Official Distributor
SKU
MPN
MINI MCR-SL-TC-UI-NC
Weight
0.089 kg
MINI MCR-SL-TC-UI-NC - Thermocouple measuring transducer
MCR temperature transducer for thermocouples, can be configured via DIP switches, with screw connection, standard configuration
- Power supply possible via the foot element (TBUS)
- For J and K thermocouples according to IEC 60584
- Error indication via diagnostic LED and analog signal
- Temperature measuring range of -150°C to +1350°C
- Highly-compact temperature transducer for electrical isolation, conversion, amplification, and filtering of thermocouple signals to create standard signals
- Internal cold junction compensation
- Input and output signals can be configured via DIP switches
- 3-way isolation
Technical Specifications
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
Product family | MINI Analog |
No. of channels | 1 |
Insulation characteristics
Overvoltage category | II |
Pollution degree | 2 |
Electrical properties
Rated Insulation Voltage | 50 V AC/DC |
Electrical isolation | Basic insulation in accordance with EN 61010 |
Typical cold point errors | < 2 K |
Cold point error, max. | < 3 K |
Maximum power dissipation for nominal condition | 235.5 mW |
Test voltage, input/output/supply | 1.5 kV AC (50 Hz, 60 s) |
Protective circuit | Transient protection |
Step response (0–99%) | < 30 ms |
Maximum temperature coefficient | < 0.02 %/K |
Transmission error in the set measuring range | ((150 K / set measurement range [K]) + 0.1)% |
Transmission error in the full measuring range | ≤ 0,2 % |
Supply
Nominal Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
Max. current consumption | < 25 mA (at 24 V DC) |
Power consumption | < 500 mW |
Signal
Number of Inputs | 1 |
Input Signal | Temperature |
Measurement
Sensor types that can be used (TC) | Thermocouples type J, K (IEC 584-1) |
Temperature measuring range | min. 50 K |
Sensor type: | -150 °C ... 1200 °C (configurable) |
Sensor type: | -150 °C ... 1350 °C |
Signal
Number of Outputs | 1 |
Voltage output signal | 0 V ... 10 V |
Voltage output signal | 10 V ... 0 V |
Voltage output signal | 0 V ... 5 V |
Voltage output signal | 1 V ... 5 V |
Max. voltage output signal | 12.5 V |
Non-load voltage | approx. 12.5 V |
Current Output Signal | 0 mA ... 20 mA |
Current Output Signal | 4 mA ... 20 mA |
Current Output Signal | 20 mA ... 0 mA |
Current Output Signal | 20 mA ... 4 mA |
Max. current output signal | 23 mA |
Short-circuit current | approx. 10 mA |
Load/output load voltage output | ≥ 10 kΩ |
Load/Output Load Current Output | < 500 Ω (at 20 mA) |
Ripple | < 20 mVPP (at 500 Ω) |
Ripple | < 20 mVPP (at 10 kΩ) |
Connection data
Connection Method | Screw connection |
Stripping length | 12 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 12 |
Dimensions
Width | 6.2 mm |
Height | 93.1 mm |
Depth | 102.5 mm |
Material specifications
Color | green (RAL 6021) |
Housing Material | PBT |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -20 °C ... 65 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
CE
Certificate | CE-compliant |
ATEX
Identification | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada
Identification | UL 508 Recognized |
Identification | Class I, Div. 2, Groups A, B, C, D T5 |
GL
Identification | GL EMC 2 D |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Comments | Safety measures must be taken to prevent electrostatic discharge. |
Electromagnetic HF field
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 10 % |
Fast transients (burst)
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 10 % |
Surge current load (surge)
Standards/regulations | EN 61000-4-5 |
Comments | Criterion B |
Conducted interference
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 10 % |
Standards and Regulations
Electrical isolation | Basic insulation in accordance with EN 61010 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail. |
Mounting Position | any |
Why Proax for Phoenix Contact 2864299?
Proax is an authorized distributor of Phoenix Contact 2864299 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended