Official Distributor
SKU
MPN
TRIO-PS-2G/1AC/24DC/3/C2LPS
Weight
0.364 kg
Series TRIO-PS
TRIO-PS-2G/1AC/24DC/3/C2LPS - Power supply unit
Primary-switched TRIO POWER power supply with push-in connection for DIN rail mounting, input: 1-phase, output: 24 V DC/3 A C2LPS
- Save time and costs, thanks to the Push-in connection and narrow design
- Increase system availability, thanks to dynamic boost with 150% of the nominal current for five seconds
- Maximum flexibility due to the wide temperature range from -25°C to +70°C and device startup at -40°C
- Rugged design
Technical Specifications
AC operation
Network Type | Star network |
Nominal input voltage range | 100 V AC ... 240 V AC |
Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
Input Voltage Range AC | 85 V AC ... 264 V AC |
Electric strength, max. | ≤ 300 V AC 15 s |
Typical national grid voltage | 120 V AC |
Typical national grid voltage | 230 V AC |
Voltage type of supply voltage | AC/DC |
Inrush Current | ≤ 15 A (typical) |
Inrush current integral (I2t) | < 0.26 A2s |
Inrush current limitation | typ. 15 A (after 1 ms) |
AC frequency range | 50 Hz ... 60 Hz ±10 % |
Mains buffering time | typ. 10 ms (120 V AC) |
Mains buffering time | typ. 20 ms (230 V AC) |
Current consumption | 1.4 A (100 V AC) |
Current consumption | 1 A (120 V AC) |
Current consumption | 0.6 A (230 V AC) |
Current consumption | 0.7 A (240 V AC) |
Nominal Power Consumption | 157.7 VA |
Protective circuit | Transient surge protection; Varistor |
Power factor (cos phi) | 0.52 |
Typical response time | < 1 s |
Input fuse | 6.3 A (internal (device protection)) |
Recommended breaker for input protection | 6 A ... 16 A (Characteristics B, C, D, K) |
Discharge current to PE | < 0.25 mA |
DC operation
Nominal input voltage range | 110 V DC ... 250 V DC |
Input voltage range | 99 V DC ... 275 V DC |
Voltage type of supply voltage | AC/DC |
Mains buffering time | > 20 ms (230 V AC) |
Current consumption | 0.8 A (110 V DC) |
Current consumption | 0.3 A (250 V DC) |
Output data
Efficiency | > 89 % (for 230 V AC and nominal values) |
Output characteristic | U/I with dynamic load reserve |
Nominal Output Voltage | 24 V DC ±1 % |
Setting range of the output voltage (USet) | 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) | 3 A |
Dynamic Boost (IDyn.Boost) | 4.5 A (1 s) |
Derating | > 60 °C ... 70 °C (2.5 %/K) |
Feedback voltage resistance | ≤ 35 V DC |
Protection against overvoltage at the output (OVP) | ≤ 30 V DC |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
Control deviation | < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) |
Control deviation | < 0.1 % (change in input voltage ±10 %) |
Residual ripple | < 50 mVPP (with nominal values) |
Output Power | 72 W |
Output Power | 108 W (1 s) |
Maximum no-load power dissipation | < 1 W |
Power loss nominal load max. | < 10 W |
Rise time | ≤ 15 ms (UOUT (10 % ... 90 %)) |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Signal: DC OK
Maximum Switching Voltage | 30 V AC/DC |
Continuous load current | 100 mA |
Input
Connection Method | Push-in connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 4 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 10 mm |
Output
Connection Method | Push-in connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 4 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 8 mm |
Signal
Connection Method | Push-in connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 1.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 1.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 16 |
Stripping length | 8 mm |
Signaling
Types of signaling | LED |
Types of signaling | Floating signal contact |
Signal output: LED status indicator
Signalization designation | DC OK |
Status display | “DC OK” LED |
Color | green |
Electrical properties
Number of phases | 1.00 |
Insulation voltage input/output | 3 kV AC (type test) |
Insulation voltage input/output | 1.5 kV AC (routine test) |
Product properties
Product family | TRIO POWER |
MTBF (IEC 61709, SN 29500) | > 3500000 h (25 °C) |
MTBF (IEC 61709, SN 29500) | > 2000000 h (40 °C) |
MTBF (IEC 61709, SN 29500) | > 930000 h (60 °C) |
Insulation characteristics
Protection class | II (in closed control cabinet) |
Degree of pollution | 2 |
Dimensions
Width | 30 mm |
Height | 130 mm |
Depth | 115 mm |
Installation dimensions
Installation distance right/left | 0 mm / 0 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
With protective coating | No |
Material specifications
Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
Housing Material | Plastic |
Type of housing | Polycarbonate |
Hood version | Polycarbonate |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (start-up type tested) | -25 °C |
Maximum altitude | ≤ 5000 m (> 2000 m, observe derating) |
Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
Vibration (Operation) | 15 Hz ... 150 Hz, 4g, 90 min. |
Standards and Regulations
Rail applications | EN 50121-4 |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Standard - Electrical safety | IEC 62368-1 (SELV) |
Standard – Safety extra-low voltage | IEC 62368-1 (SELV) und EN 60204-1 (PELV) |
Standard - Safe isolation | DIN VDE 0100-410 |
Standard - Safety of transformers | EN 61558-2-16 (air clearances and creepage distances only) |
Approvals
UL approvals | UL Listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
UL approvals | NEC Class 2 as per UL 1310 |
Conformity/Approvals
SIL in accordance with IEC 61508 | 0 |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 55011 (EN 55022) |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | 6 kV (Test Level 4) |
Discharge in air | 8 kV (Test Level 4) |
Comments | Criterion A |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 1 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency Range | 1 GHz ... 2 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency Range | 2 GHz ... 3 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | 4 kV (Test Level 4 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 1 kV (Test Level 1 - symmetrical) |
Input | 2 kV (Test Level 1 - asymmetrical) |
Output | 0.5 kV (Test Level 1 - symmetrical) |
Output | 0.5 kV (Test Level 1 - asymmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
Input/Output | asymmetrical |
Frequency Range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Emitted interference
Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Accessories
Why Proax for Phoenix Contact 2903147?
Proax is an authorized distributor of Phoenix Contact 2903147 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended