Official Distributor
SKU
MPN
PSR-SCP- 24DC/MXF1/4X1/2X2/B
Weight
0.287 kg
Series PSR-SCP
PSR-SCP- 24DC/MXF1/4X1/2X2/B - Safety relays
Multifunctional safety relay for emergency stop and safety doors up to SIL 3, Cat. 4, PL e, automatically or manually monitored activation, 4 N/O contacts, 3 safety functions, 2 shutdown levels, plug-in screw terminal block
- Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
- 3 safety functions in one device
- Low housing width of only 22.5mm
- No software configuration required
- Also available with push-in connection
Technical Specifications
Product properties
Application | Emergency stop |
Application | Safety door |
Mechanical service life | 10x 106 cycles |
Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
Electrical properties
Maximum power dissipation for nominal condition | 3 W |
Nominal operating mode | 100% operating factor |
Air clearances and creepage distances between the power circuits
Rated Insulation Voltage | 250 V AC |
Rated surge voltage/insulation | 4 kV/basic isolation (safe isolation, reinforced insulation and 6 kV between input circuit, enabling current paths and safety circuit 1 (13/14, 23/24) and safety circuit 2 (43/44, 53/54).) |
General
Nominal input voltage UN | 24 V DC |
Input voltage range in reference to UN | 0.85 ... 1.1 |
Typical input current at UN | 125 mA (with actuated relays) |
Typical input current at UN | 55 mA (Two-channel 24 V/0 V + max. 200 mA control (message outputs 32/62) with non-actuated relays) |
Current consumption | typ. 5 mA (Imax/Ix inputs) |
Current consumption | 20 mA (in electric torque) |
Voltage at input/start and feedback circuit | 24 V -15 % / +10 % (first channel: 24 V; second channel: 0 V) |
Filter time | max. 1.5 ms (Test pulse duration; for all equivalent inputs) |
Filter time | min. 7.5 ms (Test pulse rate; for all equivalent inputs) |
Typical response time | 175 ms (monitored/manual start) |
Typical response time | 250 ms (automatic start) |
Typ. starting time with Us | 250 ms (when controlled via A1) |
Typical release time | 25 ms (when controlled via S11/I1,I3,I5 and S21/I2,I4,I6) |
Typical release time | 20 ms (when controlled via A1) |
Concurrence | ∞ |
Recovery time | 1 s (Availability time after activation of sensor circuit: 100ms) |
Maximum switching frequency | 0.5 Hz |
Protective circuit | Surge protection; Suppressor diode |
Max. permissible overall conductor resistance | 100 Ω |
Operating voltage display | 1 x green LED |
Status display | 5x LED green |
Output data
Contact switching type | 4 enabling current paths |
Contact switching type | 2 semiconductor alarm outputs |
Contact Material | AgCuNi, +0.2 ... 0.4 µm Au |
Maximum Switching Voltage | 250 V AC/DC |
Minimum Switching Voltage | 10 V AC/DC |
Limiting Continuous Current | 6 A (N/O contact) |
Limiting Continuous Current | max. 100 mA (Alarm output (24 V DC)) |
Maximum Inrush Current | 6 A |
Inrush current, minimum | 10 mA |
Sq. Total current | 72 A2 (ITH2 = I12 + I22+ I32+ I42) |
Interrupting rating (ohmic load) max. | 1500 VA (250 V AC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 66 W (220 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 66 W (110 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 100 W (48 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 144 W (24 V DC, τ = 0 ms) |
Maximum interrupting rating (inductive load) | 48 W (24 V DC, τ = 40 ms) |
Maximum interrupting rating (inductive load) | 43 W (48 V DC, τ = 40 ms) |
Switching capacity min. | 0.1 W |
Switching capacity (360/h cycles) | 5 A (0,1 Hz; DC13; 24 V) |
Switching capacity (3600/h cycles) | 3 A (AC15; 230 V) |
Output fuse | 6 A gL/gG NEOZED (N/O contact) |
Output fuse | 4 A gL/gG NEOZED (for low-demand applications) |
Connection technology
pluggable | yes |
Conductor connection
Connection Method | Screw connection |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross-section AWG | 24 ... 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Dimensions
Width | 22.5 mm |
Height | 112.2 mm |
Depth | 114.5 mm |
Material specifications
Color | yellow |
Safety data
Stop category | 0 |
Safety data: EN ISO 13849
Category | 4 |
Performance level (PL) | e (5 A DC13; 3 A AC15; 8760 cycles/year) |
Safety data: EN 50156
Safety Integrity Level (SIL) | 3 |
Safety data
Safety Integrity Level (SIL) | 3 |
Safety Integrity Level (SIL) | 3 |
Safety Integrity Level (SIL) | 3 |
Ambient conditions
Degree of Protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Ambient Temperature (Operation) | -20 °C ... 45 °C (see derating curve) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Maximum altitude | ≤ 2000 m (Above sea level) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Air clearances and creepage distances between the power circuits
Standards/regulations | IEC 60664-1 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | See derating curve |
Mounting Position | vertical or horizontal |
Why Proax for Phoenix Contact 2902725?
Proax is an authorized distributor of Phoenix Contact 2902725 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended