SKU
MPN
MACX MCR-EX-SL-RPSSI-2I
Weight
0.246 kg
This product is Not Cancellable/Not Returnable
Series MACX-MCR-EX-SL-RPSSI
MACX MCR-EX-SL-RPSSI-2I - Repeater power supply
Ex i measuring transducer power supply and input signal conditioner, HART-transparent. Transfers supplied or active 0/4…20 mA electrically isolated signals from the Ex area to two loads in the safe area. 4-way electrical isolation, screw connection, SIL, PL.
- 0/4 mA ... 20 mA input, intrinsically safe, [Ex ia], powered and not powered
- Measuring transducer supply voltage > 16 V
- Two electrically isolated 0/4 mA ... 20 mA (active) outputs
- Bidirectional HART transmission (both outputs)
- Error indication according to NAMUR NE 43
- SIL 2 according to IEC/EN 61508
- Safe electrical isolation between input, outputs, and supply
- Power supply possible via DIN rail connector
- Installation in zone 2 permitted
- Plug-in connection terminal blocks, screw connection technology, with integrated sockets for HART communicators
- Housing width: 12.5 mm
- Minimal power dissipation
- High transmission accuracy
Technical Specifications
Product properties
Product family | MACX Analog |
No. of channels | 1 |
Type | Ex i signal conditioners with SIL and PL Functional Safety |
Electrical properties
Electrical isolation | 3-way isolation |
Electrical isolation between input and output | yes |
Signal transmission behavior | In = Out |
Step response (10-90%) | 1.3 ms (for jump 4 mA ... 20 mA, typical) |
Maximum temperature coefficient | < 0.01 %/K |
Maximum transmission error | < 0.1 % (of final value) |
Transmission error, typical | < 0.05 % (of final value) |
Electrical isolation
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation Input/output/power supply IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation |
Electrical isolation Input/output IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 265 Vrms |
Electrical isolation Input/power supply IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 265 Vrms |
Electrical isolation Output 1/output 2
Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Supply
Designation | Repeater power supply operation |
Nominal Supply Voltage | 24 V DC -20 % ... +25 % |
Supply Voltage Range | 19.2 V DC ... 30 V DC |
Max. current consumption | < 75 mA (24 V DC / 20 mA) |
Power dissipation | < 1.45 W (24 V DC / 20 mA) |
Power consumption | ≤ 1.8 W |
Designation | Signal conditioner operation |
Nominal Supply Voltage | 24 V DC -20 % ... +25 % |
Supply Voltage Range | 19.2 V DC ... 30 V DC |
Max. current consumption | < 46 mA (24 V DC / 20 mA) |
Power dissipation | < 1.2 W (24 V DC / 20 mA) |
Signal: Repeater power supply operation
Description of the input | Repeater power supply operation |
Number of Inputs | 1 |
Current Input Signal | 4 mA ... 20 mA |
Transmitter supply voltage | > 16 V (20 mA) |
Transmitter supply voltage | > 15.1 V (23 mA) |
Polarization and surge protection | Yes |
Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Signal: Signal conditioner operation
Description of the input | Signal conditioner operation |
Current Input Signal | 0 mA ... 20 mA |
Current Input Signal | 4 mA ... 20 mA |
Voltage drop | < 3.9 V (in input isolating amplifier operation) |
Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Signal: Repeater power supply operation
Output description | Repeater power supply operation |
Number of Outputs | 2 |
Current Output Signal | 4 mA ... 20 mA (Output 1 and output 2 active) |
Load/Output Load Current Output | < 450 Ω (20 mA) |
Load/Output Load Current Output | < 380 Ω (23 mA) |
Output ripple | < 20 mVrms |
Output behavior in the event of an error | 0 mA (Cable break in the input) |
Output behavior in the event of an error | ≥ 23 mA (Cable short-circuit in the input) |
Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Signal: Signal conditioner operation
Output description | Signal conditioner operation |
Current Output Signal | 0 mA ... 20 mA (active) |
Current Output Signal | 4 mA ... 20 mA (active) |
Load/Output Load Current Output | < 450 Ω (20 mA) |
Load/Output Load Current Output | < 380 Ω (23 mA) |
Output ripple | < 20 mVrms |
Output behavior in the event of an error | 0 mA (Cable break in the input) |
Output behavior in the event of an error | 0 mA (Cable short-circuit in the input) |
Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Connection data
Connection Method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Test socket
Max. diameter | 2.3 mm |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Ex i circuits (EPL) | Ga |
Ex i circuits (EPL) | Da |
Ex i circuits (EPL) | Ma |
Ex i circuits (EPL) | Div. 1 |
Safety data: Repeater power supply operation
Max. output voltage Uo | 25.2 V |
Max. output current Io | 93 mA |
Max. output power Po | 587 mW |
Safety-related maximum voltage Um | 253 V AC |
Safety-related maximum voltage Um | 125 V DC |
I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 40 mH / 4.8 µF |
IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 26 mH / 2.9 µF |
IIB (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 14 mH / 820 nF |
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 3 mH / 107 nF |
IIA (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 26 mH / 470 nF, 20 mH / 570 nF, 1 mH / 630 nF, 0.5 mH / 720 nF, 0.1 mH / 1.1 µF, 0.005 mH / 2.9 µF |
IIB/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 16 mH / 370 nF, 1 mH / 430 nF, 500 µH / 510 nF, 200 µH / 660 nF, 100 µH / 820 nF |
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 2.2 mH / 47 nF, 2 mH / 49 nF, 1 mH / 63 nF, 500 µH / 80 nF, 200 µH / 107 nF |
I (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 37 mH / 0.54 µF, 0.2 mH / 1.1 µF, 10 µH / 2.8 µF, 0.001 mH / 4.15 µF |
Safety data: Signal conditioner operation
Input voltage Ui | ≤ 30 V |
Input current Ii | ≤ 150 mA |
Max. internal inductance Li | negligible |
Max. internal capacitance Ci | negligible |
Safety-related maximum voltage Um | 253 V AC |
Safety-related maximum voltage Um | 125 V DC |
Data communication (bypass)
HART Function | Yes |
Protocols Supported | HART-transparent |
Signaling
Status display | Green LED (supply voltage) |
Dimensions
Width | 12.5 mm |
Height | 112.5 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing Material | PA 6.6-FR |
Ambient conditions
Degree of Protection | IP20 (not assessed by UL) |
Ambient Temperature (Operation) | -40 °C ... 60 °C (Any mounting position) |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m)
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient Temperature (Operation) | -40 °C ... 60 °C |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
Rated Insulation Voltage | 375 VPP (Power supply, input / output) |
Altitude range (≤ 3000 m)
Height Range | > 2000 m ... 3000 m |
Ambient Temperature (Operation) | -40 °C ... 54 °C |
Ambient Temperature (Operation) | -40 °C ... 63 °C (Derating) |
Rated Insulation Voltage | 190 V AC (Power supply, input / output) |
Rated Insulation Voltage | 110 V DC (Power supply, input / output) |
Altitude range (≤ 4000 m)
Height Range | > 3000 m ... 4000 m |
Ambient Temperature (Operation) | -40 °C ... 48 °C |
Ambient Temperature (Operation) | -40 °C ... 56 °C (Derating) |
Rated Insulation Voltage | 60 V AC/DC (Power supply, input / output) |
Altitude range (≤ 5000 m)
Height Range | > 4000 m ... 5000 m |
Ambient Temperature (Operation) | -40 °C ... 42 °C |
Ambient Temperature (Operation) | -40 °C ... 49 °C (Derating) |
Rated Insulation Voltage | 60 V AC/DC (Power supply, input / output) |
CE
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX
Identification | II (1) G [Ex ia Ga] IIC |
Identification | II (1) D [Ex ia Da] IIIC |
Identification | II 3(1) G Ex ec [ia Ga] IIC T4 Gc |
Identification | I (M1) [Ex ia Ma] I |
Certificate | BVS 10 ATEX E 143 X |
IECEx
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia Ga] IIC T4 Gc |
Identification | [Ex ia Ma] I |
Certificate | IECEx BVS 10.0097X |
CCC / China-Ex
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia Ga] IIC T4 Gc |
Certificate | 2022122316115971 |
UL, USA/Canada
Identification | IS for Class I,II,III, Division 1 and Zone 0 |
Identification | Installation in Class I, Division 2 and Zone 2 |
Certificate | , C.D.-No 83104549 |
Identification | Class I Div 2; IS for Class I, II, III Div 1 |
Certificate | , C.D.-No 83104549 |
Shipbuilding approval
Certificate | DNV GL TAA000020C |
Safety Integrity Level (SIL, IEC 61508)
Identification | 2 |
Certificate | IN-AT-AS-MRL-23-00432A |
Systematic Capability
Identification | 3 |
Performance Level (ISO 13849)
Identification | d / KAT 2 |
INMETRO
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia Ga] IIC T4 Gc |
Identification | [Ex ia Ma] I |
Certificate | DNV 18.0139 X |
DNV GL data
Temperature | B |
Humidity | B |
Vibration | A |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Standards and Regulations
Electrical isolation | 3-way isolation |
GB Standard
Standards/regulations | GB/T 3836.1 |
Standards/regulations | GB/T 3836.3 |
Standards/regulations | GB/T 3836.4 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2865366?
Proax is an authorized distributor of Phoenix Contact 2865366 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended