Official Distributor
SKU
MPN
MINI MCR-SL-UI-F
Weight
0.108 kg
MINI MCR-SL-UI-F - Frequency measuring transducer
Analog frequency transducers for converting analog standard signals into frequency signals or PWM signals, configurable via DIP switch, with screw connection
- Power supply possible via the foot element (TBUS)
- Error indication via diagnostic LED and analog signal
- PWM output of 5 ... 95 %
- Highly-compact analog-to-frequency transducer for electrical isolation, amplification, conversion, and filtering of standard signals to create frequencies or PWM signals
- Input and output signals can be configured via DIP switches
- Configurable interference filter
- 3-way isolation
Technical Specifications
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
Product family | MINI Analog |
No. of channels | 1 |
Configuration | DIP switches |
Insulation characteristics
Overvoltage category | II |
Pollution degree | 2 |
Functionality
Configuration | DIP switches |
Electrical properties
Electrical isolation between input and output | yes |
Step response (0–99%) | < 15 ms (+ (1/f) smallest filter) |
Step response (0–99%) | < 1 s (+ (1/f) largest filter) |
Maximum temperature coefficient | < 0.02 %/K |
Temperature coefficient, typical | < 0.02 %/K |
Maximum transmission error | ≤ 0.1 % (> 7 kHz ≤ 0.2 %) |
Electrical isolation Input/output/power supply
Rated Insulation Voltage | 30 V AC |
Rated Insulation Voltage | 50 V DC |
Test voltage | 1.5 kV AC (50 Hz, 60 s) |
Insulation | Basic insulation in accordance with IEC/EN 61010 |
Supply
Nominal Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715) |
Max. current consumption | < 10 mA (at 24 V DC) |
Power consumption | < 200 mW |
Signal: Voltage/current
Number of Inputs | 1 |
Configurable/programmable | Yes |
Voltage input signal | 0 V ... 5 V |
Voltage input signal | 1 V ... 5 V |
Voltage input signal | 0 V ... 10 V |
Voltage input signal | 2 V ... 10 V |
Max. voltage input signal | 30 V DC |
Current Input Signal | 0 mA ... 20 mA |
Current Input Signal | 4 mA ... 20 mA |
Current Input Signal | 0 mA ... 10 mA |
Current Input Signal | 2 mA ... 10 mA |
Max. current input signal | 100 mA |
Input resistance of voltage input | approx. 110 kΩ |
Input resistance current input | approx. 50 Ω |
Behavior in the event of an error | Alarm in the form of a red LED |
Frequency: Frequency
Frequency output | 0 Hz ... 10 kHz |
Frequency output | 0 Hz ... 5 kHz |
Frequency output | 0 Hz ... 2.5 kHz |
Frequency output | 0 Hz ... 1 kHz |
Frequency output | 0 Hz ... 500 Hz |
Frequency output | 0 Hz ... 250 Hz |
Frequency output | 0 Hz ... 100 Hz |
Frequency output | 0 Hz ... 50 Hz |
Load min. | 4 mA ≤ (UL / RL) ≤ 20 mA |
Output signal PWM | 7.8 kHz (10 bit) |
Output signal PWM | 3.9 kHz (10 bit) |
Output signal PWM | 1.9 kHz (12 bit) |
Output signal PWM | 977 Hz (12 bit) |
Output signal PWM | 488 Hz (14 bit) |
Output signal PWM | 244 Hz (14 bit) |
Output signal PWM | 122 Hz (16 bit) |
Output signal PWM | 61 Hz (16 bit) |
Load min. | 12 mA ≤ (UL/RL) ≤ 20 mA |
Load current maximum | 20 mA |
Maximum Switching Voltage | 30 V |
Overrange/underrange | can be set (via DIP switch) |
Protective circuit | Short-circuit protection, polarity reversal protection |
Signal
Number of Outputs | 1 |
Connection data
Connection Method | Screw connection |
Stripping length | 12 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 12 |
Dimensions
Width | 6.2 mm |
Height | 93.1 mm |
Depth | 101.2 mm |
Material specifications
Color | green (RAL 6021) |
Housing Material | PBT |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -20 °C ... 65 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
CE
Certificate | CE-compliant |
UKCA
Certificate | UKCA-compliant |
UL, USA/Canada
Identification | UL 508 Recognized |
Identification | Class I, Div. 2, Groups A, B, C, D T4 |
Shipbuilding approval
Certificate | DNV GL TAA000020N |
DNV GL data
Temperature | B |
Humidity | B |
Vibration | B |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Noise immunity | EN 61000-6-2 |
Note | When being exposed to interference, there may be minimal deviations. |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Comments | Safety measures must be taken to prevent electrostatic discharge. |
Electromagnetic HF field
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 2 % |
Fast transients (burst)
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 2 % |
Surge current load (surge)
Standards/regulations | EN 61000-4-5 |
Comments | Criterion B |
Conducted interference
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 2 % |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any |
Accessories
Why Proax for Phoenix Contact 2864082?
Proax is an authorized distributor of Phoenix Contact 2864082 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- MINI MCR-SL-UI-I-LP-SP-NC, The 6.2 mm wide MINI MCR-SL-UI-I-LP... configurable 2-way isolating amplifier is used to electrically isolate, condition, and filter analog signals.The output loops that supply the loop-powered isolating amplifier enable the isolating amplifier to operate on an active analog input module. The modules are supplied via the current loop of the controller.On the input side, standard analog signals and non-standard analog signals can be connected, starting from 2 mA or 50 mV up to 40 mA or 30 V. These are converted to a 4...20 mA signal.The DIP switches accessible on the housing side enable the configuration of input signal ranges.
- MINI MCR-SL-UI-2I, The 6.2 mm wide configurable 4-way isolating amplifier MINI MCR-SL-UI-2I-... is used for electrical isolation, conversion, amplification and filtering of standard signals.On the input side, the analog standard signals 0...20 mA, 4...20 mA, 0...10 V or 1...5V can be selected, on the output side there are two current outputs that can be set independently of one another with a 0...20 mA-, or 4...20mA signal, electrically isolated (4-way isolation).The DIP switches, which can be accessed on the side of the housing, can be used to configure the input and output signal ranges.Power (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in conjunction with the DIN rail connector.
- MINI MCR-SL-UI-2I-SP-NC, The 6.2 mm wide configurable 4-way isolating amplifier MINI MCR-SL-UI-2I-... is used for electrical isolation, conversion, amplification and filtering of standard signals.On the input side, the analog standard signals 0...20 mA, 4...20 mA, 0...10 V or 1...5V can be selected, on the output side there are two current outputs that can be set independently of one another with a 0...20 mA-, or 4...20mA signal, electrically isolated (4-way isolation).The DIP switches, which can be accessed on the side of the housing, can be used to configure the input and output signal ranges.Power (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in conjunction with the DIN rail connector.