SKU
MPN
MACX MCR-EX-SL-SD-21-40-LP
Weight
0.171 kg
Series MACX-MCR-EX-SL-SD
MACX MCR-EX-SL-SD-21-40-LP - Solenoid driver
Ex i solenoid driver. For the intrinsically safe control of Ex i solenoid valves, alarm modules or LEDs installed in the Ex area. Current limitation at 40 mA. For gases up to Group IIC, loop-powered, electrical isolation, SIL 3. Screw connection.
- Mechanically compatible with the DIN rail connector
- Various output characteristic curves compatible with standard solenoid valves
- Loop-powered: the required power is supplied via the control signal on the input side.
- Up to SIL 3 in accordance with IEC 61508
- Installation in zone 2, protection type "n" (EN 60079-15) permitted
- Output: [Ex ia] IIC/[Ex ia] IIB
- 2-way electrical isolation
- Input: 19.2 V DC … 30 V DC
Technical Specifications
Product properties
Product family | MACX Analog |
No. of channels | 1 |
Type | Ex i signal conditioners with SIL functional safety |
Compatible Valve | ASCO Coil 195 |
Compatible Valve | Bürkert Coil AC 10 standard |
Compatible Valve | Bürkert Coil AC 10 high resistance |
Compatible Valve | Bürkert Coil AC 21 standard 700 mW / 65°C |
Compatible Valve | Bürkert Coil AC 21 high resistance 700 mW / 65°C |
Compatible Valve | Bürkert Coil AC 21 standard 900 mW / 45°C |
Compatible Valve | Bürkert Coil AC 21 high resistance 900 mW / 45°C |
Compatible Valve | Bürkert Coil AC 21 standard 900 mW / 60°C |
Compatible Valve | Bürkert Coil AC 21 high resistance 900 mW / 60°C |
Compatible Valve | Bürkert Coil G1 642735 standard 600 mW / 50°C |
Compatible Valve | Bürkert Coil G1 642735 high resistance 600 mW / 50°C |
Compatible Valve | Bürkert Coil G1 642735 standard 800 mW / 40°C |
Compatible Valve | Bürkert Coil G1 642735 high resistance 800 mW / 40°C |
Compatible Valve | Bürkert Coil G1 642735 standard 1000 mW / 40°C |
Compatible Valve | Bürkert Coil G1 642735 high resistance 1000 mW / 40°C |
Compatible Valve | Norgren Herion Coil 2050 |
Compatible Valve | Norgren Herion Coil 2051 |
Compatible Valve | Norgren Herion Coil 2052 |
Compatible Valve | Norgren Herion Coil 2080 / 2082 |
Compatible Valve | Norgren Herion Coil 2081 / 2083 |
Compatible Valve | Norgren Herion Coil 2084 |
Compatible Valve | Hörbiger Piezo P8 38x RF-Nx-SPN65 30 V type |
Compatible Valve | Hörbiger Piezo P20 381RF-NG-CPN61 30 V type |
Compatible Valve | Parker Coil VZ07 488650.01 |
Compatible Valve | Parker Coil VZ33 494035.10 |
Compatible Valve | Parker Coil VZ08 488660.01 |
Compatible Valve | Parker Coil VZ09 488670.01 |
Compatible Valve | Parker Coil VZ95 482160.01 EEx ia IIB T6 |
Compatible Valve | Parker Coil VZ23 482870.01 |
Compatible Valve | Samson Coil 3701-12 (12 V) |
Compatible Valve | Samson Coil 3701-13 (24 V) |
Compatible Valve | Samson Coil 3963-12 (12 V) |
Compatible Valve | Samson Coil 3963-13 (24 V) |
Compatible Valve | Samson Coil 3964-12 (12 V) |
Compatible Valve | Samson Coil 3964-13 (24 V) |
Compatible Valve | Seitz Pilot valve PV 12F73 Ci oH |
Compatible Valve | Seitz Pilot valve PV 12F73 Xi oH |
Compatible Valve | Seitz Pilot valve PV 12F73 Xi oH-2 |
Note | This is an extract of possible combinations of valves and solenoid drivers. |
Electrical properties
Electrical isolation | 2-way isolation |
Maximum temperature coefficient | 0.01 %/K |
Electrical isolation
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation Output/input IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 375 VPP |
Electrical isolation Output/input IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Insulation | Safe isolation |
Supply
Supply Voltage Range | loop-powered, no external supply necessary |
Power dissipation | < 1.055 W |
Signal: Voltage
Number of Inputs | 1 |
Voltage input signal | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
Max. current input signal | 65 mA (Ue = 24 V DC) |
Output description | intrinsically safe |
Number of Outputs | 1 |
Output Voltage | 10 V DC (40 mA) |
Output resistor | 287 Ω (Internal resistance Ri) |
Current limitation | 40 mA |
Response time | 20 ms |
Non-load voltage | 21.9 V DC |
Short-circuit-proof | yes |
Connection data
Connection Method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Test socket
Max. diameter | 2 mm |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Ex i circuits (EPL) | Ga |
Ex i circuits (EPL) | Da |
Ex i circuits (EPL) | Ma |
Ex i circuits (EPL) | Div. 1 |
Safety data
Max. internal inductance Li | negligible |
Max. internal capacitance Ci | negligible |
Max. output voltage Uo | 25.1 V |
Max. output current Io | 87 mA |
Max. output power Po | 550 mW |
Safety-related maximum voltage Um | 253 V AC |
Safety-related maximum voltage Um | 125 V DC |
IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 20 mH / 0.83 µF |
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 5 mH / 0.108 µF |
IIB/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 10 mH / 380 nF, 5 mH / 380 nF, 1 mH / 440 nF, 0.1 mH / 820 nF |
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 2 mH / 52 nF, 1 mH / 65 nF, 0.5 mH / 82 nF, 0.2 mH / 108 nF, 0.1 mH / 108 nF |
Signaling
Status display | Yellow LED (switching state / status, lights up when output circuit is active) |
Dimensions
Width | 12.5 mm |
Height | 112.5 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing Material | PA 6.6-FR |
Ambient conditions
Degree of Protection | IP20 (not assessed by UL) |
Ambient Temperature (Operation) | -40 °C ... 60 °C (Any mounting position) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
CE
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX
Identification | II (1) G [Ex ia Ga] IIC/IIB/IIA |
Identification | II (1) D [Ex ia Da] IIIC |
Identification | II 3 (1)G Ex nA [ia IIC Ga] IIC T4 Gc X |
Certificate | IBExU 07 ATEX 1133X |
UKCA Ex (UKEX)
Identification | I (M1) [Ex ia Ma] I |
Identification | II (1) G [Ex ia Ga] IIC |
Identification | II (1) D [Ex ia Da] IIIC |
Identification | II 3 (1) Ex ec [ia Ga] IIC T4 Gc |
Certificate | CML 22UKEX3526X |
IECEx
Identification | [Ex ia Ga] IIC/IIB/IIA |
Identification | [Ex ia Da] IIIC |
Identification | Ex nA [ia IIC Ga] IIC T4 Gc |
Certificate | IECEx IBE 08.0002X |
CCC / China-Ex
Identification | [Ex ia Ga] IIC |
Identification | [Ex iaD] |
Identification | Ex nA [ia Ga] IIC T4 Gc |
Certificate | NEPSI GYJ20.1316X |
UL, USA/Canada
Identification | UL 61010 Listed |
Identification | Class I, Div. 2, Groups A, B, C, D T4 |
Identification | Class I, Div. 2, Groups IIC, IIB, IIA T4 |
Identification | Associated apparatus for use in Class I, Division 1, Groups A,B,C,D |
Identification | Associated apparatus for use in Class II, Div.1 Groups E,F,G |
Identification | Associated apparatus for use in Class III, Division 1 |
Identification | Associated apparatus for use in Class I, Zone 0,1,2, Groups IIC,IIB,IIA |
Certificate | , C.D.-No 83104549 |
Identification | Class I Div 2; IS for Class I, II, III Div 1 |
Certificate | , C.D.-No 83104549 |
Shipbuilding approval
Certificate | DNV GL TAA000020C |
Safety Integrity Level (SIL, IEC 61508)
Identification | 3 |
INMETRO
Identification | [Ex ia Ga] IIC/IIB/IIA |
Identification | [Ex ia Da] IIIC |
Identification | Ex nA [ia IIC Ga] IIC T4 Gc |
Certificate | DNV 18.0115 X |
DNV GL data
Temperature | B |
Humidity | B |
Vibration | A |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Standards and Regulations
Electrical isolation | 2-way isolation |
GB Standard
Standards/regulations | GB 3836.1 |
Standards/regulations | GB 3836.4 |
Standards/regulations | GB 3836.8 |
Standards/regulations | GB 3626.20 |
Standards/regulations | GB 12476.1 |
Standards/regulations | GB 12476.4 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2865764?
Proax is an authorized distributor of Phoenix Contact 2865764 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended