By Phoenix Contact

SKU
MPN
MACX MCR-EX-IDS-I-I-SP
Weight
0.165 kg
This product is Not Cancellable/Not Returnable

MACX MCR-EX-IDS-I-I-SP - Output signal conditioner

Ex i output signal conditioner, HART-transparent. Isolates and transmits 0/4 mA … 20 mA signals with intrinsic safety to a load in the Ex area. 3-way electrical isolation, line fault detection (can be switched off via DIP switch), SIL 2 (SC3) in accordance with IEC 61508, Push-in connection.

Technical Specifications

Product properties

Product familyMACX Analog
No. of channels1
TypeEx i signal conditioners with SIL functional safety
ConfigurationDIP switches

Functionality

ConfigurationDIP switches

Electrical properties

Electrical isolation3-way isolation
Signal transmission behaviorIn = Out
Step response (10-90%)< 140 µs (for 4 mA ... 20 mA step)
Maximum temperature coefficient0.01 %/K
Temperature coefficient, typical≤ 0.005 %/K
Maximum transmission error0.1 % (of final value)
Transmission error, typical≤ 0.05 % (of final value)

Electrical isolation

Overvoltage categoryII
Pollution degree2

Electrical isolation Input/output IEC/EN 61010-1

Standards/regulationsIEC/EN 61010-1
Rated Insulation Voltage300 Vrms
Test voltage2.5 kV AC (50 Hz, 60 s)
InsulationSafe isolation

Electrical isolation Input/power supply IEC/EN 61010-1

Standards/regulationsIEC/EN 61010-1
Rated Insulation Voltage50 Vrms
Test voltage1.5 kV AC (50 Hz, 60 s)
InsulationBasic insulation

Electrical isolation Output/supply IEC/EN 61010-1

Standards/regulationsIEC/EN 61010-1
Rated Insulation Voltage300 Vrms
Test voltage2.5 kV AC (50 Hz, 60 s)
InsulationSafe isolation

Electrical isolation Output/input IEC/EN 60079-11

Standards/regulationsIEC/EN 60079-11
Rated Insulation Voltage375 VPP

Electrical isolation Output/supply IEC/EN 60079-11

Standards/regulationsIEC/EN 60079-11
Rated Insulation Voltage375 VPP

Supply

Nominal Supply Voltage24 V DC -20 % ... +25 %
Supply Voltage Range19.2 V DC ... 30 V DC
Max. current consumption< 45 mA (24 V DC / 20 mA)
Power dissipation< 0.8 W (24 V DC / 20 mA)
Power consumption≤ 1.1 W (24 V DC / 20 mA)

Signal: Current

Current Input Signal0 mA ... 20 mA (Function (short-circuit detection off))
Current Input Signal0.2 mA ... 20 mA (Function (short-circuit detection on))
Current Input Signal4 mA ... 20 mA (Safety)
Current Input Signal0 mA ... 24 mA (Underload/overload range)
Input Current≤ 30 mA
Input Impedance> 1 MΩ (If there is a line fault)
Line fault detection> 0.2 mA (Response threshold of input current)
Voltage drop< 2.4 V (at 20 mA)
Output descriptionintrinsically safe
Number of Outputs1
Current Output Signal0 mA ... 20 mA (Function (short-circuit detection off))
Current Output Signal0.2 mA ... 20 mA (Function (short-circuit detection on))
Current Output Signal4 mA ... 20 mA (Safety)
Current Output Signal0 mA ... 24 mA (Underload/overload range)
Load100 Ω ... 700 Ω (20 mA (short-circuit detection on))
Load100 Ω ... 650 Ω (20.5 mA (short-circuit detection on))
Load100 Ω ... 500 Ω (24 mA (short-circuit detection on))
Load0 Ω ... 700 Ω (20 mA (short-circuit detection off))
Load0 Ω ... 650 Ω (20.5 mA (short-circuit detection off))
Load0 Ω ... 500 Ω (24 mA (short-circuit detection off))
Output ripple< 20 mVrms
Non-load voltage≤ 27 V
Line fault detection> 10 kΩ (Line break)
Line fault detection< 50 Ω (Short circuit)

Connection data

Connection MethodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section flexible (2 conductors with same cross section)0.25 mm² ... 0.34 mm² (TWIN ferrule without plastic sleeve)
Conductor cross section flexible (2 conductors with same cross section)0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve)
Conductor cross section AWG24 ... 14
Conductor cross section AWG24 ... 22 (TWIN ferrule without plastic sleeve)
Conductor cross section AWG20 ... 16 (TWIN ferrule with plastic sleeve)

Ex data

Ex installation (EPL)Gc
Ex installation (EPL)Div. 2
Ex i circuits (EPL)Ga
Ex i circuits (EPL)Da
Ex i circuits (EPL)Ma
Ex i circuits (EPL)Div. 1

Safety data

Max. internal inductance Linegligible
Max. internal capacitance Cinegligible
Max. output voltage Uo25.2 V
Max. output current Io93 mA
Max. output power Po586 mW
Safety-related maximum voltage Um253 V AC
Safety-related maximum voltage Um125 V DC
IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co10 mH / 2.9 µF
IIB (simple circuit): Max. external inductivity Lo / Max. external capacitance Co4 mH / 817 nF
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co2 mH / 104 nF
IIA (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co10 mH / 587 nF, 1 mH / 627 nF, 500 µH / 717 nF, 200 µH / 907 nF, 100 µH / 1.1 µF
IIB (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co4 mH / 367 nF, 1 mH / 427 nF, 500 µH / 507 nF, 200 µH / 657 nF, 100 µH / 817 nF
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co2 mH / 46 nF, 1 mH / 60 nF, 500 µH / 77 nF, 200 µH / 104 nF

Data communication (bypass)

HART FunctionYes
Protocols SupportedHART-transparent

Signaling

Status displayGreen LED (supply voltage)

Dimensions

Width12.5 mm
Height107.9 mm
Depth113.7 mm
Depth NS 35/7,5114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)

Material specifications

Colorgray (RAL 7042)
Flammability rating according to UL 94V0 (Housing)
Housing MaterialPA 6.6-FR

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-40 °C ... 70 °C (Any mounting position)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)

Altitude range (≤ 2000 m (Ex))

DescriptionEx applications
Altitude≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.)
Ambient Temperature (Operation)-40 °C ... 70 °C
Safety-related maximum voltage Um253 V AC
Safety-related maximum voltage Um125 V DC
Rated Insulation Voltage320 V (Power supply, input / output)

Altitude range (≤ 3000 m (Ex))

DescriptionEx applications
Height Range> 2000 m ... 3000 m
Ambient Temperature (Operation)-40 °C ... 60 °C
Safety-related maximum voltage Um190 V AC
Safety-related maximum voltage Um110 V DC
Rated Insulation Voltage190 V (Power supply, input / output)

Altitude range (≤ 4000 m (Ex))

DescriptionEx applications
Height Range> 3000 m ... 4000 m
Ambient Temperature (Operation)-40 °C ... 55 °C
Safety-related maximum voltage Um60 V AC
Safety-related maximum voltage Um60 V DC
Rated Insulation Voltage63 V (Power supply, input / output)

Altitude range (≤ 5000 m (Ex))

DescriptionEx applications
Height Range> 4000 m ... 5000 m
Ambient Temperature (Operation)-40 °C ... 45 °C
Safety-related maximum voltage Um60 V AC
Safety-related maximum voltage Um60 V DC
Rated Insulation Voltage63 V (Power supply, input / output)

Altitude range (≤ 2000 m)

DescriptionNon-Ex applications (EN 61010-1)
Altitude≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.)
Ambient Temperature (Operation)-40 °C ... 70 °C
Rated Insulation Voltage300 V (Power supply, input / output)

Altitude range (≤ 3000 m)

DescriptionNon-Ex applications (EN 61010-1)
Height Range> 2000 m ... 3000 m
Ambient Temperature (Operation)-40 °C ... 60 °C
Rated Insulation Voltage150 V (Power supply, input / output)

Altitude range (≤ 4000 m)

DescriptionNon-Ex applications (EN 61010-1)
Height Range> 3000 m ... 4000 m
Ambient Temperature (Operation)-40 °C ... 55 °C
Rated Insulation Voltage150 V (Power supply, input / output)

Altitude range (≤ 5000 m)

DescriptionNon-Ex applications (EN 61010-1)
Height Range> 4000 m ... 5000 m
Ambient Temperature (Operation)-40 °C ... 45 °C
Rated Insulation Voltage150 V (Power supply, input / output)

CE

CertificateCE-compliant
Noteand EN 61326

ATEX

Identification I (M1) [Ex ia Ma] I
Identification II (1) G [Ex ia Ga] IIC
Identification II (1) D [Ex ia Da] IIIC
Identification II 3(1) G Ex ec [ia Ga] IIC T4 Gc
CertificateBVS 20 ATEX E 004 X

IECEx

Identification[Ex ia Ma] I
Identification[Ex ia Ga] IIC
Identification[Ex ia Da] IIIC
IdentificationEx ec [ia Ga] IIC T4 Gc
CertificateIECEx BVS 20.0003X

CCC / China-Ex

Identification[Ex ia Ga] IIC
Identification[Ex ia Da] IIIC
IdentificationEx ec [ia Ga] IIC T4 Gc
Certificate2021122316114080

UL, USA/Canada

IdentificationUL 61010 Listed
IdentificationClass I Div 2; IS for Class I, II, III Div 1
Certificate, C.D.-No 83104549

Shipbuilding approval

CertificateDNV GL TAA00000AG

Safety Integrity Level (SIL, IEC 61508)

Identification2

Systematic Capability

Identification3

INMETRO

Identification[Ex ia Ma] I
Identification[Ex ia Ga] IIC
Identification[Ex ia Da] IIIC
IdentificationEx ec [ia Ga] IIC T4 Gc
CertificateDNV 21.0092 X

DNV GL data

TemperatureB
HumidityB
VibrationA
EMCB
EnclosureRequired protection according to the Rules shall be provided upon installation on board

EMC data

Noise immunityEN 61000-6-2
NoteWhen being exposed to interference, there may be minimal deviations.
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4

Standards and Regulations

Electrical isolation3-way isolation

GB Standard

Standards/regulationsGB/T 3836.1
Standards/regulationsGB/T 3836.3
Standards/regulationsGB/T 3836.4

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact 2908062?

Proax is an authorized distributor of Phoenix Contact 2908062 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability