MACX MCR-EX-IDS-2I-2I - Output signal conditioner
2-channel Ex i output signal conditioner, HART-transparent. Isolates and transmits 0/4 mA … 20 mA signals with intrinsic safety to a load in the Ex area. 4-way electrical isolation, line fault detection, SIL 2 (SC3) in accordance with IEC 61508, screw connection.
Technical Specifications
Product properties
Product family | MACX Analog |
No. of channels | 2 |
Type | Ex i signal conditioners with SIL functional safety |
Electrical properties
Electrical isolation | 4-way isolation |
Signal transmission behavior | In = Out |
Step response (10-90%) | < 140 µs (for 4 mA ... 20 mA step) |
Maximum temperature coefficient | 0.01 %/K |
Temperature coefficient, typical | ≤ 0.005 %/K |
Maximum transmission error | 0.1 % (of final value) |
Transmission error, typical | ≤ 0.05 % (of final value) |
Electrical isolation
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation Input/output IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation |
Electrical isolation Input/power supply IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 50 Vrms |
Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Insulation | Basic insulation |
Electrical isolation Output/supply IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Insulation | Safe isolation |
Electrical isolation Input 1/input 2, output 1/output 2
Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Electrical isolation Output/input IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 375 VPP |
Electrical isolation Output/supply IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 375 VPP |
Electrical isolation Output 1/output 2 IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 60 VPP |
Supply
Nominal Supply Voltage | 24 V DC -20 % ... +25 % |
Supply Voltage Range | 19.2 V DC ... 30 V DC |
Max. current consumption | < 85 mA (24 V DC / 20 mA) |
Power dissipation | < 1.4 W (24 V DC / 20 mA) |
Power consumption | ≤ 2 W (24 V DC / 20 mA) |
Signal: Current
Current Input Signal | 0.2 mA ... 20 mA (Function) |
Current Input Signal | 4 mA ... 20 mA (Safety) |
Current Input Signal | 0 mA ... 24 mA (Underload/overload range) |
Input Current | ≤ 30 mA |
Input Impedance | > 1 MΩ (If there is a line fault) |
Line fault detection | > 0.2 mA (Response threshold of input current) |
Voltage drop | < 2.4 V (20 mA) |
Output description | intrinsically safe |
Current Output Signal | 0.2 mA ... 20 mA (Function) |
Current Output Signal | 4 mA ... 20 mA (Safety) |
Current Output Signal | 0 mA ... 24 mA (Underload/overload range) |
Load | 100 Ω ... 700 Ω (20 mA) |
Load | 100 Ω ... 650 Ω (20.5 mA) |
Load | 100 Ω ... 500 Ω (24 mA) |
Output ripple | < 20 mVrms |
Non-load voltage | ≤ 27 V |
Line fault detection | > 10 kΩ (Line break) |
Line fault detection | < 50 Ω (Short circuit) |
Connection data
Connection Method | Screw connection |
Stripping length | 7 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
COMBICON connection
Max. diameter | 2 mm |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Ex i circuits (EPL) | Ga |
Ex i circuits (EPL) | Da |
Ex i circuits (EPL) | Ma |
Ex i circuits (EPL) | Div. 1 |
Safety data
Max. internal inductance Li | negligible |
Max. internal capacitance Ci | negligible |
Max. output voltage Uo | 25.2 V |
Max. output current Io | 93 mA |
Max. output power Po | 586 mW |
Safety-related maximum voltage Um | 253 V AC |
Safety-related maximum voltage Um | 125 V DC |
IIA (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 10 mH / 2.9 µF |
IIB (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 4 mH / 817 nF |
IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 2 mH / 104 nF |
IIA (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 10 mH / 587 nF, 1 mH / 627 nF, 500 µH / 717 nF, 200 µH / 907 nF, 100 µH / 1.1 µF |
IIB (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 4 mH / 367 nF, 1 mH / 427 nF, 500 µH / 507 nF, 200 µH / 657 nF, 100 µH / 817 nF |
IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 2 mH / 46 nF, 1 mH / 60 nF, 500 µH / 77 nF, 200 µH / 104 nF |
Data communication (bypass)
HART Function | Yes |
Protocols Supported | HART-transparent |
Signaling
Status display | Green LED (supply voltage) |
Dimensions
Width | 12.5 mm |
Height | 112.5 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing Material | PA 6.6-FR |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Any mounting position) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Altitude range (≤ 2000 m (Ex))
Description | Ex applications |
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient Temperature (Operation) | -40 °C ... 70 °C |
Safety-related maximum voltage Um | 253 V AC |
Safety-related maximum voltage Um | 125 V DC |
Rated Insulation Voltage | 320 V (Power supply, input / output) |
Altitude range (≤ 3000 m (Ex))
Description | Ex applications |
Height Range | > 2000 m ... 3000 m |
Ambient Temperature (Operation) | -40 °C ... 60 °C |
Safety-related maximum voltage Um | 190 V AC |
Safety-related maximum voltage Um | 110 V DC |
Rated Insulation Voltage | 190 V (Power supply, input / output) |
Altitude range (≤ 4000 m (Ex))
Description | Ex applications |
Height Range | > 3000 m ... 4000 m |
Ambient Temperature (Operation) | -40 °C ... 55 °C |
Safety-related maximum voltage Um | 60 V AC |
Safety-related maximum voltage Um | 60 V DC |
Rated Insulation Voltage | 63 V (Power supply, input / output) |
Altitude range (≤ 5000 m (Ex))
Description | Ex applications |
Height Range | > 4000 m ... 5000 m |
Ambient Temperature (Operation) | -40 °C ... 45 °C |
Safety-related maximum voltage Um | 60 V AC |
Safety-related maximum voltage Um | 60 V DC |
Rated Insulation Voltage | 63 V (Power supply, input / output) |
Altitude range (≤ 2000 m)
Description | Non-Ex applications (EN 61010-1) |
Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
Ambient Temperature (Operation) | -40 °C ... 70 °C |
Rated Insulation Voltage | 300 V (Power supply, input / output) |
Altitude range (≤ 3000 m)
Description | Non-Ex applications (EN 61010-1) |
Height Range | > 2000 m ... 3000 m |
Ambient Temperature (Operation) | -40 °C ... 60 °C |
Rated Insulation Voltage | 150 V (Power supply, input / output) |
Altitude range (≤ 4000 m)
Description | Non-Ex applications (EN 61010-1) |
Height Range | > 3000 m ... 4000 m |
Ambient Temperature (Operation) | -40 °C ... 55 °C |
Rated Insulation Voltage | 150 V (Power supply, input / output) |
Altitude range (≤ 5000 m)
Description | Non-Ex applications (EN 61010-1) |
Height Range | > 4000 m ... 5000 m |
Ambient Temperature (Operation) | -40 °C ... 45 °C |
Rated Insulation Voltage | 150 V (Power supply, input / output) |
CE
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX
Identification | I (M1) [Ex ia Ma] I |
Identification | II (1) G [Ex ia Ga] IIC |
Identification | II (1) D [Ex ia Da] IIIC |
Identification | II 3(1) G Ex ec [ia Ga] IIC T4 Gc |
Certificate | BVS 20 ATEX E 004 X |
IECEx
Identification | [Ex ia Ma] I |
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia Ga] IIC T4 Gc |
Certificate | IECEx BVS 20.0003X |
CCC / China-Ex
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia Ga] IIC T4 Gc |
Certificate | 2021122316114080 |
UL, USA/Canada
Identification | UL 61010 Listed |
Identification | Class I Div 2; IS for Class I, II, III Div 1 |
Certificate | , C.D.-No 83104549 |
Shipbuilding approval
Certificate | DNV GL TAA00000AG |
Safety Integrity Level (SIL, IEC 61508)
Identification | 3 |
Systematic Capability
Identification | 3 |
INMETRO
Identification | [Ex ia Ga] IIC |
Identification | [Ex ia Da] IIIC |
Identification | Ex ec [ia Ga] IIC T4 Gc |
Identification | [Ex ia Ma] I |
Certificate | DNV 21.0092 X |
DNV GL data
Temperature | B |
Humidity | B |
Vibration | A |
EMC | B |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Standards and Regulations
Electrical isolation | 4-way isolation |
GB Standard
Standards/regulations | GB/T 3836.1 |
Standards/regulations | GB/T 3836.3 |
Standards/regulations | GB/T 3836.4 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2865421?
Proax is an authorized distributor of Phoenix Contact 2865421 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- MACX MCR-EX-IDS-I-I-SP - Ex i output signal conditioner, HART-transparent. Isolates and transmits 0/4 mA … 20 mA signals with intrinsic safety to a load in the Ex area. 3-way electrical isolation, line fault detection (can be switched off via DIP switch), SIL 2 (SC3) in accordance with IEC 61508, Push-in connection.