SKU
MPN
MACX MCR-EX-SL-TC-I-NC
Weight
0.165 kg
This product is Not Cancellable/Not Returnable

MACX MCR-EX-SL-TC-I-NC - Temperature measuring transducer

Ex i temperature transducer: converts signals from thermocouples installed in the Ex area and mV sources and transmits a 0/4 - 20 mA signal to a load in the safe area. Freely programmable, 3-way isolation. Replacement item: 1050233 MACX MCR-EX-TC-I.

  • Power supply possible via DIN rail connector
  • Input for resistance thermometers and resistance-type sensors, [Ex ia] IIC
  • Programming during operation with Ex measuring circuit connected and also voltage-free using IFS-USB-PROG-ADAPTER programming adapter
  • Installation in zone 2, protection type "n" (EN 60079-15) permitted
  • 3-way electrical isolation
  • Status indicator for supply voltage, cable, sensor, and module errors
  • Configuration via software (FDT/DTM): sensor type, connection technology, measuring range, measuring unit, filter, alarm signal, and output range
  • Output: 0 mA ... 20 mA or 4 mA ... 20 mA
Technical Specifications

Product properties

ApplicationTemperature
No. of channels1
TypeEx i signal conditioners

Insulation characteristics

Overvoltage categoryII
Pollution degree2

Electrical properties

Alignment span± 5 %
Alignment zero± 5 %
Typical cold point errors± 1 K
Step response (0–99%)700 ms
Step response (0–99%)≤ 1100 ms
Temperature coefficient, typical0.01 %/K

Electrical isolation Input/output/power supply

Rated Insulation Voltage300 Vrms
Test voltage2.5 kV AC (50 Hz, 60 s)
InsulationSafe isolation in accordance with IEC/EN 61010-1

Electrical isolation Input/output

Electrical isolation375 V (Peak value in accordance with IEC/EN 60079-11)

Electrical isolation Input/power supply

Electrical isolation375 V (Peak value in accordance with IEC/EN 60079-11)

Supply

Nominal Supply Voltage24 V DC
Supply Voltage Range19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %)
Max. current consumption< 40 mA (24 V DC)
Power dissipation< 1 W

Signal

Number of Inputs1
Input SignalTemperature
Input SignalVoltage
Voltage input signal-20 mV ... 70 mV

Measurement

Description of the inputIntrinsically safe
Sensor types that can be used (TC)E, J, K, N as per IEC / EN 60584, L as per DIN 43760
Temperature measuring range-250 °C ... 1372 °C (Range depending on the sensor type)
Sensor type: -210 °C ... 1200 °C
Sensor type: -200 °C ... 1372 °C
Sensor type: -200 °C ... 1300 °C
Sensor type: -226 °C ... 1000 °C
Sensor type: -200 °C ... 900 °C
Linear mV signal range-20 mV ... 70 mV
Temperature measuring rangeMin. 50 K for thermocouples, 3 mV for mV sources

Switching:

Configurable/programmableno

Signal

Output descriptionCurrent output
Number of Outputs1
Configurable/programmableYes
Current Output Signal0 mA ... 20 mA
Current Output Signal4 mA ... 20 mA
Load/Output Load Current Output≤ 500 Ω
Output ripple (current)< 50 µAPP
Output ripple (current)< 10 µArms
Behavior in the event of a sensor errorAs per NE 43 or can be freely defined

Connection data

Connection MethodScrew connection
Stripping length7 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Tightening torque0.5 Nm ... 0.6 Nm

Safety data

Max. output voltage Uo6 V
Max. output current Io4.7 mA
Max. output power Po7 mW
Safety-related maximum voltage Um253 V AC
Safety-related maximum voltage Um125 V DC
IIC: Max. external inductivity Lo / Max. external capacitance Co100 mH / 1.5 µF, 10 mH / 1.9 µF, 1 mH / 2.7 µF
IIB: Max. external inductivity Lo / Max. external capacitance Co100 mH / 7 µF, 10 mH / 9.4 µF, 1 mH / 15 µF

Signaling

Status displayGreen LED (supply voltage, PWR)
Status displayRed LED, flashing 2.4 Hz (cable error, sensor error on input or output, ERR)
Status displayRed LED, flashing 1.2 Hz (service operation, ERR)
Status displayRed LED, permanently on (module error, ERR)

Dimensions

Width12.5 mm
Height106.4 mm
Depth114.5 mm

Material specifications

Colorgray (RAL 7042)
Flammability rating according to UL 94V0 (Housing)
Housing MaterialPA 6.6-FR

Ambient conditions

Degree of ProtectionIP20 (not assessed by UL)
Ambient Temperature (Operation)-20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m
Permissible humidity (operation)5 % ... 95 % (non-condensing)

CE

CertificateCE-compliant
Noteand EN 61326

ATEX

Identification II (1) G [Ex ia Ga] IIC/IIB
Identification II (1) D [Ex ia Da] IIIC
Identification II 3(1) G Ex nA ic [ia Ga] IIC T4 Gc X
CertificateIBExU 09 ATEX 1030

IECEx

Identification[Ex ia Ga] IIC/IIB
Identification[Ex ia Da] IIIC
IdentificationEx nA ic [ia Ga] IIC T4 Gc
CertificateIECEx IBE 09.0002X

UL, USA/Canada

IdentificationClass I Div 2; IS for Class I, II, III Div 1
Certificate, C.D.-No 83104549

KC-s

Identification[Ex ia] IIC/IIB
Certificate17-KA4BO-0415X

Shipbuilding approval

IdentificationC, EMC1
CertificateGL 86 644-10HH

EAC Ex

Identification [Ex ia Ga] IIC
Identification [Ex ia Da] IIIC
CertificateRU C-DE.AB72.B.00093/19

EMC data

Noise immunityEN 61000-6-2
NoteWhen being exposed to interference, there may be minimal deviations.
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4

Electromagnetic HF field

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3

Fast transients (burst)

DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4

Conducted interference

DesignationConducted interferences
Standards/regulationsEN 61000-4-6

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact 2865586?

Proax is an authorized distributor of Phoenix Contact 2865586 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability