SKU
MPN
MACX MCR-EX-SL-SD-21-25-LFD-SP
Weight
0.172 kg
Series MACX-MCR-EX-SL-SD
MACX MCR-EX-SL-SD-21-25-LFD-SP - Solenoid driver
Ex i solenoid driver for controlling Ex i solenoid valves in hazardous areas, logic input, off-load voltage 21.1 V, current limitation at 25.1 mA, line fault transparency, error message output, up to SIL 3 according to IEC 61508; Push-in connection.
- Input: logic
- Output: intrinsically safe [Ex ia]; off-load voltage > 21.1 V DC; current limitation > 25.1 mA
- Line fault detection (can be enabled/disabled), via the signal circuit or via a separate error message output
- Transparent for test pulses
- Up to SIL 3 according to IEC/EN 61508
- Safe electrical isolation between output, input, supply, and error message output
- Power supply and error indication possible via DIN rail connector
- Plug-in connection terminals, push-in connection technology
- Installation in zone 2 permitted
- Housing width: 12.5 mm
Documents
Technical Specifications
Product properties
Product family | MACX Analog |
Type | Ex i signal conditioners with SIL functional safety |
Configuration | DIP switches |
Electrical isolation
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation Output/input, error message output IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 375 VPP |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Electrical isolation Output/input, error message output IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation |
Electrical isolation Output/supply, DIN rail connector IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 375 VPP |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Electrical isolation Output/supply, DIN rail connector IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation |
Electrical isolation Input/error message output/supply
Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Supply
Nominal Supply Voltage | 24 V DC -20 % ... +25 % |
Supply Voltage Range | 19.2 V DC ... 30 V DC |
Power dissipation | < 0.8 W |
Signal: Logic
Number of Inputs | 1 |
Switching level "0" signal | 0 V DC ... 5 V DC (or open) |
Switching level "1" signal | 15 V DC ... 30 V DC |
Input Current | < 12 mA |
Input Impedance | 3 MΩ (high-resistance in the event of a line fault at the output) |
Immune to test pulses | Yes |
Signal: Error message output
Contact switching type | N/O contact |
Type of output signal | Transistor output, passive |
Maximum Switching Voltage | 30 V DC |
Max. switching current | 50 mA |
Short-circuit-proof | yes |
Signal: Voltage
Output description | intrinsically safe |
Number of Outputs | 1 |
Output Voltage | ≥ 4.64 V DC (25.1 mA) |
Current limitation | > 25.1 mA (with line fault detection) |
Response time | < 30 ms |
Non-load voltage | > 21.1 V DC |
Short-circuit-proof | yes |
Line fault detection | > 10 kΩ (Line break) |
Line fault detection | < 50 Ω (Short circuit) |
Line fault detection | Activated /deactivated via DIP switch |
Connection data
Connection Method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible (2 conductors with same cross section) | 0.25 mm² ... 0.34 mm² (TWIN ferrule without plastic sleeve) |
Conductor cross section flexible (2 conductors with same cross section) | 0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) |
Conductor cross section AWG | 24 ... 14 |
Conductor cross section AWG | 24 ... 22 (TWIN ferrule without plastic sleeve) |
Conductor cross section AWG | 20 ... 16 (TWIN ferrule with plastic sleeve) |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Ex i circuits (EPL) | Ga |
Ex i circuits (EPL) | Da |
Ex i circuits (EPL) | Ma |
Ex i circuits (EPL) | Div. 1 |
Safety data
Max. internal inductance Li | negligible |
Max. internal capacitance Ci | 11 nF |
Max. output voltage Uo | 23.98 V |
Max. output current Io | 37.4 mA |
Max. output power Po | 224 mW |
Maximum internal resistance Ri | 641 Ω |
Safety-related maximum voltage Um | 253 V AC |
Safety-related maximum voltage Um | 125 V DC |
IIA/I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 203.4 mH / 3.33 µF |
IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 101.7 mH / 0.91 µF |
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 25.4 mH / 0.114 µF |
IIA (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 50 mH / 0.67 µF, 20 mH / 0.76 µF, 0.5 mH / 0.83 µF, 0.2 mH / 0.89 µF |
IIB/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 5 mH / 289 nF, 0.5 mH / 489 nF |
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 5 mH / 59 nF, 0.5 mH / 89 nF |
Signaling
Status display | Green LED (supply voltage) |
Status display | LED yellow (switching state) |
Status display | Red LED (line errors) |
Dimensions
Width | 12.5 mm |
Height | 107.9 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing Material | PA 6.6-FR |
Ambient conditions
Degree of Protection | IP20 (not assessed by UL) |
Ambient Temperature (Operation) | -20 °C ... 60 °C (Any mounting position) |
Ambient Temperature (Operation) | -20 °C ... 70 °C (Derating) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m)
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient Temperature (Operation) | -20 °C ... 70 °C |
Safety-related maximum voltage Um | 253 V AC |
Safety-related maximum voltage Um | 125 V DC |
Rated Insulation Voltage | 375 VPP |
Rated Insulation Voltage | 300 V AC/DC |
Altitude range (≤ 3000 m)
Height Range | > 2000 m ... 3000 m |
Ambient Temperature (Operation) | -20 °C ... 63 °C |
Safety-related maximum voltage Um | 190 V AC |
Safety-related maximum voltage Um | 110 V DC |
Rated Insulation Voltage | 190 V |
Altitude range (≤ 4000 m)
Height Range | > 3000 m ... 4000 m |
Ambient Temperature (Operation) | -20 °C ... 56 °C |
Safety-related maximum voltage Um | 60 V AC/DC |
Rated Insulation Voltage | 60 V AC/DC |
Altitude range (≤ 5000 m)
Height Range | > 4000 m ... 5000 m |
Ambient Temperature (Operation) | -20 °C ... 49 °C |
Safety-related maximum voltage Um | 60 V AC/DC |
Rated Insulation Voltage | 60 V AC/DC |
CE
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX
Identification | I (M1) [Ex ia Ma] I |
Identification | II (1) G [Ex ia Ga] IIC |
Identification | II (1) D [Ex ia Da] IIIC |
Identification | II 3(1) G Ex ec [ia Ga] IIC T4 Gc X |
Certificate | IBExU 13 ATEX1045X |
IECEx
Identification | [Ex ia Ma] I |
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia Ga] IIC T4 Gc |
Certificate | IECEx IBE 13.0014X |
CCC / China-Ex
Identification | [Ex ia Ga] IIB |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia IIB Ga] IIC T4 Gc |
Certificate | 2022122316115979 |
UL, USA/Canada
Identification | UL 61010 Listed |
Certificate | , C.D.-No 83104549 |
Shipbuilding approval
Certificate | DNV GL TAA000020C |
Safety Integrity Level (SIL, IEC 61508)
Identification | 3 |
INMETRO
Identification | [Ex ia Ma] I |
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia Ga] IIC T4 Gc |
Certificate | DNV 18.0145 X |
Temperature | B |
Humidity | B |
Vibration | A |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Electromagnetic compatibility | Conformance with EMC directive |
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Noise emission | EN 61000-6-4 |
GB Standard
Standards/regulations | GB/T 3836.1 |
Standards/regulations | GB/T 3836.3 |
Standards/regulations | GB/T 3836.4 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2905674?
Proax is an authorized distributor of Phoenix Contact 2905674 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended