Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
MACX MCR-EX-SL-SD-23-48-LFD
Weight
0.186 kg

MACX MCR-EX-SL-SD-23-48-LFD - Solenoid driver

Ex i solenoid driver for controlling Ex i solenoid valves in hazardous areas, logic input, off-load voltage 22.6 V, current limitation at 48 mA, line fault transparency, error message output, up to SIL 3 in accordance with IEC 61508, screw connection

  • Input: logic
  • Output: intrinsically safe [Ex ia]; off-load voltage > 22.6 V DC; current limitation > 48 mA
  • Line fault detection (can be enabled/disabled), via the signal circuit or via a separate error message output
  • Transparent for test pulses
  • Up to SIL 3 according to IEC/EN 61508
  • Safe electrical isolation between output, input, supply, and error message output
  • Power supply and error indication possible via DIN rail connector
  • Plug-in connection terminals, screw connection technology
  • Installation in zone 2 permitted
  • Housing width: 12.5 mm
Technical Specifications

Utilization restriction

EMC noteEMC: class A product, see manufacturer's declaration in the download area

Product properties

Product familyMACX Analog
No. of channels1
TypeEx i signal conditioners with SIL functional safety

Electrical isolation

Overvoltage categoryII
Pollution degree2

Electrical isolation Output/input, error message output IEC/EN 60079-11

Standards/regulationsIEC/EN 60079-11
Rated Insulation Voltage375 VPP
Test voltage2.5 kV AC (50 Hz, 60 s)

Electrical isolation Output/input, error message output IEC/EN 61010-1

Standards/regulationsIEC/EN 61010-1
Rated Insulation Voltage300 Vrms
Test voltage2.5 kV AC (50 Hz, 60 s)
InsulationSafe isolation

Electrical isolation Output/supply, DIN rail connector IEC/EN 60079-11

Standards/regulationsIEC/EN 60079-11
Rated Insulation Voltage375 VPP
Test voltage2.5 kV AC (50 Hz, 60 s)

Electrical isolation Output/supply, DIN rail connector IEC/EN 61010-1

Standards/regulationsIEC/EN 61010-1
Rated Insulation Voltage300 Vrms
Test voltage2.5 kV AC (50 Hz, 60 s)
InsulationSafe isolation

Electrical isolation Input/error message output/supply

Test voltage1.5 kV AC (50 Hz, 60 s)

Supply

Nominal Supply Voltage24 V DC -20 % ... +25 %
Supply Voltage Range19.2 V DC ... 30 V DC
Power dissipation< 1.8 W

Signal: Logic

Number of Inputs1
Switching level "0" signal0 V DC ... 5 V DC (or open)
Switching level "1" signal15 V DC ... 30 V DC
Input Current< 12 mA
Input Impedance3 MΩ (high-resistance in the event of a line fault at the output)
Immune to test pulsesYes

Signal: Error message output

Contact switching typeN/O contact
Type of output signalTransistor output, passive
Maximum Switching Voltage30 V DC
Max. switching current50 mA
Short-circuit-proofyes

Signal: Voltage

Output descriptionintrinsically safe
Number of Outputs1
Output Voltage≥ 9.36 V DC (48 mA)
Output resistor≥ 269.3 Ω (Internal resistance Ri)
Current limitation> 48 mA (with line fault detection)
Response time< 30 ms
Non-load voltage> 22.5 V DC
Short-circuit-proofyes
Line fault detection> 10 kΩ (Line break)
Line fault detection< 50 Ω (Short circuit)
Line fault detectionActivated /deactivated via DIP switch

Connection data

Connection MethodScrew connection
Stripping length7 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Tightening torque0.5 Nm ... 0.6 Nm

Test socket

Max. diameter2.3 mm

Ex data

Ex installation (EPL)Gc
Ex installation (EPL)Div. 2
Ex i circuits (EPL)Ga
Ex i circuits (EPL)Da
Ex i circuits (EPL)Ma
Ex i circuits (EPL)Div. 1

Safety data

Max. internal inductance Linegligible
Max. internal capacitance Ci11 nF
Max. output voltage Uo25.3 V
Max. output current Io94 mA
Max. output power Po595 mW
Safety-related maximum voltage Um253 V AC
Safety-related maximum voltage Um125 V DC
IIC: Max. external inductivity Lo / Max. external capacitance Co3 mH / 95 nF
IIB/IIIC: Max. external inductivity Lo / Max. external capacitance Co12 mH / 810 nF
IIA/I: Max. external inductivity Lo / Max. external capacitance Co24 mH / 2750 nF

Signaling

Status displayGreen LED (supply voltage)
Status displayLED yellow (switching state)
Status displayRed LED (line errors)

Dimensions

Width12.5 mm
Height112.5 mm
Depth113.7 mm
Depth NS 35/7,5114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)

Material specifications

Colorgray (RAL 7042)
Flammability rating according to UL 94V0 (Housing)
Housing MaterialPA 6.6-FR

Ambient conditions

Degree of ProtectionIP20 (not assessed by UL)
Ambient Temperature (Operation)-20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)

Altitude range (≤ 2000 m)

Altitude≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.)
Ambient Temperature (Operation)-20 °C ... 60 °C
Rated Insulation Voltage253 V AC (Power supply, input / output)
Rated Insulation Voltage125 V DC (Power supply, input / output)

Altitude range (≤ 3000 m)

Height Range> 2000 m ... 3000 m
Ambient Temperature (Operation)-20 °C ... 54 °C
Rated Insulation Voltage190 V AC (Power supply, input / output)
Rated Insulation Voltage110 V DC (Power supply, input / output)

Altitude range (≤ 4000 m)

Height Range> 3000 m ... 4000 m
Ambient Temperature (Operation)-20 °C ... 48 °C
Rated Insulation Voltage60 V AC/DC (Power supply, input / output)

Altitude range (≤ 5000 m)

Height Range> 4000 m ... 5000 m
Ambient Temperature (Operation)-20 °C ... 42 °C
Rated Insulation Voltage60 V AC/DC (Power supply, input / output)

CE

CertificateCE-compliant
Noteand EN 61326

ATEX

Identification I (M1) [Ex ia Ma] I
Identification II (1) G [Ex ia Ga] IIC
Identification II (1) D [Ex ia Da] IIIC
Identification II 3(1) G Ex ec [ia Ga] IIC T4 Gc X
CertificateIBExU 13 ATEX1045X

UKCA Ex (UKEX)

Identification II (1) G [Ex ia Ga] IIC
Identification II (1) D [Ex ia Da] IIIC
Identification II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
Identification I (M1) [Ex ia Ma] I
CertificateCML 22UKEX3530X

IECEx

Identification[Ex ia Ma] I
Identification[Ex ia Ga] IIC
Identification[Ex ia Da] IIIC
IdentificationEx ec [ia Ga] IIC T4 Gc
CertificateIECEx IBE 13.0014X

CCC / China-Ex

Identification[Ex ia Ga] IIC
Identification[Ex iaD]
IdentificationEx nA [ia Ga] IIC T4 Gc
CertificateNEPSI GYJ20.1315X

UL, USA/Canada

IdentificationUL 61010 Listed
Certificate, C.D.-No 83104549

Shipbuilding approval

CertificateDNV GL TAA000020C

Safety Integrity Level (SIL, IEC 61508)

Identification3

KC-s

Identification[Ex ia] IIC/IIB
Certificate17-KA4BO-0402X

INMETRO

Identification[Ex ia Ma] I
Identification[Ex ia Ga] IIC
Identification[Ex ia Da] IIIC
IdentificationEx ec [ia Ga] IIC T4 Gc
CertificateDNV 18.0145 X

DNV GL data

TemperatureB
HumidityB
VibrationA
EMCA
EnclosureRequired protection according to the Rules shall be provided upon installation on board

EMC data

Noise immunityEN 61000-6-2
NoteWhen being exposed to interference, there may be minimal deviations.
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4

GB Standard

Standards/regulationsGB 3836.1
Standards/regulationsGB 3836.4
Standards/regulationsGB 3836.8
Standards/regulationsGB 3626.20
Standards/regulationsGB 12476.1
Standards/regulationsGB 12476.4

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact 2924867?

Proax is an authorized distributor of Phoenix Contact 2924867 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability