SKU
MPN
MACX MCR-EX-SL-NAM-2RO
Weight
0.183 kg
This product is Not Cancellable/Not Returnable
Series MACX-MCR-EX-SL-NAM
MACX MCR-EX-SL-NAM-2RO - Isolation amplifier
Ex i NAMUR isolating amplifier For operating proximity sensors and switches in Ex areas. The signals are transmitted via 2 relay outputs (N/O contact) to the safe area. Line fault detection (LFD), 3-way isolation, SIL 2.
- Power supply and error indication possible via DIN rail connector
- Installation in zone 2, protection type "n" (EN 60079-15) permitted
- Up to SIL 2 in accordance with EN 61508
- Line fault detection (LFD), can be activated/deactivated, error indicated by flashing red LED with de-excitation of output relay
- 4-way electrical isolation
- Direction of operation can be selected (operating or closed circuit current behavior)
- 2 relay signal outputs (N/O contact); output 2 can also be used as an error signaling output
- Input for NAMUR proximity sensors (EN 60947-5-6), floating contacts or contacts with resistance circuit, [Ex ia] IIC
- LED indicators for supply voltage, switching state, and malfunction in accordance with NAMUR NE 44
Technical Specifications
Product properties
Product family | MACX Analog |
Application | Digital IN |
No. of channels | 1 |
Type | Ex i signal conditioners with SIL functional safety |
Configuration | DIP switches |
Functionality
Configuration | DIP switches |
Electrical properties
Electrical isolation | 3-way isolation |
Electrical isolation between input and output | yes |
Electrical isolation Input/output IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 375 VPP |
Overvoltage category | III |
Pollution degree | 2 |
Electrical isolation Input/supply, DIN rail connector IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 375 VPP |
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation Input/supply, DIN rail connector IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Overvoltage category | II |
Pollution degree | 2 |
Insulation | Safe isolation |
Electrical isolation Output 1/output 2/input, power supply, DIN rail connector IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Overvoltage category | III |
Pollution degree | 2 |
Insulation | Safe isolation |
Electrical isolation Output 1/output 2/input/power supply, DIN rail connector
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Overvoltage category | III |
Pollution degree | 2 |
Supply
Nominal Supply Voltage | 24 V DC -20 % ... +25 % |
Supply Voltage Range | 19.2 V DC ... 30 V DC |
Max. current consumption | 30 mA (24 V DC) |
Power dissipation | < 1 W |
Power consumption | < 1 W |
Signal: NAMUR
Description of the input | Intrinsically safe |
Number of Inputs | 1 |
Available Input Sources | NAMUR proximity sensors (IEC/EN 60947-5-6) |
Available Input Sources | Floating switch contacts |
Available Input Sources | Switch contacts with resistance circuit |
Switching threshold "0" signal current | < 1.2 mA (blocking) |
Switching threshold "1" signal, current | > 2.1 mA (conductive) |
Short-circuit current | 8 mA |
Switching hysteresis | < 0.2 mA |
Line fault detection | < 0.05 mA ... 0.35 mA (Line break) |
Line fault detection | < 100 Ω ... 360 Ω (Short circuit) |
Line fault detection | Activated /deactivated via DIP switch |
Non-load voltage | 8 V DC |
Switching: Relay
Contact switching type | 2 N/O contacts |
Contact Material | AgSnO2, hard gold-plated |
Maximum Switching Voltage | 250 V AC (2 A) |
Maximum Switching Voltage | 120 V DC (0.2 A) |
Maximum Switching Voltage | 30 V DC (2 A) |
Maximum switching capacity | 500 VA |
Recommended minimum load | 5 V / 10 mA |
Switching frequency | ≤ 20 Hz (without load) |
Signal
Number of Outputs | 2 |
Connection data
Connection Method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Test socket
Max. diameter | 2 mm |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Ex i circuits (EPL) | Ga |
Ex i circuits (EPL) | Da |
Ex i circuits (EPL) | Ma |
Ex i circuits (EPL) | Div. 1 |
Safety data
Max. internal inductance Li | negligible |
Max. internal capacitance Ci | 11 nF |
Max. output voltage Uo | 9.6 V |
Max. output current Io | 10 mA |
Max. output power Po | 25 mW |
Safety-related maximum voltage Um | 253 V AC |
Safety-related maximum voltage Um | 125 V DC |
IIA/I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 1000 mH / 210 µF |
IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 1000 mH / 26 µF |
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 300 mH / 3.6 µF |
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 500 nF, 50 mH / 570 nF, 5 mH / 590 nF, 1 mH / 590 nF, 10 µH / 590 nF |
I/IIB/IIA/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 1 µF, 5 mH / 1 µF, 1 mH / 1 µF, 10 µH / 1 µF |
Signaling
Status display | Green LED (supply voltage) |
Status display | LED yellow (switching state) |
Status display | Red LED (line errors) |
Dimensions
Width | 12.5 mm |
Height | 112.5 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing Material | PA 6.6-FR |
Ambient conditions
Degree of Protection | IP20 (not assessed by UL) |
Ambient Temperature (Operation) | -40 °C ... 60 °C (Any mounting position) |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m)
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient Temperature (Operation) | -40 °C ... 60 °C |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
Rated Insulation Voltage | 253 V AC (Power supply, input / output) |
Rated Insulation Voltage | 125 V DC (Power supply, input / output) |
Altitude range (≤ 3000 m)
Height Range | > 2000 m ... 3000 m |
Ambient Temperature (Operation) | -40 °C ... 54 °C |
Ambient Temperature (Operation) | -40 °C ... 63 °C (Derating) |
Rated Insulation Voltage | 190 V AC (Power supply, input / output) |
Rated Insulation Voltage | 110 V DC (Power supply, input / output) |
Altitude range (≤ 4000 m)
Height Range | > 3000 m ... 4000 m |
Ambient Temperature (Operation) | -40 °C ... 48 °C |
Ambient Temperature (Operation) | -40 °C ... 56 °C (Derating) |
Rated Insulation Voltage | 60 V AC/DC (Power supply, input / output) |
Altitude range (≤ 5000 m)
Height Range | > 4000 m ... 5000 m |
Ambient Temperature (Operation) | -40 °C ... 42 °C |
Ambient Temperature (Operation) | -40 °C ... 49 °C (Derating) |
Rated Insulation Voltage | 60 V AC/DC (Power supply, input / output) |
CE
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX
Identification | II (1) G [Ex ia Ga] IIC |
Identification | II (1) D [Ex ia Da] IIIC |
Identification | II 3 (1) G Ex ec [ia Ga] nC IIC T4 Gc |
Identification | I (M1) [Ex ia Ma] I |
Certificate | IBExU 07 ATEX 1069 X |
UKCA Ex (UKEX)
Identification | II (1) G [Ex ia Ga] IIC |
Identification | II (1) D [Ex ia Da] IIIC |
Identification | II 3 (1) G Ex ec [ia Ga] nC IIC T4 Gc |
Identification | I (M1) [Ex ia Ma] I |
Certificate | CML 22UKEX7421X |
IECEx
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia Ga] nC IIC T4 Gc |
Identification | [Ex ia Ma] I |
Certificate | IECEx IBE 08.0001X |
CCC / China-Ex
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec nC [ia Ga] IIC T4 Gc |
Certificate | 2022122316115975 |
UL, USA/Canada
Identification | UL 61010 Listed |
Identification | Class I, Div. 2, Groups A, B, C, D T4 |
Identification | Class I, Div. 2, Groups IIC, IIB, IIA T4 |
Identification | Associated apparatus for use in Class I, Division 1, Groups A,B,C,D |
Identification | Associated apparatus for use in Class II, Div.1 Groups E,F,G |
Identification | Associated apparatus for use in Class III, Division 1 |
Identification | Associated apparatus for use in Class I, Zone 0,1,2, Groups IIC,IIB,IIA |
Certificate | , C.D.-No 83104549 |
Identification | Class I Div 2; IS for Class I, II, III Div 1 |
Identification | UL 61010 Listed |
Certificate | , C.D.-No 83104549 |
KC-s
Identification | [Ex ia] IIC/IIB |
Certificate | 17-KA4BO-0409X |
Shipbuilding approval
Certificate | DNV GL TAA00000AG |
Safety Integrity Level (SIL, IEC 61508)
Identification | 2 |
INMETRO
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec nC [ia Ga] IIC T4 Gc |
Identification | [Ex ia Ma] I |
Certificate | DNV 18.0114 X |
DNV GL data
Temperature | B |
Humidity | B |
Vibration | A |
EMC | B |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Noise immunity | EN 61000-6-2 |
Noise immunity | EN 61326 |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Standards and Regulations
Electrical isolation | 3-way isolation |
GB Standard
Standards/regulations | GB/T 3836.1 |
Standards/regulations | GB/T 3836.3 |
Standards/regulations | GB/T 3836.4 |
Standards/regulations | GB/T 3836.8 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2865450?
Proax is an authorized distributor of Phoenix Contact 2865450 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended