Series PSI-MOS-RS
PSI-MOS-RS485W2/FO1300 E - FO converters
FO converter with integrated optical diagnostics, alarm contact, for RS-485 2-wire bus systems (SUCONET K, MODBUS ...) up to 500 kbps, NRZ coding, termination device with an FO interface (SC-Duplex), 1300 nm, for fiberglass cable
- Connections can be plugged in via a COMBICON screw terminal block
- Supply voltage and data signals routed through the DIN rail connectors
- Can be combined with the PSI copper repeater in a modular way using DIN rail connectors
- Automatic data rate detection or fixed data rate setting via DIP switches
- Redundant power supply possible by means of optional system power supply unit
- High-quality electrical isolation between all interfaces (RS-485 // fiber optic ports // power supply // DIN rail connector)
- Approved for use in zone 2
- Floating switch contact for advance warning of critical FO paths
- Integrated optical diagnostics for continuous monitoring of FO paths
- Suitable for data rates up to 500 kbps
Technical Specifications
Utilization restriction
CCCex note | Use in potentially explosive areas is not permitted in China. |
Product properties
MTTF | 903 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
MTTF | 412 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) |
MTTF | 169 Years (SN 29500 standard, temperature 40°C, operating cycle 100%) |
MTBF | 484 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
MTBF | 102 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) |
Electrical properties
Electrical isolation | VCC // RS-485 |
Maximum power dissipation for nominal condition | 1.375 W |
Test voltage data interface/power supply | 1.5 kVrms (50 Hz, 1 min.) |
Supply
Supply Voltage Range | 18 V DC ... 32 V DC |
Nominal Supply Voltage | 24 V DC (in acc. with UL) |
Typical current consumption | 55 mA (24 V DC) |
Max. current consumption | 90 mA |
Max. current consumption | ≤ 2 A (For operation in a joining station, via the DIN rail connector) |
Switching
Output name | Relay output |
Output description | Alarm output |
Number of Outputs | 1 |
Maximum Switching Voltage | 60 V DC (Resistive Load, General Load) |
Maximum Switching Voltage | 30 V AC (Resistive load) |
Maximum Switching Voltage | 42 V AC (peak, resistive load) |
Limiting Continuous Current | 0.46 A |
Supply
Connection Method | COMBICON plug-in screw terminal block |
Stripping length | 7.00 mm |
Tightening torque | 0.56 Nm ... 0.79 Nm |
Interfaces
Bit distortion, input | ± 35 % (permitted) |
Bit distortion, output | < 6.25 % |
Signal | Modbus |
Signal | S-BUS |
Signal | Suconet K |
Signal | J-BUS |
Signal | DATA HIGHWAY |
Data: optical FO
No. of channels | 1 |
Transmit capacity, minimum | -3.4 dBm (50/125 μm, multimode fiberglass) |
Transmit capacity, minimum | -4.7 dBm (62.5/125 μm, multimode fiberglass) |
Transmit capacity, minimum | -5.5 dBm (9/125 μm, singlemode fiberglass) |
Transmission length incl. 3 dB system reserve | 25 km (With F-G 50/125 0.7 dB/km at 1300 nm) |
Transmission length incl. 3 dB system reserve | 22 km (with F-G 62.5/125 0.8 dB/km at 1300 nm) |
Transmission length incl. 3 dB system reserve | 45 km (With F-E 9/125 0,4 dB/km at 1300 nm) |
Transmission protocol | Protocol-transparent to the RS-485 interface |
Connection Method | SC duplex |
Wavelength | 1300 nm |
Minimum receiver sensitivity | -25.5 dBm (50/125 µm) |
Minimum receiver sensitivity | -25.5 dBm (62,5/125 µm) |
Minimum receiver sensitivity | -26.5 dBm (9/125 µm) |
Maximum receiver sensitivity | 0 dBm (9/125 µm) |
Transmission medium | Multi-mode fiberglass |
Transmission medium | Single-mode fiberglass |
Data: RS-485 interface, 2-wire
Serial transmission speed | 4.8/ 9.6/ 19.2/ 38.4/ 57.6/ 75/ 93.75/ 115.2/ 136/ 187.5/ 375/ 500 kbps |
Connection Method | Pluggable screw connection |
Transmission length | ≤ 1200 m (depending on the data rate, with shielded, twisted data cable) |
Termination resistor | 390 Ω (Can be connected) |
Termination resistor | 220 Ω |
Termination resistor | 390 Ω |
Single conductor/terminal point, rigid | 0.2 mm² ... 2.5 mm² |
Single-wire/terminal point, flexible | 0.2 mm² ... 2.5 mm² |
Max. AWG conductor cross section, flexible | 14 |
Min. AWG conductor cross section, flexible | 24 |
Single-wire/terminal point, rigid AWG max. | 14 |
Single-wire/terminal point, rigid AWG min. | 24 |
Transmission medium | Copper |
File format/coding | UART (11/10 bit switchable; NRZ), slip-tolerant |
Data direction switching | Automatic control |
Dimensions
Width | 35 mm |
Height | 99 mm |
Depth | 105 mm |
Material specifications
Color (Housing) | gray (RAL 7042) |
Material (Housing) | PA 6.6-FR |
FO cable
Fiber types | 50/125 µm |
Fiber types | 9/125 µm |
Fiber types | Fiberglass |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -20 °C ... 60 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation) |
Altitude | ≤ 2000 m (Hazardous locations) |
Permissible humidity (operation) | 30 % ... 95 % (non-condensing) |
CE
Certificate | CE-compliant |
ATEX
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | UL 21 ATEX 2550X |
Note | Please follow the special installation instructions in the documentation! |
IECEx
Identification | Ex ec IIC T4 Gc |
Certificate | IECEx ULD 21.00013X |
UL, USA/Canada
Identification | Class I, Zone 2, AEx ec IIC T4 Gc |
Identification | Ex ec IIC T4 Gc X |
Identification | Class I, Div. 2, Groups A, B, C, D |
Corrosive gas test
Identification | ISA-S71.04-1985 G3 Harsh Group A |
EMC data
Noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 55011 |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | ± 6 kV |
Discharge in air | ± 8 kV |
Comments | Criterion B |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Field intensity | 10 V/m |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | ± 2 kV |
Signal | ± 2 kV |
Comments | Criterion B |
Surge current load (surge)
Standards/regulations | EN 61000-4-5 |
Input | ± 0.5 kV |
Signal | ± 1 kV |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
Comments | Criterion A |
Voltage | 10 V |
Emitted interference
Standards/regulations | EN 55011 |
Comments | Class A, industrial applications |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Standards and Regulations
Free from substances that could impair the application of coating | in accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0 |
Mounting
Mounting Type | DIN rail mounting |
Accessories
- 2713645 - DIN rail connector, color: light grey, nominal current: 8 A (parallel contacts), rated voltage (III/2): 125 V, number of positions: 5, product range: TBUS5-17,5.., pitch: 3.81 mm, mounting: DIN rail mounting, locking: without, mounting: without, type of packaging: packed in cardboard, Item with gold-plated contacts, bus connectors for connecting with electronics housings, 5 parallel contacts
Why Proax for Phoenix Contact PSI-MOS-RS485W2/FO1300 E?
Proax is an authorized distributor of Phoenix Contact PSI-MOS-RS485W2/FO1300 E and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | PSIMOSRS485W2FO1300E |
Pack Size | 1 |
Recommended