Official Distributor
SKU
MPN
CBM E8 24DC/0.5-10A NO-R
Weight
0.306 kg
Series CBM-E
CBM E8 24DC/0.5-10A NO-R - Electronic circuit breaker
Multi-channel, electronic circuit breaker with active current limitation for protecting eight loads at 24 V DC in the event of overload and short circuit. With nominal current assistant and electronic locking of the set nominal currents. For installation on DIN rails.
- Easy to configure, thanks to the nominal current assistant
- Active current limitation to improve the capacity of the upstream power supply
- Adjustable in increments per channel: from 0.5 A to 10 A
- Easy system monitoring with early signaling and direct pickup of information at the product
- Increased system availability with intelligent detection of under- and overvoltage
Technical Specifications
Product properties
Product family | CBM |
Type | DIN rail module, one-piece |
Number of Positions | 1 |
No. of channels | 8 |
Insulation characteristics
Protection class | III |
Pollution degree | 2 |
General
Operating Voltage | 18 V DC ... 30 V DC |
Rated voltage | 24 V DC |
Rated current IN | max. 80 A DC (for double supply IN+ with at least 2 x 6 mm²) |
Rated current IN | max. 70 A DC (for UL 2367) |
Rated current IN | 0.5 / 1 / 2 / 4 / 6 / 10 A DC (adjustable per output channel) |
Rated current (pre-adjusted) | 0.5 A |
Rated surge voltage | 0.5 kV |
Tripping method | E (electronic) |
Feedback resistance | max. 35 V DC |
Required backup fuse | Only required if Imax of the power supply > the short-circuit switching capacity. Integrated failsafe element. |
Short-circuit switching capacity | 300 A |
Dielectric strength | max. 30 V DC (Load circuit) |
Active current limitation | typ. 1.5 x IN (2 - 10 A) |
Fuse | electronic |
Efficiency | > 99 % |
Closed circuit current I0 | typ. 50 mA |
Power dissipation | 1.2 W (No-load operation) |
Power dissipation | 17.2 W (Nominal operation) |
Module initialization time | 3.3 s |
Waiting time after switch off of a channel | 10 s (at overload / short circuit) |
Measuring tolerance I | typ. 40 % (0.5 A ... 1 A) |
Measuring tolerance I | typ. 10 % (2 A ... 10 A) |
Temperature derating | 40 A DC (at 70°C (65°C for UL 2367)) |
Temperature derating | 50 A DC (at 60 °C) |
Temperature derating | 60 A DC (at 50 °C) |
Temperature derating | 70 A DC (at 40 °C) |
Temperature derating | 80 A DC (at 40 °C) |
Temperature derating | 70 A DC (at 40°C for UL 2367) |
MTBF (IEC 61709, SN 29500) | 1304293 h (at 25 °C) |
MTBF (IEC 61709, SN 29500) | 858501 h (at 40 °C) |
MTBF (IEC 61709, SN 29500) | 440048 h (at 60 °C) |
Fail-safe element | 15 A DC (per output channel) |
Load circuit
Shutdown time | 0.02 s (> 1.3 x IN) |
Shutdown time | 30 s (1.1 ... 1.3 x IN) |
Undervoltage switch-off | ≤ 17.8 V DC (active) |
Undervoltage switch-off | ≥ 19 V DC (inactive) |
Overvoltage switch-off | ≥ 30.5 V DC (active) |
Overvoltage switch-off | ≤ 29.5 V DC (inactive) |
Max. capacitive load | 75000 µF |
Reset
Input voltage range | 7 V DC ... 30 V DC (Reset with falling edge) |
Current consumption | typ. 0.4 mA (at 24 V DC) |
Pulse length | ≥ 50 ms (High signal) |
Pulse length | ≥ 50 ms (Low signal) |
Voltage | < 5 V DC (Low signal) |
Voltage | > 8 V DC (High signal) |
Status output
Output Voltage | 24 V DC |
Output Current | max. 20 mA (when I > 80% at at least one channel) |
Indicator/remote signaling
Connection name | Remote indication circuit |
Switching function | N/O contact |
Operating Voltage | 0 V DC ... 30 V DC |
Operating current | 1 mA DC ... 100 mA DC |
Main circuit IN+
Connection Method | Push-in connection |
Stripping length | 18 mm |
Conductor cross section rigid | 0.75 mm² ... 16 mm² |
Conductor cross section AWG | 20 ... 4 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.75 mm² ... 10 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.75 mm² ... 16 mm² |
Main circuit IN-
Connection Method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
Main circuit OUT
Connection Method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
Remote indication circuit
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
Signaling
DC OK LED off | off (No supply voltage) |
DC OK LED yellow | lit (Undervoltage active, voltage ≤ 17.8 V, active channels switched off and channel LEDs are lit red) |
DC OK LED yellow | flashing (Undervoltage switch-off inactive, device was in undervoltage switch-off) |
DC OK LED green | lit (Operating voltage in nominal range 18 ... 30 V) |
DC OK LED red | lit (Overvoltage switch-off active, voltage ≥ 30.5 V, channels switched off and channel LEDs are lit red) |
DC OK LED red | flashing (Overvoltage switch-off inactive, device was in overvoltage shutdown) |
Channel LED off | off (Channel switched off) |
Channel LED yellow | lit (Channel switched on, channel load > 80% ) |
Channel LED yellow-green | flashing (Channel switched on, nominal current assistant active) |
Channel LED green | lit (Channel switched on) |
Channel LED green | flashing (Channel switched on, programming mode active) |
Channel LED red | lit (Channel switched off, over- or undervoltage active) |
Channel LED red | ON temporarily (Channel switched off, 10 s cool-down phase, overload or short-circuit release) |
Channel LED red | flashing (Channel switched off, ready to be switched back on, overload or short-circuit release) |
Channel LED red-yellow | flashing (Channel switched on, overload mode, capacity approximately 110 ... 130% , shutdown after 30 s) |
Channel LED red-green | flashing (Channel switched off, programming mode active, current adjustment after overload or short-circuit release) |
Dimensions
Width | 41 mm |
Height | 130 mm |
Depth | 121 mm (incl. DIN rail 7.5 mm) |
Material specifications
Color | light grey (RAL 7035) |
Color | gray (RAL 7042) |
Material | PC |
Material | PA 6.6 |
Material | PC |
Material | PBT-FR17 |
Material | POM |
Flammability rating according to UL 94 | V-0 |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C (Startup at -40 C type-tested) |
Ambient Temperature (Operation) | -25 °C ... 65 °C (for UL 2367) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 6000 m (amsl) |
Humidity test | 240 h, 95 % RH, 40 °C |
Shock (operation) | 30g (IEC 60068-2-27, Test Ea) |
Vibration (Operation) | 5 Hz ... 24.9 Hz (Amplitude ±1.6 mm; in accordance with IEC 60068-2-6, Test Fc) |
Vibration (Operation) | 24.9 Hz … 150 Hz (Acceleration 4g; in accordance with IEC 60068-2-6, Test Fc with additional resonance frequency testing in accordance with DNV GL) |
UL approval
Identification | UL/C-UL Listed UL 508 |
Identification | UL Recognized UL 2367 |
Identification | UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
Shipbuilding approval
Identification | DNV GL |
Corrosive gas test
Identification | ISA S71.04.2013 G3 Harsh Group A |
DNV GL data
Temperature | D |
Humidity | B |
Vibration | B |
EMC | A |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Standards and Regulations
Standards/specifications | EN 61000-6-2 |
Note | EMC – Immunity for industrial areas |
Standards/specifications | EN 61000-6-3 |
Note | EMC – Emission for residential, business and commercial properties and small operations |
Standards/specifications | EN 60068-2-6 |
Note | Environmental influences – Vibrations (sinusoidal) |
Standards/specifications | EN 60068-2-1 |
Note | Environmental influences – Part 2-1: Tests – Test A: Cold |
Standards/specifications | EN 60068-2-2 |
Note | Environmental influences – Part 2-2: Tests – Test B: Dry heat |
Standards/specifications | EN 60068-2-78 |
Note | Environmental influences – Moisture and heat, constant |
Mounting
Mounting Type | DIN rail: 35 mm |
Accessories
Why Proax for Phoenix Contact 2905744?
Proax is an authorized distributor of Phoenix Contact 2905744 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |