2986096
SKU
PHX2986096
MPN
PSR-SCP- 24DC/TS/SDOR4/4X1
Weight
0.201 kg
This product is Not Cancellable/Not Returnable
Series PSR-SCP
PSR-SCP- 24DC/TS/SDOR4/4X1 - Extension module
PSR-TRISAFE-M relay output extension module with 4 safe relay output contacts (choice of 4 single-channel or 2 two-channel relay contacts), 4 alarm outputs; up to SIL 3, Cat.4/PLe, SIL 3, EN 50156, plug-in screw connection terminal blocks
Technical Specifications
Product properties
| Application | PSR-TRISAFE-M extension module | 
Insulation characteristics: Air clearances and creepage distances between the power circuits
| Overvoltage category | III | 
| Pollution degree | 2 | 
Times
| Response time | max. 50 ms | 
| Recovery time | < 10 s | 
Electrical properties
| Maximum power dissipation for nominal condition | 3932 mW (up to 40°C ambient temperature, at m = 4, n = 4, Iload = 4 A, Isignal = 50 mA) | 
| Maximum power dissipation for nominal condition | 1532 mW (up to 55°C ambient temperature, at m = 4, n = 4, Iload = 1 A, Isignal = 50 mA) | 
| Nominal operating mode | 100% operating factor | 
| Interfaces | DIN rail TBUS for connection to the master module, supplied as standard | 
Air clearances and creepage distances between the power circuits
| Rated Insulation Voltage | 250 V AC | 
| Rated surge voltage/insulation | 4 kV / basic insulation between output contact current paths (13/14, 23/24, 33/34, 43/44); 6 kV / safe isolation, reinforced insulation between output contact current paths (13/14, 23/24, 33/34, 43/44) and the other circuits | 
Supply
| Rated control circuit supply voltage US | 18 V DC ... 30 V DC (Incl. all tolerances, incl. residual ripple) | 
| Rated control circuit supply voltage US | 24 V DC (Electrical supply via PSR-TBUS) | 
| Rated control supply current IS | Electrical supply via PSR-TBUS | 
| Rated control supply current IS | 74 mA (At 24 V DC, relay outputs set) | 
| Rated control supply current IS | 54 mA (At 24 V DC, relay outputs not set) | 
| Protective circuit | Yes, within the scope of the operating voltage limits | 
| Status display | 1 x green LED, 1 x red LED | 
Output data
| Maximum Switching Voltage | 250 V AC | 
| Maximum Switching Voltage | 24 V DC | 
| Minimum Switching Voltage | 5 V AC/DC | 
| Limiting Continuous Current | 4 A (see derating curve) | 
| Maximum Inrush Current | 6 A | 
| Inrush current, minimum | 5 mA | 
| Switching capacity (3600/h cycles) | 3 A (230 V (AC 15)) | 
| Switching capacity (3600/h cycles) | 5 A (24 V (DC13)) | 
| Output fuse | 6 A gL/gG | 
| Response time | max. 50 ms | 
Relay
| Output description | Relay contacts, safety-related N/O contacts | 
| Number of Outputs | 4 (Single-channel) | 
| Number of Outputs | 2 (Two-channel, connected in pairs) | 
| Contact switching type | 4 relay output contacts | 
| Contact Material | AgSnO2 (From HW03)AgCuNi +0.2 ... 0.4 μm Au (up to HW02) | 
| Switching voltage | min. 12 V AC/DC (from HW 03) | 
| Switching voltage | min. 5 V AC/DC (Up to HW02) | 
| Switching voltage | max. 250 V AC/DC | 
| Switching current | min. 3 mA (from HW 03) | 
| Switching current | min. 5 mA (Up to HW02) | 
| Switching capacity | min. 60 mW | 
| Limiting Continuous Current | 4 A (see to derating) | 
| Mechanical service life | 10x 10⁶ cycles | 
| Output fuse | 6 A (gL/gG) | 
| Output fuse | 4 A (gL/gG for low-demand applications) | 
| Status display | 4 x green LEDs | 
Signal
| Output description | Digital | 
| Number of Outputs | 4 | 
| Voltage | 24 V DC (Supply via A1/A2) | 
| Limiting Continuous Current | 50 mA | 
| Protective circuit | Yes, within the scope of the operating voltage limits | 
| Short-circuit protection | Yes | 
Connection technology
| pluggable | yes | 
Conductor connection
| Connection Method | Screw connection | 
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² | 
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² | 
| Conductor cross-section AWG | 24 ... 12 | 
| Stripping length | 7 mm | 
| Screw thread | M3 | 
| Tightening torque | 0.5 Nm ... 0.6 Nm | 
| Tightening torque | 5 lbf-in. ... 7 lbf-in. | 
Dimensions
| Width | 22.5 mm | 
| Height | 99 mm | 
| Depth | 114.5 mm | 
Material specifications
| Color | yellow | 
| Housing Material | Polyamide PA non-reinforced | 
Safety data
| Stop category | 0 | 
Safety data: EN ISO 13849
| Category | 1 (1-channel parameterization) | 
| Category | 4 (2-channel parameterization) | 
| Performance level (PL) | c (1-channel parameterization) | 
| Performance level (PL) | e (2-channel parameterization) | 
Safety data: EN 50156
| Safety Integrity Level (SIL) | max. 3 (Reference IEC 61508) | 
Safety data: IEC 61508 - High demand
| Safety Integrity Level (SIL) | 1 (1-channel parameterization) | 
| Safety Integrity Level (SIL) | 3 (2-channel parameterization) | 
Safety data: IEC 61508 - Low demand
| Safety Integrity Level (SIL) | 1 (1-channel parameterization) | 
| Safety Integrity Level (SIL) | 3 (2-channel parameterization) | 
Safety data: EN IEC 62061
| Safety Integrity Level (SIL) | 1 (1-channel parameterization) | 
| Safety Integrity Level (SIL) | 3 (2-channel parameterization) | 
Ambient conditions
| Degree of Protection | IP20 | 
| Min. degree of protection of inst. location | IP54 | 
| Ambient Temperature (Operation) | -20 °C ... 55 °C (see to derating) | 
| Ambient temperature (storage/transport) | -20 °C ... 70 °C | 
| Maximum altitude | max. 2000 m (See Appendix "Using PSR-TRISAFE modules at altitudes greater than 2000 m above sea level") | 
| Max. permissible humidity (storage/transport) | 75 % (On average, 85 % occasionally) | 
| Max. permissible relative humidity (operation) | 75 % (On average, 85 % occasionally) | 
| Shock (operation) | 10g (Δt = 11 ms, three shocks in each space direction) | 
| Shock (operation) | 10g (Δt = 16 ms, continuous shock, 1000 shocks in each space direction) | 
| Vibration (Operation) | 2g | 
| Air pressure (operation) | 70 kPa ... 108 kPa (up to 3000 m above sea level) | 
| Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) | 
Air clearances and creepage distances between the power circuits
| Standards/regulations | DIN EN 50178 | 
Mounting
| Mounting Type | DIN rail mounting | 
| Mounting Position | On horizontal DIN rail | 
Accessories
 ME 22,5 TBUS 1,5/ 5-ST-3,81 GN - DIN rail connector, color: green, nominal current: 8 A (parallel contacts), rated voltage (III/2): 125 V, number of positions: 5, product range: TBUS5-22,5.., pitch: 3.81 mm, mounting: DIN rail mounting, locking: without, mounting: without, type of packaging: packed in cardboard, Item with gold-plated contacts, bus connectors for connecting with electronics housings, 5 parallel contacts ME 22,5 TBUS 1,5/ 5-ST-3,81 GN - DIN rail connector, color: green, nominal current: 8 A (parallel contacts), rated voltage (III/2): 125 V, number of positions: 5, product range: TBUS5-22,5.., pitch: 3.81 mm, mounting: DIN rail mounting, locking: without, mounting: without, type of packaging: packed in cardboard, Item with gold-plated contacts, bus connectors for connecting with electronics housings, 5 parallel contacts
Why Proax for Phoenix Contact 2986096?
Proax is an authorized distributor of Phoenix Contact 2986096 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 | 
Recommended
 PSR-SCP- 24DC/FSP2/2X1/1X2 - Safe coupling relay for SIL 2 high- and low-demand applications, couples digital output signals to the periphery, two enabling current paths, one signal contact, module for safe state off applications, integrated test pulse filter, plug-in screw connection, width: 17.5 mm PSR-SCP- 24DC/FSP2/2X1/1X2 - Safe coupling relay for SIL 2 high- and low-demand applications, couples digital output signals to the periphery, two enabling current paths, one signal contact, module for safe state off applications, integrated test pulse filter, plug-in screw connection, width: 17.5 mm
 PSR-SCP- 24DC/FSP/2X1/1X2 - Safe coupling relay for SIL 3 high- and low-demand applications, couples digital output signals to the periphery, two enabling current paths, one signal contact, module for safe state off applications, integrated test pulse filter, plug-in screw connection, width: 17.5 mm PSR-SCP- 24DC/FSP/2X1/1X2 - Safe coupling relay for SIL 3 high- and low-demand applications, couples digital output signals to the periphery, two enabling current paths, one signal contact, module for safe state off applications, integrated test pulse filter, plug-in screw connection, width: 17.5 mm