2702636
SKU
PHX2702636
MPN
PSI-TERMINATOR-PB-TBUS
Weight
0.14 kg
PSI-TERMINATOR-PB-TBUS - Termination resistor
Active termination resistor for PROFIBUS and RS-485 bus systems, redundant power supply, routing of the supply voltage via DIN rail connector, electrical isolation, switchable termination, integrated programming interface
- Diagnostic LEDs for voltage and data activity
- Interference-free bus communication thanks to active termination
- Compact housing design
- Fixed programming interface in the network
- Termination can be connected externally
- Installation as single device or in combination with other devices
- Extended temperature range of -40 °C … +70 °C
- Electrical isolation of power supply and data interface
- Redundant power supply
- Supply voltage routed through a DIN rail connector for use in combination with other devices
Technical Specifications
Utilization restriction
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| CCCex note | Use in potentially explosive areas is not permitted in China. |
Product properties
| MTTF | 3305 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
| MTTF | 1923 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) |
| MTTF | 911 Years (SN 29500 standard, temperature 40°C, operating cycle 100%) |
Insulation characteristics
| Overvoltage category | II |
| Pollution degree | 2 |
Electrical properties
| Electrical isolation | RS-485 // VCC |
| Maximum power dissipation for nominal condition | 0.24 W |
| Test voltage data interface/power supply | 1.5 kV AC (50 Hz, 1 min.) |
Supply
| Supply Voltage Range | 18 V DC ... 30 V DC (via pluggable COMBICON screw terminal block) |
| Nominal Supply Voltage | 24 V DC (via pluggable COMBICON screw terminal block) |
| Typical current consumption | 10 mA (24 V DC, no load on D-SUB) |
| Typical current consumption | 60 mA (24 V DC, current drain at D-SUB of 150 mA) |
| Max. current consumption | 12 mA (18 V DC, no load on D-SUB) |
| Max. current consumption | 77 mA (18 V DC, current drain at D-SUB of 150 mA) |
Function
| Status and diagnostic indicators | LEDs: US (power supply), ACT (data activity) |
Supply
| Single conductor/terminal point, rigid | 0.2 mm² ... 2.5 mm² |
| Single-wire/terminal point, flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section, flexible [AWG] | 24 ... 12 |
| Tightening torque | 0.6 Nm ... 0.8 Nm |
Interfaces
| Signal | Modbus |
| Signal | PROFIBUS |
Data: PROFIBUS acc. to IEC 61158, RS-485 2-conductor
| Serial transmission speed | ≤ 12 Mbps |
| Connection Method | D-SUB-9, COMBICON |
| Transmission length | ≤ 1200 m (Depends on transmission speed and cable type) |
| Termination resistor | 390 Ω |
| Termination resistor | 220 Ω |
| Termination resistor | 390 Ω (Can be connected) |
| Single conductor/terminal point, rigid | 0.2 mm² ... 1.5 mm² |
| Single-wire/terminal point, flexible | 0.2 mm² ... 1.5 mm² |
| Max. AWG conductor cross section, flexible | 16 |
| Min. AWG conductor cross section, flexible | 24 |
| Single-wire/terminal point, rigid AWG max. | 16 |
| Single-wire/terminal point, rigid AWG min. | 24 |
| Output nominal voltage | 5 V DC |
Dimensions
| Width | 22.5 mm |
| Height | 92 mm |
| Depth | 73 mm |
Material specifications
| Color (Housing) | green (RAL 6021) |
| Material (Housing) | PA 6.6-FR |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -40 °C ... 70 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation) |
| Altitude | ≤ 2000 m (Restrictions for ATEX applications) |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Air pressure (operation) | ≤ 80 kPa (When used in EX zone 2) |
CE
| Certificate | CE-compliant |
ATEX
| Identification | II 3 G Ex nA IIC T4 Gc X |
| Note | Please follow the special installation instructions in the documentation! |
UL, USA/Canada
| Identification | 508 Listed |
Corrosive gas test
| Identification | ISA-S71.04-1985 G3 Harsh Group A |
EMC data
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Electrostatic discharge
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | ± 6 kV (Test Level 3) |
| Discharge in air | ± 8 kV (Test Level 3) |
| Indirect discharge | ± 6 kV |
| Comments | Criterion B |
Electromagnetic HF field
| Standards/regulations | EN 61000-4-3 |
| Frequency Range | 80 MHz ... 3 GHz (Test Level 3) |
| Field intensity | 10 V/m |
| Comments | Criterion A |
Fast transients (burst)
| Standards/regulations | EN 61000-4-4 |
| Input | ± 2.2 kV (Test Level 3) |
| Signal | ± 2.2 kV (Test Level 3) |
| Comments | Criterion B |
Surge current load (surge)
| Standards/regulations | EN 61000-4-5 |
| Input | ± 0.5 kV (sym./asym.) |
| Signal | ± 1 kV (Data line, asymmetrical) |
| Comments | Criterion B |
Conducted interference
| Standards/regulations | EN 61000-4-6 |
| Frequency Range | 0.15 MHz ... 80 MHz |
| Comments | Criterion A |
| Voltage | 10 V |
Emitted interference
| Standards/regulations | EN 55011 |
| Comments | Class A, industrial applications |
Criteria
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Standards and Regulations
| Free from substances that could impair the application of coating | in accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0 |
Mounting
| Mounting Type | DIN rail mounting |
Accessories
ME 22,5 TBUS 1,5/ 5-ST-3,81 GN - DIN rail connector, color: green, nominal current: 8 A (parallel contacts), rated voltage (III/2): 125 V, number of positions: 5, product range: TBUS5-22,5.., pitch: 3.81 mm, mounting: DIN rail mounting, locking: without, mounting: without, type of packaging: packed in cardboard, Item with gold-plated contacts, bus connectors for connecting with electronics housings, 5 parallel contacts
SUBCON-PLUS-PROFIB/90/PG/IDC - D-SUB connector, 9-pos., male connector, 90° cable entry, bus system: PROFIBUS DP up to 12 Mbps with PG D-SUB socket for connecting a programming device, termination resistor can be switched on via slide switch, pin assignment: 3, 5, 6, 8; IDC terminal block connection
SUBCON-PLUS-PROFIB/90/PG/SC - D-SUB connector, 9-pos., male connector, 90° cable entry, bus system: PROFIBUS DP up to 12 Mbps with PG D-SUB socket for connecting a programming device, termination resistor can be switched on via slide switch, pin assignment: 3, 5, 6, 8; screw connection terminal blocks
SUBCON-PLUS-PROFIB/PG/SC2 - D-SUB connector, 9-pos., male connector, 35° cable entry, bus system: PROFIBUS DP up to 12 Mbps with PG D-SUB socket for connecting a programming device, termination resistor can be switched on via slide switch, pin assignment: 3, 5, 6, 8; screw connection terminal blocks
Why Proax for Phoenix Contact 2702636?
Proax is an authorized distributor of Phoenix Contact 2702636 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
PSI-TERMINATOR-PB, PROFIBUS or other RS-485 networks can be actively terminated at the end of the bus using the PSI-TERMINATOR-PB. This ensures safe communication even if the bus device is connected/disconnected during operation. In addition, the connectable termination enables the device to be operated as a service interface at any point in the bus system. For the operation of active programming and diagnostic devices, the required power supply is provided at the alternative D-SUB connection.