Technical Specifications

DC operation

Nominal input voltage range600 V DC ... 1500 V DC
Input voltage range600 V DC ... 1500 V DC -15 % ... +10 %
Wide-range inputno
Input voltage range DC600 V DC ... 1500 V DC -15 % ... +10 %
Electric strength, max.≤ 1800 V DC 1 s
Typical national grid voltage1500 V DC
Typical national grid voltage600 V DC
Voltage type of supply voltageDC
Inrush current integral (I2t)typ. 0.15 A2s
Current consumptiontyp. 0.35 A (600 V DC)
Current consumptiontyp. 0.145 A (1500 V DC)
Recommended breaker for input protection2 A (gPV)
Recommended fuse for input protection1500 V DC

Output data

Efficiencytyp. 91.5 % (600 V DC)
Efficiencytyp. 90.9 % (900 V DC)
Efficiencytyp. 89 % (1500 V DC)
Nominal Output Voltage24 V DC ±1 %
Setting range of the output voltage (USet)24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)8 A
Derating> 60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance≤ 35 V DC
Protection against overvoltage at the output (OVP)≤ 30 V DC
Control deviation< 1 % (change in load, static 10 % ... 90 %)
Control deviation< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
Control deviation< 0.1 % (change in input voltage ±10 %)
Residual ripple< 40 mVPP (Ripple)
Residual ripple< 50 mVPP (Noise)
Short-circuit-proofyes
No-load proofyes
Output Power192 W
Maximum no-load power dissipation< 9 W
Power loss nominal load max.< 24 W
Rise time≤ 30 ms (UOUT (10 % ... 90 %))
Connection in parallelyes, for redundancy and increased capacity
Connection in seriesNo

Signal: DC OK

Continuous load current100 mA

Signal relay 13/14

Defaultclosed
Digital30 V AC 30 V DC 100 mA

Input

Connection MethodPush-in connection
Conductor cross section, rigid min.1 mm²
Conductor cross section, rigid max.4 mm²
Conductor cross section flexible min.1 mm²
Conductor cross section flexible max.2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.1 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.1 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.2.5 mm²
Conductor cross section AWG min.18
Conductor cross section AWG max.12
Stripping length10 mm

Output

Connection MethodPush-in connection
Conductor cross section, rigid min.1 mm²
Conductor cross section, rigid max.4 mm²
Conductor cross section flexible min.1 mm²
Conductor cross section flexible max.2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.1.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.1.5 mm²
Conductor cross section AWG min.18
Conductor cross section AWG max.12
Stripping length10 mm

Signal

Connection MethodPush-in connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.1.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

Signaling

Types of signalingLED
Types of signalingFloating signal contact

Signal output: LED status indicator

Signalization designationDC OK
Status display"DC OK" LED green
Note on status displayUOUT > 21.5 V: LED lights up
Colorgreen
DC OKUOUT > 0.9 x UN (UN = 24 V DC)

Electrical properties

Number of phases1.00
Insulation voltage input/output4.2 kV DC (type test)
Insulation voltage input/output2.6 kV DC (routine test)

Product properties

Product familyTRIO POWER
MTBF (IEC 61709, SN 29500)> 1500000 h (25 °C)
MTBF (IEC 61709, SN 29500)> 900000 h (40 °C)
MTBF (IEC 61709, SN 29500)> 400000 h (60 °C)

Insulation characteristics

Protection classI
Degree of pollution2

Dimensions

Width88.5 mm
Height130 mm
Depth160 mm

Installation dimensions

Installation distance right/left0 mm / 0 mm (≤ 40°C)
Installation distance right/left (active)10 mm / 10 mm (≤ 70 °C)
Installation distance top/bottom50 mm / 50 mm (≤ 70 °C)
Installation distance top/bottom (active)50 mm / 50 mm (≤ 70 °C)

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsalignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
Mounting Positionhorizontal DIN rail NS 35, EN 60715
With protective coatingNo

Material specifications

Flammability rating according to UL 94 (housing / terminal blocks)V0
Housing MaterialMetal
Type of housingAluminum (AlMg3)
Hood versionPolycarbonate

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 70 °C (>60°C derating: 1.2%/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Ambient temperature (start-up type tested)-40 °C
Maximum altitude≤ 4000 m (> 2000 m, Derating: 10 %/1000 m)
Climatic class3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (Operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (Operation)15 Hz ... 150 Hz, 2.3g, 90 min.

Standards and Regulations

Standard - Electrical safetyEN 62109-1:2011
Standard – Safety extra-low voltageIEC 62109-1:2011 (SELV)
Standard - Safe isolationDIN VDE 0100-410

Overvoltage category

IEC 62109-1II

Approvals

UL approvalsUL 62109-1:2014

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
Noise immunityEN 61000-6-2:2005
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Conducted noise emissionEN 55016
Conducted noise emissionEN 61000-6-4 (Class A)
Noise emissionEN 55016
Noise emissionEN 61000-6-4 (Class A)

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Contact discharge4 kV (Test Level 2)
Discharge in air8 kV (Test Level 3)
CommentsCriterion A

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 1 GHz
Test field strength20 V/m (> Test intensity 3)
Frequency Range1 GHz ... 2 GHz
Test field strength10 V/m (Test Level 3)
Frequency Range2 GHz ... 3 GHz
Test field strength10 V/m (Test Level 3)
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input4 kV (Test Level 4 - asymmetrical)
Output2 kV (Test Level 3 - asymmetrical)
Signal1 kV (Test Level 3 - asymmetrical)
CommentsCriterion B

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Input1 kV (Test Level 3 - symmetrical)
Input2 kV (Test Level 3 - asymmetrical)
Output0.5 kV (Test Level 2 - symmetrical)
Output0.5 kV (Test Level 1 - asymmetrical)
Signal1 kV (Test Level 2 - asymmetrical)
CommentsCriterion B

Conducted interference

Standards/regulationsEN 61000-4-6
Input/Outputasymmetrical
Frequency Range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)

Voltage dips

Standards/regulationsEN 61000-4-11

Emitted interference

Standards/regulationsEN 61000-6-4
Radio interference voltage in acc. with EN 55011EN 55011 (EN 55022) Class A industrial area of application
Emitted radio interference in acc. with EN 55011EN 55011 (EN 55022) Class A industrial area of application

Criteria

Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Accessories

Why Proax for Phoenix Contact TRIO-PS-2G/1500DC/24DC/8?

Proax is an authorized distributor of Phoenix Contact TRIO-PS-2G/1500DC/24DC/8 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesTRIOPS2G1500DC24DC8
Pack Size1
Recommended

Available for order