2708892
SKU
PHX2708892
MPN
PSI-MOS-PROFIB/FO1300 T
Weight
0.252 kg
This product is Not Cancellable/Not Returnable
Series PSI-MOS-PROFIB-FO
PSI-MOS-PROFIB/FO1300 T - FO converters
Fiber optic converter with integrated optical diagnostics, alarm contact, for PROFIBUS up to 12 Mbps, T-coupler with two fiber optic interfaces (SC-Duplex), 1300 nm, for fiberglass cable
- Supply voltage and data signals routed through the DIN rail connectors
- Can be combined with the PSI copper repeater in a modular way using DIN rail connectors
- Connections can be plugged in via a COMBICON screw terminal block
- Automatic data rate detection or fixed data rate setting via DIP switches
- Redundant power supply possible by means of optional system power supply unit
- High-quality electrical isolation between all interfaces (PROFIBUS // fiber optic ports // power supply // DIN rail connector)
- Approved for use in zone 2
- Integrated optical diagnostics for continuous monitoring of FO paths
- Floating switch contact for advance warning of critical FO paths
- Bit retiming for any cascading depth
- Suitable for all data rates up to 12 Mbps
Technical Specifications
Utilization restriction
| CCCex note | Use in potentially explosive areas is not permitted in China. | 
Product properties
| MTTF | 614 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) | 
| MTTF | 272 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) | 
| MTTF | 113 Years (SN 29500 standard, temperature 40°C, operating cycle 100%) | 
| MTBF | 307 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) | 
| MTBF | 64 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) | 
Electrical properties
| Electrical isolation | VCC // RS-485 | 
| Maximum power dissipation for nominal condition | 2.04 W | 
| Test voltage data interface/power supply | 1.5 kVrms (50 Hz, 1 min.) | 
Supply
| Supply Voltage Range | 18 V DC ... 32 V DC (via pluggable COMBICON screw terminal block) | 
| Nominal Supply Voltage | 24 V DC (in acc. with UL) | 
| Typical current consumption | 85 mA (24 V DC) | 
| Max. current consumption | 145 mA | 
| Max. current consumption | ≤ 2 A (For operation in a joining station, via the DIN rail connector) | 
Switching
| Output name | Relay output | 
| Output description | Alarm output | 
| Number of Outputs | 1 | 
| Maximum Switching Voltage | 60 V DC (Resistive Load, General Load) | 
| Maximum Switching Voltage | 30 V AC (Resistive load) | 
| Maximum Switching Voltage | 42 V AC (peak, resistive load) | 
| Limiting Continuous Current | 0.46 A | 
Supply
| Connection Method | COMBICON plug-in screw terminal block | 
| Stripping length | 7.00 mm | 
| Tightening torque | 0.56 Nm ... 0.79 Nm | 
Interfaces
| Bit distortion, input | ± 35 % (permitted) | 
| Bit distortion, output | < 6.25 % | 
| Bit delay | < 1 bit (DIP 7 = OFF, standard operation) | 
| Bit delay | 11 bit (DIP 7 = ON, redundancy operation) | 
| Signal | PROFIBUS | 
Data: optical FO
| No. of channels | 2 | 
| Transmit capacity, minimum | -3.4 dBm (50/125 μm, multimode fiberglass) | 
| Transmit capacity, minimum | -4.7 dBm (62.5/125 μm, multimode fiberglass) | 
| Transmit capacity, minimum | -5.5 dBm (9/125 μm, singlemode fiberglass) | 
| Transmission length incl. 3 dB system reserve | 25 km (With F-G 50/125 0.7 dB/km at 1300 nm) | 
| Transmission length incl. 3 dB system reserve | 22 km (with F-G 62.5/125 0.8 dB/km at 1300 nm) | 
| Transmission length incl. 3 dB system reserve | 45 km (With F-E 9/125 0,4 dB/km at 1300 nm) | 
| Transmission protocol | Protocol-transparent to the RS-485 interface | 
| Connection Method | SC duplex | 
| Wavelength | 1300 nm | 
| Minimum receiver sensitivity | -25.5 dBm (Multi mode) | 
| Minimum receiver sensitivity | -26.5 dBm (Singlemode) | 
| Maximum receiver sensitivity | 0 dBm | 
| Transmission medium | Multi-mode fiberglass | 
| Transmission medium | Single-mode fiberglass | 
Data: PROFIBUS acc. to IEC 61158, RS-485 2-wire, half duplex, automatic control
| Serial transmission speed | ≤ 12 Mbps | 
| Connection Method | D-SUB-9 female connector | 
| Transmission length | ≤ 1200 m (depending on the data rate, with shielded, twisted pair data cable) | 
| Single conductor/terminal point, rigid | 0.2 mm² ... 2.5 mm² | 
| Single-wire/terminal point, flexible | 0.2 mm² ... 2.5 mm² | 
| Max. AWG conductor cross section, flexible | 14 | 
| Min. AWG conductor cross section, flexible | 24 | 
| Single-wire/terminal point, rigid AWG max. | 14 | 
| Single-wire/terminal point, rigid AWG min. | 24 | 
| Transmission medium | 2-wire twisted pair, shielded | 
| File format/coding | UART (11 Bit, NRZ) | 
| Data direction switching | Automatic control | 
| Output nominal voltage | 5 V DC ±0.25 (50 mA) | 
Dimensions
| Width | 35 mm | 
| Height | 105 mm | 
| Depth | 106 mm | 
Material specifications
| Color (Housing) | gray (RAL 7042) | 
| Material (Housing) | PA 6.6-FR | 
FO cable
| Fiber types | 50/125 µm | 
| Fiber types | 62.5/125 µm | 
| Fiber types | 9/125 µm | 
| Fiber types | Fiberglass | 
Ambient conditions
| Degree of Protection | IP20 | 
| Ambient Temperature (Operation) | -20 °C ... 60 °C | 
| Ambient temperature (storage/transport) | -40 °C ... 85 °C | 
| Altitude | ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation) | 
| Altitude | ≤ 2000 m (Hazardous locations) | 
| Permissible humidity (operation) | 30 % ... 95 % (non-condensing) | 
CE
| Certificate | CE-compliant | 
ATEX
| Identification |  II 3 G Ex ec IIC T4 Gc | 
| Certificate | UL 21 ATEX 2550X | 
| Note | Please follow the special installation instructions in the documentation! | 
IECEx
| Identification | Ex ec IIC T4 Gc | 
| Certificate | IECEx ULD 21.00013X | 
UL, USA/Canada
| Identification | Class I, Zone 2, AEx ec IIC T4 Gc | 
| Identification | Ex ec IIC T4 Gc X | 
| Identification | Class I, Div. 2, Groups A, B, C, D | 
KC approval for South Korea
| Certificate | MSIP-REI-PCK-2708892 | 
Corrosive gas test
| Identification | ISA-S71.04-1985 G3 Harsh Group A | 
EMC data
| Noise immunity | EN 61000-6-2:2005 | 
| Electromagnetic compatibility | Conformance with EMC directive 89/336/EC | 
| Noise emission | EN 55011 | 
Electrostatic discharge
| Standards/regulations | EN 61000-4-2 | 
| Contact discharge | ± 6 kV | 
| Discharge in air | ± 8 kV | 
| Comments | Criterion B | 
Electromagnetic HF field
| Standards/regulations | EN 61000-4-3 | 
| Field intensity | 10 V/m | 
| Comments | Criterion A | 
Fast transients (burst)
| Standards/regulations | EN 61000-4-4 | 
| Input | ± 2 kV | 
| Signal | ± 2 kV | 
| Comments | Criterion B | 
Surge current load (surge)
| Standards/regulations | EN 61000-4-5 | 
| Input | ± 0.5 kV | 
| Signal | ± 1 kV | 
| Comments | Criterion B | 
Conducted interference
| Standards/regulations | EN 61000-4-6 | 
| Comments | Criterion A | 
| Voltage | 10 V | 
Emitted interference
| Standards/regulations | EN 55011 | 
| Comments | Class A, industrial applications | 
Criteria
| Criterion A | Normal operating behavior within the specified limits. | 
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. | 
Standards and Regulations
| Free from substances that could impair the application of coating | in accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0 | 
Mounting
| Mounting Type | DIN rail mounting | 
Accessories
 ME 17,5 TBUS 1,5/ 5-ST-3,81 KMGY - DIN rail connector, color: light grey, nominal current: 8 A (parallel contacts), rated voltage (III/2): 125 V, number of positions: 5, product range: TBUS5-17,5.., pitch: 3.81 mm, mounting: DIN rail mounting, locking: without, mounting: without, type of packaging: packed in cardboard, Item with gold-plated contacts, bus connectors for connecting with electronics housings, 5 parallel contacts ME 17,5 TBUS 1,5/ 5-ST-3,81 KMGY - DIN rail connector, color: light grey, nominal current: 8 A (parallel contacts), rated voltage (III/2): 125 V, number of positions: 5, product range: TBUS5-17,5.., pitch: 3.81 mm, mounting: DIN rail mounting, locking: without, mounting: without, type of packaging: packed in cardboard, Item with gold-plated contacts, bus connectors for connecting with electronics housings, 5 parallel contacts
 SUBCON-PLUS-PROFIB/90/PG/SC - D-SUB connector, 9-pos., male connector, 90° cable entry, bus system: PROFIBUS DP up to 12 Mbps with PG D-SUB socket for connecting a programming device, termination resistor can be switched on via slide switch, pin assignment: 3, 5, 6, 8; screw connection terminal blocks SUBCON-PLUS-PROFIB/90/PG/SC - D-SUB connector, 9-pos., male connector, 90° cable entry, bus system: PROFIBUS DP up to 12 Mbps with PG D-SUB socket for connecting a programming device, termination resistor can be switched on via slide switch, pin assignment: 3, 5, 6, 8; screw connection terminal blocks
 SUBCON-PLUS-PROFIB/90/PG/IDC - D-SUB connector, 9-pos., male connector, 90° cable entry, bus system: PROFIBUS DP up to 12 Mbps with PG D-SUB socket for connecting a programming device, termination resistor can be switched on via slide switch, pin assignment: 3, 5, 6, 8; IDC terminal block connection SUBCON-PLUS-PROFIB/90/PG/IDC - D-SUB connector, 9-pos., male connector, 90° cable entry, bus system: PROFIBUS DP up to 12 Mbps with PG D-SUB socket for connecting a programming device, termination resistor can be switched on via slide switch, pin assignment: 3, 5, 6, 8; IDC terminal block connection
Why Proax for Phoenix Contact 2708892?
Proax is an authorized distributor of Phoenix Contact 2708892 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 | 
Recommended