Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
PLT-SEC-T3-230-FM-PT
Weight
0.092 kg
Series PLT-SEC-T3

PLT-SEC-T3-230-FM-PT - Type 3 surge protection device

Type 2/3 surge protection, consisting of protective plug and base element with Push-in connection. For single-phase power supply network with integrated status indicator and remote signaling. Nominal voltage: 230 V AC/DC

  • Surge protection family for universal use with optimum energy coordination from the lightning current arrester to the device protection
  • Easy to maintain due to consistently pluggable protection modules
  • Excellent level of information provided by mechanical/visual status indicator and remote indication contact
  • Your preferred connection technology can be selected as both screw connection and Push-in connection are available
  • Optimal additional protection of the industrial power supply for a longer service life and increased availability of the system
  • 5-year warranty on your QUINT 4 power supply when installed together with PLT-SEC, see document in the download area
Technical Specifications

Product properties

Product familySEC Family
IEC power supply systemTN-S
IEC power supply systemTT
TypeDIN rail module, two-section, divisible
Number of Positions2
Surge protection fault messageOptical, remote indicator contact

Insulation characteristics

Overvoltage categoryIII
Pollution degree2
IEC test classificationII / III
IEC test classificationT2 / T3
EN typeT2 / T3
Number of PortsOne

Indicator/remote signaling

Connection nameRemote fault indicator contact
Switching functionChangeover contact
Operating Voltage250 V AC
Operating Voltage125 V DC (200 mA DC)
Operating current0.5 A AC
Operating current0.5 A DC (75 V DC)

Connection data

Connection MethodPush-in connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section rigid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Dimensions

Width17.7 mm
Height101 mm
Depth74.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Material specifications

Color (Male connector)light grey (RAL 7035)
Color (Base element)gray (RAL 7042)
Flammability rating according to UL 94V-0
CTI value of material600
Insulating materialPA 6.6-FR 20 % GF
Insulating materialPA 6.6-FR
Housing MaterialPA 6.6-FR 20 % GF
Housing MaterialPA 6.6-FR

Protective circuit

Mode of protectionL-N
Mode of protectionL-PE
Mode of protectionN-PE
Direction of action1L-N & N-PE
Nominal voltage UN240 V AC (TN-S)
Nominal voltage UN240 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC264 V AC
Rated load current IL26 A (at 30 °C)
Residual current IPE≤ 5 µA
Standby power consumption PC≤ 26.40 mVA (at UREF)
Standby power consumption PC≤ 26.40 mVA (at UC)
Reference test voltage UREF264.00 V AC
Nominal discharge current In (8/20) µs5 kA
Maximum discharge current Imax (8/20) µs10 kA
Combination wave UOC6 kV
Voltage protection level Up (L-N)≤ 1.25 kV (at UOC)
Voltage protection level Up (L-N)≤ 1.4 kV (at In)
Voltage protection level Up (L-PE)≤ 1.4 kV
Voltage protection level Up (N-PE)≤ 1.4 kV
TOV behavior at UT (L-N)400 V AC (5 s / withstand mode)
TOV behavior at UT (L-N)457 V AC (120 min / safe failure mode)
TOV behavior at UT (L-PE)457 V AC (5 s / withstand mode)
TOV behavior at UT (L-PE)457 V AC (120 min / withstand mode)
TOV behavior at UT (L-PE)1464 V AC (200 ms / safe failure mode)
TOV behavior at UT (N-PE)1200 V AC (200 ms / safe failure mode)
Response time tA (L-N)≤ 25 ns
Response time tA (L-PE)≤ 100 ns
Response time tA (N-PE)≤ 100 ns
Short-circuit current rating ISCCR10 kA AC
Max. backup fuse with branch wiring32 A (gG / B / C)

Additional technical data

Short-circuit current rating ISCCR0.25 kA DC (Without additional backup fuse in the DC branch wiring)
Short-circuit current rating ISCCR5 kA DC (for 20 A gG / B backup fuse)
Residual voltage Ures (L-N)≤ 1.15 kV (at 2 kA)
Residual voltage Ures (L-N)≤ 1.25 kV (at 3 kA)
Residual voltage Ures (L-N)≤ 1.1 kV (at UOC = 4 kV)
Residual voltage Ures (L-PE)≤ 1.1 kV (at 2 kA)
Residual voltage Ures (L-PE)≤ 1.1 kV (at 3 kA)
Residual voltage Ures (L-PE)≤ 1.2 kV (at UOC = 4 kV)
Residual voltage Ures (N-PE)≤ 1.1 kV (at 2 kA)
Residual voltage Ures (N-PE)≤ 1.1 kV (at 3 kA)
Residual voltage Ures (N-PE)≤ 1.2 kV (at UOC = 4 kV)
Maximum continuous voltage UC275 V AC
Maximum continuous voltage UC240 V DC
Mode of protection(DC+) - (DC-)
Mode of protection(DC+/DC-) - PE
IEC test classification (in accordance with IEC 61643-21)D1
Impulse durability (wire-wire)D1 - 500 A
Impulse durability (line-earth)D1 - 500 A
Pulse discharge current Iimp (10/350) µs (line-line)0.5 kA
Pulse discharge current Iimp (10/350) µs (line-earth)0.5 kA

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (operating voltage remote contact ≤ 250 V)
Altitude≤ 6000 m (operating voltage remote contact ≤ 150 V)
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (Operation)5g (5 ... 500 Hz / 2.5 h / X, Y, Z)

Standards and Regulations

Standards/specificationsIEC 61643-11
Note2011

EN 61643-11

Standards/specificationsEN 61643-11
Note2012

Mounting

Mounting TypeDIN rail: 35 mm

Why Proax for Phoenix Contact 2907928?

Proax is an authorized distributor of Phoenix Contact 2907928 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.