2865586
SKU
PHX2865586
MPN
MACX MCR-EX-SL-TC-I-NC
Weight
0.165 kg
This product is Not Cancellable/Not Returnable
MACX MCR-EX-SL-TC-I-NC - Temperature measuring transducer
Ex i temperature transducer: converts signals from thermocouples installed in the Ex area and mV sources and transmits a 0/4 - 20 mA signal to a load in the safe area. Freely programmable, 3-way isolation. Replacement item: 1050233 MACX MCR-EX-TC-I.
- Power supply possible via DIN rail connector
- Input for resistance thermometers and resistance-type sensors, [Ex ia] IIC
- Programming during operation with Ex measuring circuit connected and also voltage-free using IFS-USB-PROG-ADAPTER programming adapter
- Installation in zone 2, protection type "n" (EN 60079-15) permitted
- 3-way electrical isolation
- Status indicator for supply voltage, cable, sensor, and module errors
- Configuration via software (FDT/DTM): sensor type, connection technology, measuring range, measuring unit, filter, alarm signal, and output range
- Output: 0 mA ... 20 mA or 4 mA ... 20 mA
Technical Specifications
Product properties
| Application | Temperature |
| No. of channels | 1 |
| Type | Ex i signal conditioners |
Insulation characteristics
| Overvoltage category | II |
| Pollution degree | 2 |
Electrical properties
| Alignment span | ± 5 % |
| Alignment zero | ± 5 % |
| Typical cold point errors | ± 1 K |
| Step response (0–99%) | 700 ms |
| Step response (0–99%) | ≤ 1100 ms |
| Temperature coefficient, typical | 0.01 %/K |
Electrical isolation Input/output/power supply
| Rated Insulation Voltage | 300 Vrms |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) |
| Insulation | Safe isolation in accordance with IEC/EN 61010-1 |
Electrical isolation Input/output
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
Electrical isolation Input/power supply
| Electrical isolation | 375 V (Peak value in accordance with IEC/EN 60079-11) |
Supply
| Nominal Supply Voltage | 24 V DC |
| Supply Voltage Range | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
| Max. current consumption | < 40 mA (24 V DC) |
| Power dissipation | < 1 W |
Signal
| Number of Inputs | 1 |
| Input Signal | Temperature |
| Input Signal | Voltage |
| Voltage input signal | -20 mV ... 70 mV |
Measurement
| Description of the input | Intrinsically safe |
| Sensor types that can be used (TC) | E, J, K, N as per IEC / EN 60584, L as per DIN 43760 |
| Temperature measuring range | -250 °C ... 1372 °C (Range depending on the sensor type) |
| Sensor type: | -210 °C ... 1200 °C |
| Sensor type: | -200 °C ... 1372 °C |
| Sensor type: | -200 °C ... 1300 °C |
| Sensor type: | -226 °C ... 1000 °C |
| Sensor type: | -200 °C ... 900 °C |
| Linear mV signal range | -20 mV ... 70 mV |
| Temperature measuring range | Min. 50 K for thermocouples, 3 mV for mV sources |
Switching:
| Configurable/programmable | no |
Signal
| Output description | Current output |
| Number of Outputs | 1 |
| Configurable/programmable | Yes |
| Current Output Signal | 0 mA ... 20 mA |
| Current Output Signal | 4 mA ... 20 mA |
| Load/Output Load Current Output | ≤ 500 Ω |
| Output ripple (current) | < 50 µAPP |
| Output ripple (current) | < 10 µArms |
| Behavior in the event of a sensor error | As per NE 43 or can be freely defined |
Connection data
| Connection Method | Screw connection |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
Safety data
| Max. output voltage Uo | 6 V |
| Max. output current Io | 4.7 mA |
| Max. output power Po | 7 mW |
| Safety-related maximum voltage Um | 253 V AC |
| Safety-related maximum voltage Um | 125 V DC |
| IIC: Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 1.5 µF, 10 mH / 1.9 µF, 1 mH / 2.7 µF |
| IIB: Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 7 µF, 10 mH / 9.4 µF, 1 mH / 15 µF |
Signaling
| Status display | Green LED (supply voltage, PWR) |
| Status display | Red LED, flashing 2.4 Hz (cable error, sensor error on input or output, ERR) |
| Status display | Red LED, flashing 1.2 Hz (service operation, ERR) |
| Status display | Red LED, permanently on (module error, ERR) |
Dimensions
| Width | 12.5 mm |
| Height | 106.4 mm |
| Depth | 114.5 mm |
Material specifications
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Housing Material | PA 6.6-FR |
Ambient conditions
| Degree of Protection | IP20 (not assessed by UL) |
| Ambient Temperature (Operation) | -20 °C ... 60 °C (Any mounting position) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE
| Certificate | CE-compliant |
| Note | and EN 61326 |
ATEX
| Identification | II (1) G [Ex ia Ga] IIC/IIB |
| Identification | II (1) D [Ex ia Da] IIIC |
| Identification | II 3(1) G Ex nA ic [ia Ga] IIC T4 Gc X |
| Certificate | IBExU 09 ATEX 1030 |
IECEx
| Identification | [Ex ia Ga] IIC/IIB |
| Identification | [Ex ia Da] IIIC |
| Identification | Ex nA ic [ia Ga] IIC T4 Gc |
| Certificate | IECEx IBE 09.0002X |
UL, USA/Canada
| Identification | Class I Div 2; IS for Class I, II, III Div 1 |
| Certificate | , C.D.-No 83104549 |
KC-s
| Identification | [Ex ia] IIC/IIB |
| Certificate | 17-KA4BO-0415X |
Shipbuilding approval
| Identification | C, EMC1 |
| Certificate | GL 86 644-10HH |
EAC Ex
| Identification | [Ex ia Ga] IIC |
| Identification | [Ex ia Da] IIIC |
| Certificate | RU C-DE.AB72.B.00093/19 |
EMC data
| Noise immunity | EN 61000-6-2 |
| Note | When being exposed to interference, there may be minimal deviations. |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise emission | EN 61000-6-4 |
Electromagnetic HF field
| Designation | Electromagnetic RF field |
| Standards/regulations | EN 61000-4-3 |
Fast transients (burst)
| Designation | Fast transients (burst) |
| Standards/regulations | EN 61000-4-4 |
Conducted interference
| Designation | Conducted interferences |
| Standards/regulations | EN 61000-4-6 |
Mounting
| Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2865586?
Proax is an authorized distributor of Phoenix Contact 2865586 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |