SKU
MPN
MACX MCR-EX-SL-SD-21-60-LP-SP
Weight
0.173 kg
This product is Not Cancellable/Not Returnable
Series MACX-MCR-EX-SL-SD
MACX MCR-EX-SL-SD-21-60-LP-SP - Solenoid driver
Ex i solenoid driver. For the intrinsically safe control of Ex i solenoid valves, alarm modules or LEDs installed in the Ex area. Current limitation at 58 mA. For gases up to Group IIB, loop-powered, electrical isolation, SIL 3. Push-in connection.
- Mechanically compatible with the DIN rail connector
- Various output characteristic curves compatible with standard solenoid valves
- Loop-powered: the required power is supplied via the control signal on the input side.
- Installation in zone 2, protection type "n" (EN 60079-15) permitted
- Up to SIL 3 in accordance with IEC 61508
- 2-way electrical isolation
- Input: 19.2 V DC … 30 V DC
- Output [Ex ia] IIB
Technical Specifications
Product properties
Product family | MACX Analog |
No. of channels | 1 |
Type | Ex i signal conditioners with SIL functional safety |
Compatible Valve | ASCO Coil 302 (12 V) |
Compatible Valve | ASCO Coil 302 (24 V) |
Compatible Valve | Bürkert Coil AC 10 standard |
Compatible Valve | Bürkert Coil AC 10 high resistance |
Compatible Valve | FESTO Coil MFH-...IA-SA-EX GBXE022AIAD03 |
Compatible Valve | FESTO Coil (J)MFH-...BIA-SA-EX GBXE022AIAD03 |
Compatible Valve | Norgren Herion Coil 2050 |
Compatible Valve | Norgren Herion Coil 2051 |
Compatible Valve | Norgren Herion Coil 2052 |
Compatible Valve | Norgren Herion Coil 2053 |
Compatible Valve | Parker Coil VZ95 482160.01 EEx ia IIB T6 |
Note | This is an extract of possible combinations of valves and solenoid drivers. |
Electrical properties
Electrical isolation | 2-way isolation |
Maximum temperature coefficient | 0.01 %/K |
Electrical isolation
Test voltage | 2.5 kV AC (50 Hz, 60 s) |
Overvoltage category | II |
Pollution degree | 2 |
Electrical isolation Output/input IEC/EN 60079-11
Standards/regulations | IEC/EN 60079-11 |
Rated Insulation Voltage | 375 VPP |
Electrical isolation Output/input IEC/EN 61010-1
Standards/regulations | IEC/EN 61010-1 |
Rated Insulation Voltage | 300 Vrms |
Insulation | Safe isolation |
Supply
Supply Voltage Range | loop-powered, no external supply necessary |
Power dissipation | < 1.325 W |
Signal: Voltage
Number of Inputs | 1 |
Voltage input signal | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
Max. current input signal | 95 mA (Ue = 24 V DC) |
Output description | intrinsically safe |
Number of Outputs | 1 |
Output Voltage | 12.9 V DC (58 mA) |
Output resistor | 133.4 Ω (Internal resistance Ri) |
Current limitation | 58 mA |
Response time | 20 ms |
Non-load voltage | 21.9 V DC |
Short-circuit-proof | yes |
Connection data
Connection Method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Ex data
Ex installation (EPL) | Gc |
Ex installation (EPL) | Div. 2 |
Ex i circuits (EPL) | Ga |
Ex i circuits (EPL) | Da |
Ex i circuits (EPL) | Ma |
Ex i circuits (EPL) | Div. 1 |
Safety data
Max. internal inductance Li | negligible |
Max. internal capacitance Ci | negligible |
Max. output voltage Uo | 25.1 V |
Max. output current Io | 188 mA |
Max. output power Po | 1.18 W |
Safety-related maximum voltage Um | 253 V AC |
Safety-related maximum voltage Um | 125 V DC |
IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 4 mH / 0.83 µF |
IIB/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 2 mH / 300 nF, 1 mH / 370 nF, 0.5 mH / 460 nF, 0.1 mH / 790 nF |
Signaling
Status display | Yellow LED (switching state / status, lights up when output circuit is active) |
Dimensions
Width | 12.5 mm |
Height | 116 mm |
Depth | 113.7 mm |
Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Housing Material | PA 6.6-FR |
Ambient conditions
Degree of Protection | IP20 (not assessed by UL) |
Ambient Temperature (Operation) | -40 °C ... 60 °C (Any mounting position) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
CE
Certificate | CE-compliant |
Note | and EN 61326 |
ATEX
Identification | II (1) G [Ex ia Ga] IIB/IIA |
Identification | II (1) D [Ex ia Da] IIIC |
Identification | II 3 (1)G Ex nA [ia IIB Ga] IIC T4 Gc X |
Certificate | IBExU 07 ATEX 1133X |
UKCA Ex (UKEX)
Identification | I (M1) [Ex ia Ma] I |
Identification | II (1) G [Ex ia Ga] IIB |
Identification | II (1) D [Ex ia Da] IIIC |
Identification | II 3 (1) Ex ec [ia IIB Ga] IIC T4 Gc |
Certificate | CML 22UKEX3526X |
IECEx
Identification | [Ex ia Ga] IIB/IIA |
Identification | [Ex ia Da] IIIC |
Identification | Ex nA [ia IIB Ga] IIC T4 Gc |
Certificate | IECEx IBE 08.0002X |
CCC / China-Ex
Identification | [Ex ia Ga] IIC |
Identification | [Ex iaD] |
Identification | Ex nA [ia Ga] IIC T4 Gc |
Certificate | NEPSI GYJ20.1316X |
UL, USA/Canada
Identification | UL 61010 Listed |
Identification | Class I, Div. 2, Groups A, B, C, D T4 |
Identification | Class I, Div. 2, Groups IIC, IIB, IIA T4 |
Identification | Associated apparatus for use in Class I, Division 1, Groups C,D |
Identification | Associated apparatus for use in Class II, Div.1 Groups E,F,G |
Identification | Associated apparatus for use in Class III, Division 1 |
Identification | Associated apparatus for use in Class I, Zone 0,1,2, Groups IIB, IIA |
Certificate | , C.D.-No 83104549 |
Identification | Class I Div 2; IS for Class I, II, III Div 1 |
Certificate | , C.D.-No 83104549 |
Shipbuilding approval
Certificate | DNV GL TAA000020C |
Safety Integrity Level (SIL, IEC 61508)
Identification | 3 |
INMETRO
Identification | [Ex ia Ga] IIC/IIB/IIA |
Identification | [Ex ia Da] IIIC |
Identification | Ex nA [ia IIC Ga] IIC T4 Gc |
Certificate | DNV 18.0115 X |
DNV GL data
Temperature | B |
Humidity | B |
Vibration | A |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Standards and Regulations
Electrical isolation | 2-way isolation |
GB Standard
Standards/regulations | GB 3836.1 |
Standards/regulations | GB 3836.4 |
Standards/regulations | GB 3836.8 |
Standards/regulations | GB 3626.20 |
Standards/regulations | GB 12476.1 |
Standards/regulations | GB 12476.4 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2924100?
Proax is an authorized distributor of Phoenix Contact 2924100 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended