparent. Isolates and transmits 0/4 mA … 20 mA signals with intrinsic safety to a load in the Ex area. 3-way electrical isolation, line fault detection (can be switched off via DIP switch), SIL 2 (SC3) in accordance with IEC 61508, Push-in connection.