MACX MCR-EX-SL-NAM-NAM-SP - Isolation amplifier
Ex i NAMUR signal conditioner for operating Ex i proximity sensors and switches in the Ex area. Passive transistor output (resistive in accordance with EN 60947-5-6), line fault transparency, up to SIL 2 in accordance with IEC 61508, Push-in connection
- Signal input: intrinsically safe [Ex ia]; for NAMUR proximity sensors (EN 60947-5-6) or switch contacts
- Signal output with resistive behavior (transistor), according to EN 60947-5-6
- Signal output with line fault transparency, line fault indication directly via the signal output to SPS or PLS
- Up to 5 kHz switching frequency
- Direction of operation can be selected
- Line fault detection (LFD) can be enabled and disabled
- SIL 2 according to IEC/EN 61508
- 3-way electrical isolation
- Power supply and error indication possible via DIN rail connector
- Plug-in connection terminals, push-in connection technology
- Installation in zone 2 permitted
- Housing width: 12.5 mm
Technical Specifications
Utilization restriction
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
| Product family | MACX Analog |
| No. of channels | 1 |
| Type | Ex i signal conditioners with SIL functional safety |
| Configuration | DIP switches |
Insulation characteristics: GB Standard
| Overvoltage category | II |
| Pollution degree | 2 |
Functionality
| Configuration | DIP switches |
Electrical properties
| Electrical isolation | 3-way isolation |
| Electrical isolation between input and output | yes |
Electrical isolation Input/output
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
Electrical isolation Input/output/supply, DIN rail connector
| Rated Insulation Voltage | 300 Vrms |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) |
| Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
Electrical isolation Input/supply, DIN rail connector
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
Supply
| Nominal Supply Voltage | 24 V DC |
| Supply Voltage Range | 9.6 V DC ... 30 V DC (12 V DC ... 24 V DC (-20 % ... +25 %)) |
| Power dissipation | < 0.6 W |
| Power consumption | < 600 mW |
Signal: NAMUR
| Description of the input | Intrinsically safe |
| Number of Inputs | 1 |
| Available Input Sources | NAMUR proximity sensors (IEC/EN 60947-5-6) |
| Available Input Sources | Floating switch contacts |
| Available Input Sources | Switch contacts with resistance circuit |
| Switching threshold "0" signal current | < 1.2 mA (blocking) |
| Switching threshold "1" signal, current | > 2.1 mA (conductive) |
| Switching hysteresis | < 0.2 mA |
| Line fault detection | < 0.05 mA ... 0.35 mA (Line break) |
| Line fault detection | < 100 Ω ... 360 Ω (Short circuit) |
| Line fault detection | Activated /deactivated via DIP switch |
| Non-load voltage | 8 V DC ±10 % |
Switching: Transistor
| Output description | passive |
| Switching frequency | 5 kHz |
Signal
| Number of Outputs | 1 |
Connection data
| Connection Method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
Test socket
| Max. diameter | 2.3 mm |
Ex data
| Ex installation (EPL) | Gc |
| Ex installation (EPL) | Div. 2 |
| Ex i circuits (EPL) | Ga |
| Ex i circuits (EPL) | Da |
| Ex i circuits (EPL) | Ma |
| Ex i circuits (EPL) | Div. 1 |
Safety data
| Max. internal inductance Li | negligible |
| Max. internal capacitance Ci | negligible |
| Max. output voltage Uo | 9.6 V |
| Max. output current Io | 10 mA |
| Max. output power Po | 25 mW |
| Safety-related maximum voltage Um | 253 V AC |
| Safety-related maximum voltage Um | 125 V DC |
| IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 1000 mH / 210 µF |
| IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 1000 mH / 26 µF |
| IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 300 mH / 3.6 µF |
| IIB/IIA/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 1 µF, 5 mH / 1 µF, 1 mH / 1 µF, 10 µH / 1 µF |
| IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 510 nF, 50 mH / 580 nF, 5 mH / 600 nF, 1 mH / 600 nF, 10 µH / 600 nF |
Data
| No. of channels | 0 |
Signaling
| Status display | Green LED (supply voltage) |
| Status display | LED yellow (switching state) |
| Status display | Red LED (line errors) |
Dimensions
| Width | 12.5 mm |
| Height | 116 mm |
| Depth | 113.7 mm |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Housing Material | PA 6.6-FR |
Safety data
| Safety Integrity Level (SIL) | 2 |
| Safety Integrity Level (SIL) | 2 |
Ambient conditions
| Degree of Protection | IP20 (not assessed by UL) |
| Ambient Temperature (Operation) | -40 °C ... 70 °C (Any mounting position) |
| Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m)
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
| Ambient Temperature (Operation) | -40 °C ... 60 °C |
| Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
| Rated Insulation Voltage | 265 V AC/DC (UIsolation “ec”: Supply, input / output) |
Altitude range (≤ 3000 m)
| Height Range | > 2000 m ... 3000 m |
| Ambient Temperature (Operation) | -40 °C ... 54 °C |
| Ambient Temperature (Operation) | -40 °C ... 63 °C (Derating) |
| Safety-related maximum voltage Um | 190 V AC |
| Safety-related maximum voltage Um | 110 V DC |
| Rated Insulation Voltage | 190 V AC/DC (UIsolation “ec”: Supply, input / output) |
Altitude range (≤ 4000 m)
| Height Range | > 3000 m ... 4000 m |
| Ambient Temperature (Operation) | -40 °C ... 48 °C |
| Ambient Temperature (Operation) | -40 °C ... 56 °C (Derating) |
| Safety-related maximum voltage Um | 60 V |
| Rated Insulation Voltage | 60 V AC/DC (UIsolation “ec”: Supply, input / output) |
Altitude range (≤ 5000 m)
| Height Range | > 4000 m ... 5000 m |
| Ambient Temperature (Operation) | -40 °C ... 42 °C |
| Ambient Temperature (Operation) | -40 °C ... 49 °C (Derating) |
| Safety-related maximum voltage Um | 60 V |
| Rated Insulation Voltage | 60 V AC/DC (UIsolation “ec”: Supply, input / output) |
CE
| Certificate | CE-compliant |
| Note | and EN 61326 |
ATEX
| Identification | II (1) G [Ex ia Ga] IIC |
| Identification | II (1) D [Ex ia Da] IIIC |
| Identification | II 3(1) G Ex ec [ia Ga] IIC T4 Gc |
| Identification | I (M1) [Ex ia Ma] I |
| Certificate | IBExU 08 ATEX 1100 X |
UKCA Ex (UKEX)
| Identification | I (M1) [Ex ia Ma] I |
| Identification | II (1) G [Ex ia Ga] IIC |
| Identification | II (1) D [Ex ia Da] IIIC |
| Identification | II 3 (1) G Ex ec [ia Ga] IIC T4 Gc |
| Certificate | CML 22UKEX3527X |
IECEx
| Identification | [Ex ia Ga] IIC |
| Identification | [Ex ia Da] IIIC |
| Identification | Ex ec [ia Ga] IIC T4 Gc |
| Identification | [Ex ia Ma] I |
| Certificate | IECEx IBE 08.0005X |
CCC / China-Ex
| Identification | [Ex ia Ga] IIC |
| Identification | [Ex iaD] |
| Identification | Ex nA [ia Ga] IIC T4 Gc |
| Certificate | NEPSI GYJ20.1314X |
UL, USA/Canada
| Identification | UL 61010 Listed |
| Certificate | , C.D.-No 83104549 |
Shipbuilding approval
| Certificate | DNV GL TAA000020C |
Safety Integrity Level (SIL, IEC 61508)
| Identification | 2 |
INMETRO
| Identification | [Ex ia Ga] IIC |
| Identification | [Ex ia Da] IIIC |
| Identification | Ex ec [ia Ga] IIC T4 Gc |
| Identification | [Ex ia Ma] I |
| Certificate | DNV 18.0141 X |
DNV GL data
| Temperature | B |
| Humidity | B |
| Vibration | A |
| EMC | A |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
| Noise immunity | EN 61000-6-2 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
Standards and Regulations
| Electrical isolation | 3-way isolation |
GB Standard
| Standards/regulations | GB 3626.20 |
| Standards/regulations | GB 3836.1 |
| Standards/regulations | GB 3836.4 |
| Standards/regulations | GB 3836.8 |
| Standards/regulations | GB 12476.1 |
| Standards/regulations | GB 12476.4 |
Mounting
| Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2924883?
Proax is an authorized distributor of Phoenix Contact 2924883 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended