Official Distributor
SKU
MPN
2981732
Weight
0.234 kg
This product is Not Cancellable/Not Returnable
Series PSR-SCP
PSR-SCP- 24DC/URD3/4X1/2X2/3 - Extension module
1-channel contact extension with TBUS interface, 4 N/O contacts, 1 N/C contact, 1 confirmation current path, the contacts have an off-delay (0.3 … 3 s), Cat. 3, PL e in accordance with EN ISO 13849, plug-in terminal blocks with screw connection, width: 22.5 mm
- Up to Cat. 3/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
Technical Specifications
Product properties
Product family | PSRclassic |
Application | Extension module |
Mechanical service life | approx. 107 cycles |
Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
Electrical properties
Maximum power dissipation for nominal condition | 2.02 W |
Nominal operating mode | 100% operating factor |
Air clearances and creepage distances between the power circuits
Rated Insulation Voltage | 250 V |
Rated surge voltage/insulation | 4 kV / basic isolation (safe isolation, reinforced insulation and 6 kV between input circuit/N/C contacts and enabling current paths). |
General
Nominal input voltage UN | 24 V DC |
Input voltage range in reference to UN | 0.85 ... 1.1 |
Typical input current at UN | 94 mA |
Typical response time | 20 ms |
Typical release time range | 0.3 s ... 3 s +50 % (adjustable) |
Recovery time | 1 s |
Protective circuit | Fuse; PTC resistor |
Protective circuit | Surge protection; Suppressor diode |
Operating voltage display | Green LED |
Status display | Green LED |
Output data
Contact switching type | 4 delayed enabling current paths |
Contact switching type | 1 delayed signaling current path |
Contact switching type | 1 delayed confirmation current path |
Contact Material | AgSnO2 |
Maximum Switching Voltage | 250 V AC/DC |
Minimum Switching Voltage | 15 V AC/DC |
Limiting Continuous Current | 6 A (N/O contact) |
Limiting Continuous Current | 3 A (N/C contact) |
Maximum Inrush Current | 6 A (N/O contact) |
Maximum Inrush Current | 3 A (N/C contact) |
Inrush current, minimum | 25 mA |
Sq. Total current | 50 A2 (ITH2 = I12 + I22 + I32 + I42) |
Interrupting rating (ohmic load) max. | 144 W (24 V DC, τ = 0 ms, N/C contact 65/66: 72 W) |
Interrupting rating (ohmic load) max. | 288 W (48 V DC, τ = 0 ms, N/C contact 65/66: 144 W) |
Interrupting rating (ohmic load) max. | 77 W (110 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 88 W (220 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 1500 VA (250 V AC, τ = 0 ms, N/C contact 65/66: 750 VA) |
Maximum interrupting rating (inductive load) | 48 W (24 V DC, τ = 40 ms) |
Maximum interrupting rating (inductive load) | 40 W (48 V DC, τ = 40 ms) |
Maximum interrupting rating (inductive load) | 35 W (110 V DC, τ = 40 ms) |
Maximum interrupting rating (inductive load) | 33 W (220 V DC, τ = 40 ms) |
Switching capacity min. | 0.4 W |
Switching capacity (360/h cycles) | 6 A (24 V DC) |
Switching capacity (360/h cycles) | 5 A (230 V AC) |
Switching capacity (3600/h cycles) | 3 A (24 V (DC13)) |
Switching capacity (3600/h cycles) | 3 A (230 V (AC15)) |
Output fuse | 10 A gL/gG NEOZED (N/O contact) |
Output fuse | 4 A gL/gG NEOZED (N/C contact) |
Connection technology
pluggable | yes |
Conductor connection
Connection Method | Screw connection |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross-section AWG | 24 ... 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Dimensions
Width | 22.5 mm |
Height | 99 mm |
Depth | 114.5 mm |
Material specifications
Color (Housing) | yellow (RAL 1018) |
Housing Material | Polyamide |
Safety data
Stop category | 1 |
Safety data: EN ISO 13849
Category | 3 (In conjunction with suitable evaluating device) |
Performance level (PL) | e (In conjunction with suitable evaluating device) |
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
Safety data: EN IEC 62061
Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
Ambient conditions
Degree of Protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Ambient Temperature (Operation) | -20 °C ... 55 °C |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Maximum altitude | max. 2000 m (Above sea level) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Air clearances and creepage distances between the power circuits
Standards/regulations | IEC 60664-1 |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any |
Accessories
Why Proax for Phoenix Contact PSR-SCP- 24DC/URD3/4X1/2X2/3?
Proax is an authorized distributor of Phoenix Contact PSR-SCP- 24DC/URD3/4X1/2X2/3 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | PSRSCP24DCURD34X12X23 |
Pack Size | 1 |
Recommended