MACX MCR-EX-SL-RPSSI-I-UP-SP - Power/input isolating amplifier
Ex i repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active 0/4 … 20 mA signals from the Ex area to a load (active or passive) in the safe area. SIL 2 (1oo1) / SIL 3 (1oo2), wide-range supply.
- 250 Ω resistor that can be activated via DIP switches to increase HART impedance for low-resistance systems
- Up to SIL 2 in accordance with EN 61508
- Installation in zone 2, protection type "n" (EN 60079-15) permitted
- Wide-range power supply of 19.2 ... 253 V AC/DC
- 3-way electrical isolation
- Plug-in screw or spring-cage connection technology (Push-in technology), with integrated sockets for HART communicators
- 0/4 ... 20 mA input, [Ex ia] IIC (powered or not powered)
- Bidirectional transmission of digital HART communication signals
- 0/4 ... 20 mA output (active or passive), 0/1 ... 5 V, can be selected via DIP switches
Technical Specifications
Product properties
Product family | MACX Analog |
Application | Analog IN |
No. of channels | 1 |
Type | Ex i signal conditioners with SIL functional safety |
Configuration | DIP switches |
Electrical properties
Electrical isolation | 3-way isolation |
Electrical isolation between input and output | yes |
Step response (10-90%) | < 600 µs (for 4 mA ... 20 mA step) |
Maximum temperature coefficient | < 0.01 %/K |
Maximum transmission error | < 0.1 % (of final value) |
Transmission error, typical | < 0.05 % (of final value) |
Electrical isolation
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation Input/output/power supply IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Insulation | Safe isolation |
Electrical isolation Input/output IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 265 Vrms |
Electrical isolation Input/power supply IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 265 Vrms |
Electrical isolation Output/supply IEC/EN 60079-7
Standards/regulations | IEC/EN 60079-7 |
Rated Insulation Voltage | 265 Vrms |
Supply
Designation | Repeater power supply operation |
Nominal supply voltage range | 24 V AC/DC ... 230 V AC/DC -20 % ... +10 % (50/60 Hz) |
Supply Voltage Range | 19.2 V AC/DC ... 253 V AC/DC (50/60 Hz) |
Max. current consumption | < 80 mA (24 V DC / 20 mA) |
Power dissipation | < 1.6 W (24 V DC / 20 mA) |
Power consumption | < 2.2 W |
Designation | Signal conditioner operation |
Nominal supply voltage range | 24 V AC/DC ... 230 V AC/DC -20 % ... +10 % (50/60 Hz) |
Supply Voltage Range | 19.2 V AC/DC ... 253 V AC/DC (50/60 Hz) |
Max. current consumption | < 45 mA (24 V DC / 20 mA) |
Power dissipation | < 1.1 W (24 V DC / 20 mA) |
Signal: Repeater power supply operation
Description of the input | Active current input, intrinsically safe |
Number of Inputs | 1 |
Current Input Signal | 4 mA ... 20 mA |
Transmitter supply voltage | > 16 V (20 mA) |
Transmitter supply voltage | > 15.3 V (22.5 mA) |
Signal: Signal conditioner operation
Description of the input | Passive current input, intrinsically safe |
Current Input Signal | 0 mA ... 20 mA |
Current Input Signal | 4 mA ... 20 mA |
Voltage drop | < 3.5 V (in input isolating amplifier operation) |
Signal: Repeater power supply operation
Output description | Current output (active and passive) |
Number of Outputs | 1 |
Voltage output signal | 1 V ... 5 V (internal resistance, 250 Ω, 0.1%) |
Voltage output signal | Configurable via DIP switches |
Current Output Signal | 4 mA ... 20 mA (active) |
Current Output Signal | 4 mA ... 20 mA (14 ... 26 V ext. source voltage) |
Load/Output Load Current Output | < 600 Ω (20 mA) |
Load/Output Load Current Output | < 525 Ω (22.5 mA) |
Output ripple | < 20 mVrms |
Output behavior in the event of an error | 0 mA (Cable break in the input) |
Output behavior in the event of an error | ≥ 22.5 mA (Cable short-circuit in the input) |
Signal: Signal conditioner operation
Output description | Current output (active and passive) |
Voltage output signal | 0 V ... 5 V (internal resistance, 250 Ω, 0.1%) |
Voltage output signal | 1 V ... 5 V (internal resistance, 250 Ω, 0.1%) |
Current Output Signal | 0 mA ... 20 mA (active) |
Current Output Signal | 4 mA ... 20 mA (active) |
Current Output Signal | 0 mA ... 20 mA (14 ... 26 V ext. source voltage) |
Current Output Signal | 4 mA ... 20 mA (14 ... 26 V ext. source voltage) |
Load/Output Load Current Output | < 600 Ω (20 mA) |
Load/Output Load Current Output | < 525 Ω (22.5 mA) |
Output ripple | < 20 mVrms |
Output behavior in the event of an error | 0 mA (Cable break in the input) |
Output behavior in the event of an error | 0 mA (Cable short-circuit in the input) |
Connection data
Connection Method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible (2 conductors with same cross section) | 0.25 mm² ... 0.34 mm² (TWIN ferrule without plastic sleeve) |
Conductor cross section flexible (2 conductors with same cross section) | 0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) |
Conductor cross section AWG | 24 ... 14 |
Conductor cross section AWG | 24 ... 22 (TWIN ferrule without plastic sleeve) |
Conductor cross section AWG | 20 ... 16 (TWIN ferrule with plastic sleeve) |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Ex i circuits (EPL) | Ga |
Ex i circuits (EPL) | Da |
Ex i circuits (EPL) | Ma |
Ex i circuits (EPL) | Div. 1 |
Safety data: Repeater power supply operation
Max. output voltage Uo | 25.2 V |
Max. output current Io | 93 mA |
Max. output power Po | 587 mW |
Safety-related maximum voltage Um | 253 V AC/DC (Supply terminals) |
Safety-related maximum voltage Um | 253 V AC (Output terminals) |
Safety-related maximum voltage Um | 125 V DC (Output terminals) |
I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 40 mH / 4.8 µF |
IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 26 mH / 2.9 µF |
IIB (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 14 mH / 820 nF |
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 3 mH / 107 nF |
IIA (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 26 mH / 470 nF, 20 mH / 570 nF, 1 mH / 630 nF, 0.5 mH / 720 nF, 0.1 mH / 1.1 µF, 0.005 mH / 2.9 µF |
IIB/III (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 16 mH / 370 nF, 500 µH / 510 nF, 200 µH / 660 nF, 100 µH / 820 nF |
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 2.2 mH / 47 nF, 2 mH / 49 nF, 1 mH / 63 nF, 500 µH / 80 nF, 200 µH / 107 nF |
I (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 37 mH / 0.54 µF, 0.35 mH / 1 µF, 0.009 mH / 2.9 µF, 0.001 mH / 4.15 µF |
Safety data: Signal conditioner operation
Input voltage Ui | ≤ 30 V |
Input current Ii | ≤ 150 mA |
Max. internal inductance Li | negligible |
Max. internal capacitance Ci | negligible |
Safety-related maximum voltage Um | 253 V AC/DC (Supply terminals) |
Safety-related maximum voltage Um | 253 V AC (Output terminals) |
Safety-related maximum voltage Um | 125 V DC (Output terminals) |
Data communication (bypass)
HART Function | Yes |
Protocols Supported | HART-transparent |
Signaling
Status display | Green LED (supply voltage) |
Dimensions
Width | 17.5 mm |
Height | 107.9 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing Material | PA 6.6-FR |
Ambient conditions
Degree of Protection | IP20 (not assessed by UL) |
Ambient Temperature (Operation) | -40 °C ... 60 °C (Any mounting position) |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m)
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient Temperature (Operation) | -40 °C ... 60 °C |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Derating) |
Rated Insulation Voltage | 375 VPP (Power supply, input / output) |
Altitude range (≤ 3000 m)
Height Range | > 2000 m ... 3000 m |
Ambient Temperature (Operation) | -40 °C ... 54 °C |
Ambient Temperature (Operation) | -40 °C ... 63 °C (Derating) |
Rated Insulation Voltage | 190 V AC (Power supply, input / output) |
Rated Insulation Voltage | 110 V DC (Power supply, input / output) |
Altitude range (≤ 4000 m)
Height Range | > 3000 m ... 4000 m |
Ambient Temperature (Operation) | -40 °C ... 48 °C |
Ambient Temperature (Operation) | -40 °C ... 56 °C (Derating) |
Rated Insulation Voltage | 60 V AC/DC (Power supply, input / output) |
Altitude range (≤ 5000 m)
Height Range | > 4000 m ... 5000 m |
Ambient Temperature (Operation) | -40 °C ... 42 °C |
Ambient Temperature (Operation) | -40 °C ... 49 °C (Derating) |
Rated Insulation Voltage | 60 V AC/DC (Power supply, input / output) |
CE
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX
Identification | II (1) G [Ex ia Ga] IIC |
Identification | II (1) D [Ex ia Da] IIIC |
Identification | II 3(1) G Ex ec [ia Ga] IIC T4 Gc |
Identification | I (M1) [Ex ia Ma] I |
Certificate | BVS 08 ATEX E 094 X |
IECEx
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia Ga] IIC T4 Gc |
Identification | [Ex ia Ma] I |
Certificate | IECEx BVS 08.0035X |
CCC / China-Ex
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia Ga] IIC T4 Gc |
Certificate | 2022122316115974 |
UL, USA/Canada
Identification | Class I Div 2; IS for Class I, II, III Div 1 |
Certificate | , C.D.-No 83104549 |
Safety Integrity Level (SIL / SILCL, IEC 61508)
Identification | 2 |
Certificate | ZP/C031/20 |
Systematic Capability (SC / SILCL)
Identification | 3 |
INMETRO
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia Ga] IIC T4 Gc |
Certificate | DNV 18.0138 X |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Electromagnetic HF field
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 1 % |
Fast transients (burst)
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 1 % |
Conducted interference
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 1 % |
Standards and Regulations
Electrical isolation | 3-way isolation |
GB Standard
Standards/regulations | GB/T 3836.1 |
Standards/regulations | GB/T 3836.3 |
Standards/regulations | GB/T 3836.4 |
Standards/regulations | GB/T 16935.1 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2924029?
Proax is an authorized distributor of Phoenix Contact 2924029 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended