Official Distributor
SKU
MPN
PSR-SCP- 24UC/URM4/5X1/2X2/B
This product is Not Cancellable/Not Returnable
Series PSR-SCP
PSR-SCP- 24UC/URM4/5X1/2X2/B - Extension module
Single or two-channel contact extension, 5 N/O contacts, 1 N/C contact, 1 confirmation current path, plug-in screw terminal blocks, width: 22.5 mm
- 1- and 2-channel control
- Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
Technical Specifications
Product properties
Product family | PSRclassic |
Application | Extension module |
Mechanical service life | 10x 106 cycles |
Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
Electrical properties
Maximum power dissipation for nominal condition | 2.21 W |
Nominal operating mode | 100% operating factor |
Air clearances and creepage distances between the power circuits
Rated Insulation Voltage | 250 V AC |
Rated surge voltage/insulation | Basic insulation 4 kV:between all current paths and housingSafe isolation, reinforced insulation 6 kV:between A1/A2, 11/12, 23/24, 71/72 and 33/34, 43/44, 53/54, 63/64 |
General
Rated control circuit supply voltage US | 24 V AC/DC -15 % / +10 % |
Power consumption at US | typ. 1.94 W (AC) |
Power consumption at US | typ. 1.7 W (DC) |
Rated control supply current IS | typ. 81 mA AC |
Rated control supply current IS | typ. 71 mA DC |
Inrush Current | 175 mA (Δt = 5 ms at Us) |
Filter time | 2 ms (at A1 in the event of voltage dips at Us) |
Typ. starting time with Us | < 20 ms (when controlled via A1) |
Typical release time | < 20 ms (when controlled via A1) |
Recovery time | < 1 s |
Maximum switching frequency | 1 Hz |
Protective circuit | Surge protection; Varistor |
Output data
Contact switching type | 5 enabling current paths |
Contact switching type | 1 confirmation current path |
Contact switching type | 1 signaling current path |
Contact Material | AgSnO2 |
Maximum Switching Voltage | 250 V AC/DC (Observe the load curve) |
Minimum Switching Voltage | 5 V AC/DC |
Limiting Continuous Current | 6 A (N/O contact, pay attention to the derating) |
Limiting Continuous Current | 6 A (N/C contact) |
Maximum Inrush Current | 20 A (Δt 100 ms) |
Inrush current, minimum | 10 mA |
Sq. Total current | 72 A2 (observe derating) |
Interrupting rating (ohmic load) max. | 144 W (24 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 288 W (48 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 110 W (110 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 88 W (220 V DC, τ = 0 ms) |
Interrupting rating (ohmic load) max. | 1500 VA (250 V AC, τ = 0 ms) |
Maximum interrupting rating (inductive load) | 42 W (24 V DC, τ = 40 ms) |
Maximum interrupting rating (inductive load) | 42 W (48 V DC, τ = 40 ms) |
Maximum interrupting rating (inductive load) | 42 W (110 V DC, τ = 40 ms) |
Maximum interrupting rating (inductive load) | 42 W (220 V DC, τ = 40 ms) |
Switching capacity min. | 50 mW |
Switching capacity (360/h cycles) | 4 A (24 V DC) |
Switching capacity (360/h cycles) | 4 A (230 V AC) |
Switching capacity (3600/h cycles) | 2.5 A (24 V (DC13)) |
Switching capacity (3600/h cycles) | 3 A (230 V (AC15)) |
Output fuse | 10 A gL/gG (N/O contact) |
Output fuse | 6 A gL/gG (N/C contact) |
Connection technology
pluggable | yes |
Conductor connection
Connection Method | Screw connection |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross-section AWG | 24 ... 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Signaling
Operating voltage display | 1 x green LED |
Dimensions
Width | 22.5 mm |
Height | 99 mm |
Depth | 114.5 mm |
Material specifications
Color (Housing) | yellow (RAL 1018) |
Housing Material | Polyamide |
Safety data
Stop category | 0 |
Safety data: EN ISO 13849
Category | 4 (In conjunction with suitable evaluating device) |
Performance level (PL) | e (In conjunction with suitable evaluating device) |
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
Safety data: EN IEC 62061
Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
Ambient conditions
Degree of Protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Ambient Temperature (Operation) | -20 °C ... 55 °C (observe derating) |
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Maximum altitude | max. 2000 m (Above sea level) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Shock | 15g |
Vibration (Operation) | 10 Hz ... 150 Hz, 2g |
CE
Identification | CE-compliant |
Air clearances and creepage distances between the power circuits
Standards/regulations | IEC 60664-1 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | See derating curve |
Mounting Position | vertical or horizontal |
Why Proax for Phoenix Contact 2981033?
Proax is an authorized distributor of Phoenix Contact 2981033 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended