Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
PSR-SCP- 24UC/URM4/5X1/2X2
Weight
0.31 kg
Series PSR-SCP

PSR-SCP- 24UC/URM4/5X1/2X2 - Extension module

1-channel or 2-channel contact extension, 5 N/O contacts, 1 N/C contact, 1 confirmation current path, together with basic device up to Cat. 4 PL e in accordance with EN ISO 13849 safe isolation, width: 35 mm, pluggable screw terminal block

  • Five enabling, one signaling, and one confirmation current path
  • 1- and 2-channel control
  • Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
Technical Specifications

Product properties

Product familyPSRclassic
ApplicationExtension module
Mechanical service lifeapprox. 107 cycles
Relay typeSafety relay for contact extension

Times

Typ. starting time with Us< 20 ms (at Us / when controlled via A11/A12)
Typical release time< 20 ms (at Us / when controlled via A11/A12)
Recovery time< 1 s

Electrical properties

Maximum power dissipation for nominal condition15.8 W (US = 26.4 V, IL² = 72 A², PTotal max = 1.4 W + 14.4 W)
Nominal operating mode100% operating factor

Air clearances and creepage distances between the power circuits

Rated Insulation Voltage250 V
Rated surge voltage/insulationSee section “Insulation coordination”

General

Rated control circuit supply voltage US24 V -20 % ... +10 %
Power consumption at US1 W (with DC)
Power consumption at US1.2 W (with AC)
Rated control supply current IStyp. 39 mA (per channel, DC)
Rated control supply current IStyp. 50 mA (per channel, AC)
Inrush Currenttyp. 200 mA (Δt = 2 ms at Us, per channel)
Protective circuitSurge protection; Varistor (40 V breakdown voltage)

Output data

Contact switching type5 enabling current paths
Contact switching type1 confirmation current path
Contact switching type1 signaling current path
Contact MaterialAgSnO2
Maximum Switching Voltage250 V AC/DC
Minimum Switching Voltage5 V AC/DC
Limiting Continuous Current6 A (N/O contact)
Limiting Continuous Current3 A (N/C contact 11/12)
Limiting Continuous Current6 A (N/C contact 71/72)
Maximum Inrush Current6 A
Inrush current, minimum10 mA
Sq. Total current72 A2 (ITH2 = I12 + I22 + ... + I52)
Switching capacity min.50 mW
Switching capacity in accordance with IEC 60947-5-13 A (AC15)
Switching capacity in accordance with IEC 60947-5-15 A (DC13)
Output fuse10 A gL/gG (N/O contact)
Output fuse6 A gL/gG (N/C contact)

Relay

Interrupting rating (ohmic load) max.see load limit curve

Connection technology

pluggableyes

Conductor connection

Connection MethodScrew connection
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross-section AWG24 ... 12
Stripping length7 mm
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm

Signaling

Operating voltage display2 x green LED

Dimensions

Width35 mm
Height99 mm
Depth114.5 mm

Material specifications

Color (Housing)yellow (RAL 1018)
Housing MaterialPolyamide

Safety data

Stop category0

Safety data: EN ISO 13849

Category4 (In conjunction with suitable evaluating device)
Performance level (PL)e (In conjunction with suitable evaluating device)

Safety data: IEC 61508 - High demand

Safety Integrity Level (SIL)3 (In conjunction with suitable evaluating device)

Safety data: IEC 61508 - Low demand

Safety Integrity Level (SIL)3 (In conjunction with suitable evaluating device)

Safety data: EN IEC 62061

Safety Integrity Level (SIL)3 (In conjunction with suitable evaluating device)

Ambient conditions

Degree of ProtectionIP20
Min. degree of protection of inst. locationIP54
Ambient Temperature (Operation)-20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 70 °C
Maximum altitude≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Shock15g
Vibration (Operation)10 Hz ... 150 Hz, 2g

Air clearances and creepage distances between the power circuits

Standards/regulationsEN 60947-5-1

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsObserve derating
Mounting Positionvertical or horizontal

Why Proax for Phoenix Contact 2963734?

Proax is an authorized distributor of Phoenix Contact 2963734 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability