Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
PSI-TERMINATOR-PB-TBUS
Weight
0.14 kg

PSI-TERMINATOR-PB-TBUS - Termination resistor

Active termination resistor for PROFIBUS and RS-485 bus systems, redundant power supply, routing of the supply voltage via DIN rail connector, electrical isolation, switchable termination, integrated programming interface

  • Diagnostic LEDs for voltage and data activity
  • Interference-free bus communication thanks to active termination
  • Compact housing design
  • Fixed programming interface in the network
  • Termination can be connected externally
  • Installation as single device or in combination with other devices
  • Extended temperature range of -40 °C … +70 °C
  • Electrical isolation of power supply and data interface
  • Redundant power supply
  • Supply voltage routed through a DIN rail connector for use in combination with other devices
Technical Specifications

Utilization restriction

EMC noteEMC: class A product, see manufacturer's declaration in the download area
CCCex noteUse in potentially explosive areas is not permitted in China.

Product properties

MTTF3305 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
MTTF1923 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
MTTF911 Years (SN 29500 standard, temperature 40°C, operating cycle 100%)

Insulation characteristics

Overvoltage categoryII
Pollution degree2

Electrical properties

Electrical isolationRS-485 // VCC
Maximum power dissipation for nominal condition0.24 W
Test voltage data interface/power supply1.5 kV AC (50 Hz, 1 min.)

Supply

Supply Voltage Range18 V DC ... 30 V DC (via pluggable COMBICON screw terminal block)
Nominal Supply Voltage24 V DC (via pluggable COMBICON screw terminal block)
Typical current consumption10 mA (24 V DC, no load on D-SUB)
Typical current consumption60 mA (24 V DC, current drain at D-SUB of 150 mA)
Max. current consumption12 mA (18 V DC, no load on D-SUB)
Max. current consumption77 mA (18 V DC, current drain at D-SUB of 150 mA)

Function

Status and diagnostic indicatorsLEDs: US (power supply), ACT (data activity)

Supply

Single conductor/terminal point, rigid0.2 mm² ... 2.5 mm²
Single-wire/terminal point, flexible0.2 mm² ... 2.5 mm²
Conductor cross section, flexible [AWG]24 ... 12
Tightening torque0.6 Nm ... 0.8 Nm

Interfaces

SignalModbus
SignalPROFIBUS

Data: PROFIBUS acc. to IEC 61158, RS-485 2-conductor

Serial transmission speed≤ 12 Mbps
Connection MethodD-SUB-9, COMBICON
Transmission length≤ 1200 m (Depends on transmission speed and cable type)
Termination resistor390 Ω
Termination resistor220 Ω
Termination resistor390 Ω (Can be connected)
Single conductor/terminal point, rigid0.2 mm² ... 1.5 mm²
Single-wire/terminal point, flexible0.2 mm² ... 1.5 mm²
Max. AWG conductor cross section, flexible16
Min. AWG conductor cross section, flexible24
Single-wire/terminal point, rigid AWG max.16
Single-wire/terminal point, rigid AWG min.24
Output nominal voltage5 V DC

Dimensions

Width22.5 mm
Height92 mm
Depth73 mm

Material specifications

Color (Housing)green (RAL 6021)
Material (Housing)PA 6.6-FR

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation)
Altitude≤ 2000 m (Restrictions for ATEX applications)
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Air pressure (operation)≤ 80 kPa (When used in EX zone 2)

CE

CertificateCE-compliant

ATEX

Identification II 3 G Ex nA IIC T4 Gc X
NotePlease follow the special installation instructions in the documentation!

UL, USA/Canada

Identification508 Listed

Corrosive gas test

IdentificationISA-S71.04-1985 G3 Harsh Group A

EMC data

Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Contact discharge± 6 kV (Test Level 3)
Discharge in air± 8 kV (Test Level 3)
Indirect discharge± 6 kV
CommentsCriterion B

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 3 GHz (Test Level 3)
Field intensity10 V/m
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input± 2.2 kV (Test Level 3)
Signal± 2.2 kV (Test Level 3)
CommentsCriterion B

Surge current load (surge)

Standards/regulationsEN 61000-4-5
Input± 0.5 kV (sym./asym.)
Signal± 1 kV (Data line, asymmetrical)
CommentsCriterion B

Conducted interference

Standards/regulationsEN 61000-4-6
Frequency Range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V

Emitted interference

Standards/regulationsEN 55011
CommentsClass A, industrial applications

Criteria

Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.

Standards and Regulations

Free from substances that could impair the application of coatingin accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0

Mounting

Mounting TypeDIN rail mounting
Accessories

Why Proax for Phoenix Contact 2702636?

Proax is an authorized distributor of Phoenix Contact 2702636 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability