MACX MCR-EX-SL-RPSSI-I - Power/input isolating amplifier

Ex i repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active 0/4 … 20 mA signals from the Ex area to a load (active or passive) in the safe area. 3-way electrical isolation, SIL 2 in accordance with IEC 61508, with screw connection

  • 0/4 mA ... 20 mA input, intrinsically safe, [Ex ia], powered and not powered
  • Measuring transducer supply voltage > 16 V
  • 0/4 mA ... 20 mA output, active up to 1000 Ω load or passive
  • Bidirectional HART signal transmission
  • Error indication according to NAMUR NE 43
  • SIL 2 according to IEC/EN 61508
  • Installation in zone 2, protection type "ec" (EN 60079-7) permitted
  • 3-way electrical isolation
  • Power supply possible via DIN rail connector
  • Plug-in connection terminal blocks, screw connection technology, with integrated sockets for HART communicators
  • Housing width: 12.5 mm
  • Minimal power dissipation
  • High transmission accuracy
Technical Specifications

Product properties

Product familyMACX Analog
ApplicationAnalog IN
No. of channels1
TypeEx i signal conditioners with SIL functional safety

Electrical properties

Electrical isolation3-way isolation
Electrical isolation between input and outputyes
Maximum power dissipation for nominal condition0.95 W (20 mA, 250 Ω)
Signal transmission behaviorIn = Out
Step response (10-90%)< 200 µs (for jump 4 mA ... 20 mA, load 600 Ω)
Step response (10-90%)< 600 µs (for jump 0 mA ... 20 mA, load 600 Ω)
Maximum temperature coefficient< 0.01 %/K
Temperature coefficient, typical< 0.004 %/K
Maximum transmission error< 0.1 % (of final value)
Transmission error, typical< 0.05 % (of final value)
Reverse polarity protectionyes

Electrical isolation

Test voltage2.5 kV AC (50 Hz, 60 s)
Overvoltage categoryII
Pollution degree2

Electrical isolation Input/output/power supply IEC/EN 61010-1

Standards/regulationsIEC/EN 61010-1
Rated Insulation Voltage300 Vrms
InsulationSafe isolation

Electrical isolation Input/output IEC/EN 60079-11

Standards/regulationsIEC/EN 60079-11
Rated Insulation Voltage265 Vrms

Electrical isolation Input/power supply IEC/EN 60079-11

Standards/regulationsIEC/EN 60079-11
Rated Insulation Voltage265 Vrms

Electrical isolation Output/supply IEC/EN 60079-7

Standards/regulationsIEC/EN 60079-7
Rated Insulation Voltage265 Vrms

Supply

DesignationRepeater power supply operation
Nominal Supply Voltage24 V DC -20 % ... +25 %
Supply Voltage Range19.2 V DC ... 30 V DC
Max. current consumption< 76 mA (24 V DC / 20 mA / 1000 Ω)
Max. current consumption< 55 mA (24 V DC / 20 mA / 250 Ω)
Power dissipation< 1.1 W (24 V DC / 20 mA / 1000 Ω)
Power dissipation< 0.95 W (24 V DC / 20 mA / 250 Ω)
Power dissipation< 1.2 W (24 V DC / 20 mA / 0 Ω)
Power consumption< 1.8 W (20 mA / 1000 Ω)
Power consumption< 1.3 W (20 mA / 250 Ω)
DesignationSignal conditioner operation
Nominal Supply Voltage24 V DC -20 % ... +25 %
Supply Voltage Range19.2 V DC ... 30 V DC
Max. current consumption< 44 mA (24 V DC / 20 mA / 1000 Ω)
Max. current consumption< 27 mA (24 V DC / 20 mA / 250 Ω)
Power dissipation< 0.75 W (24 V DC / 20 mA / 1000 Ω)
Power dissipation< 0.65 W (24 V DC / 20 mA / 250 Ω)
Power dissipation< 0.95 W (24 V DC / 20 mA / 0 Ω)

Signal: Repeater power supply operation

Description of the inputActive current input, intrinsically safe
Number of Inputs1
Input SignalCurrent
Current Input Signal4 mA ... 20 mA
Current limitation25 mA
Transmitter supply voltage> 16 V (20 mA)
Transmitter supply voltage> 15.3 V (22.5 mA)
Polarization and surge protectionYes
Underload/overload signal range0 mA ... 24 mA (Extended transmission range for diagnostics)

Signal: Signal conditioner operation

Description of the inputPassive current input, intrinsically safe
Current Input Signal0 mA ... 20 mA
Current Input Signal4 mA ... 20 mA
Voltage drop< 3.5 V (in input isolating amplifier operation)
Underload/overload signal range0 mA ... 24 mA (Extended transmission range for diagnostics)

Signal: Repeater power supply operation

Output descriptionCurrent output (active and passive)
Number of Outputs1
Current Output Signal4 mA ... 20 mA (active)
Current Output Signal4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load/Output Load Current Output< 1000 Ω (20 mA)
Load/Output Load Current Output< 825 Ω (24 mA)
Output ripple< 20 mVrms
Output behavior in the event of an error0 mA (Cable break in the input)
Output behavior in the event of an error≥ 22.5 mA (Cable short-circuit in the input)
Underload/overload signal range0 mA ... 24 mA (Extended transmission range for diagnostics)

Signal: Signal conditioner operation

Output descriptionCurrent output (active and passive)
Current Output Signal0 mA ... 20 mA (active)
Current Output Signal4 mA ... 20 mA (active)
Current Output Signal0 mA ... 20 mA (14 ... 26 V ext. source voltage)
Current Output Signal4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load/Output Load Current Output< 1000 Ω (20 mA)
Load/Output Load Current Output< 825 Ω (24 mA)
Output ripple< 20 mVrms
Output behavior in the event of an error0 mA (Cable break in the input)
Output behavior in the event of an error0 mA (Cable short-circuit in the input)
Underload/overload signal range0 mA ... 24 mA (Extended transmission range for diagnostics)

Connection data

Connection MethodScrew connection
Stripping length7 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Tightening torque0.5 Nm ... 0.6 Nm

Test socket

Max. diameter2 mm

Ex data

Ex installation (EPL)Gc
Ex installation (EPL)Div. 2
Ex i circuits (EPL)Ga
Ex i circuits (EPL)Da
Ex i circuits (EPL)Ma
Ex i circuits (EPL)Div. 1

Safety data: Repeater power supply operation

Max. output voltage Uo25.2 V
Max. output current Io93 mA
Max. output power Po587 mW
Safety-related maximum voltage Um253 V AC
Safety-related maximum voltage Um125 V DC
I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co40 mH / 4.8 µF
IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co26 mH / 2.9 µF
IIB (simple circuit): Max. external inductivity Lo / Max. external capacitance Co14 mH / 820 nF
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co3 mH / 107 nF
IIA (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co26 mH / 470 nF, 20 mH / 570 nF, 1 mH / 630 nF, 0.5 mH / 720 nF, 0.1 mH / 1.1 µF, 0.005 mH / 2.9 µF
IIB/III (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co16 mH / 370 nF, 500 µH / 510 nF, 200 µH / 660 nF, 100 µH / 820 nF
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co2.2 mH / 47 nF, 2 mH / 49 nF, 1 mH / 63 nF, 500 µH / 80 nF, 200 µH / 107 nF
I (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co37 mH / 0.54 µF, 0.35 mH / 1 µF, 0.009 mH / 2.9 µF, 0.001 mH / 4.15 µF

Safety data: Signal conditioner operation

Input voltage Ui≤ 30 V
Input current Ii≤ 150 mA
Max. internal inductance Linegligible
Max. internal capacitance Cinegligible
Safety-related maximum voltage Um253 V AC
Safety-related maximum voltage Um125 V DC

Data communication (bypass)

HART FunctionYes
Protocols SupportedHART-transparent

Signaling

Status displayGreen LED (supply voltage)

Dimensions

Width12.5 mm
Height112.5 mm
Depth113.7 mm
Depth NS 35/7,5114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)

Material specifications

Colorgray (RAL 7042)
Flammability rating according to UL 94V0 (Housing)
Housing MaterialPA 6.6-FR

Ambient conditions

Degree of ProtectionIP20 (not assessed by UL)
Ambient Temperature (Operation)-40 °C ... 60 °C (Any mounting position)
Ambient Temperature (Operation)-40 °C ... 70 °C (Derating)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)

Altitude range (≤ 2000 m)

Altitude≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.)
Ambient Temperature (Operation)-40 °C ... 60 °C
Ambient Temperature (Operation)-40 °C ... 70 °C (Derating)
Rated Insulation Voltage375 VPP (Power supply, input / output)

Altitude range (≤ 3000 m)

Height Range> 2000 m ... 3000 m
Ambient Temperature (Operation)-40 °C ... 54 °C
Ambient Temperature (Operation)-40 °C ... 63 °C (Derating)
Rated Insulation Voltage190 V AC (Power supply, input / output)
Rated Insulation Voltage110 V DC (Power supply, input / output)

Altitude range (≤ 4000 m)

Height Range> 3000 m ... 4000 m
Ambient Temperature (Operation)-40 °C ... 48 °C
Ambient Temperature (Operation)-40 °C ... 56 °C (Derating)
Rated Insulation Voltage60 V AC/DC (Power supply, input / output)

Altitude range (≤ 5000 m)

Height Range> 4000 m ... 5000 m
Ambient Temperature (Operation)-40 °C ... 42 °C
Ambient Temperature (Operation)-40 °C ... 49 °C (Derating)
Rated Insulation Voltage60 V AC/DC (Power supply, input / output)

CE

CertificateCE-compliant
Noteand EN 61326

ATEX

Identification II (1) G [Ex ia Ga] IIC
Identification II (1) D [Ex ia Da] IIIC
Identification II 3(1) G Ex ec [ia Ga] IIC T4 Gc
Identification I (M1) [Ex ia Ma] I
CertificateBVS 08 ATEX E 054X

IECEx

Identification[Ex ia Ga] IIC
Identification[Ex ia Da] IIIC
IdentificationEx ec [ia Ga] IIC T4 Gc
Identification[Ex ia Ma] I
CertificateIECEx BVS 08.0016X

CCC / China-Ex

Identification[Ex ia Ga] IIC
Identification[Ex ia Da] IIIC
IdentificationEx ec [ia Ga] IIC T4 Gc
Certificate2022122316115973

UL, USA/Canada

IdentificationUL 61010 Listed
IdentificationClass I, Div. 2, Groups A, B, C, D T4
IdentificationClass I, Div. 2, Groups IIC, IIB, IIA T4
IdentificationAssociated apparatus for use in Class I, Division 1, Groups A,B,C,D
IdentificationAssociated apparatus for use in Class II, Div.1 Groups E,F,G
IdentificationAssociated apparatus for use in Class III, Division 1
IdentificationAssociated apparatus for use in Class I, Zone 0,1,2, Groups IIC,IIB,IIA
Certificate, C.D.-No 83104549
IdentificationUL 61010 Listed
IdentificationClass I Div 2; IS for Class I, II, III Div 1
Certificate, C.D.-No 83104549

Shipbuilding approval

CertificateDNV GL TAA000020C

Safety Integrity Level (SIL, IEC 61508)

Identification2
CertificateIN-AT-AS-MRL-2300149

Systematic Capability

Identification3

KC-s

Identification[Ex ia] IIC/IIB
Certificate17-KA4BO-0400X

INMETRO

Identification[Ex ia Ga] IIC
Identification[Ex ia Da] IIIC
IdentificationEx ec [ia Ga] IIC T4 Gc
Identification[Ex ia Ma] I
CertificateDNV 18.0136 X

DNV GL data

TemperatureB
HumidityB
VibrationA
EMCA
EnclosureRequired protection according to the Rules shall be provided upon installation on board

EMC data

Noise immunityEN 61000-6-2
NoteWhen being exposed to interference, there may be minimal deviations.
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4

Electromagnetic HF field

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value1 %

Fast transients (burst)

DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value1 %

Conducted interference

DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value1 %

Standards and Regulations

Electrical isolation3-way isolation

GB Standard

Standards/regulationsGB/T 3836.1
Standards/regulationsGB/T 3836.3
Standards/regulationsGB/T 3836.4

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact 2865340?

Proax is an authorized distributor of Phoenix Contact 2865340 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability