VAL-MS 1500DC-PV/2+V
Weight
0.351 kg
Series VAL-MS
VAL-MS 1500DC-PV/2+V - Type 2 surge arrester
Surge protective device for 2-pos. isolated and grounded 1500 V DC PV systems, for DIN rail mounting, 3-pos. base element, three pluggable temperature-monitored protective elements, status message on each plug.
- Quality proven millions of times over in the widest range of applications
- Rapid installation with bridges, thanks to industry-standard overall width of 1 HP
- Easy testing and insulation measurement, thanks to pluggable protection modules
- Wide range of applications due to various nominal voltages
- High degree of modularity provides individual solutions for every application
Technical Specifications
General
Note | The device is intended for touch proof installation in a housing. Ensure that there is a gap of at least 8 mm between the active and grounded parts in the connection area. |
Product properties
Product family | VALVETRAB MS |
IEC test classification | PV II |
IEC test classification | PV T2 |
EN type | T2 |
IEC power supply system | DC |
Type | DIN rail module, two-section, divisible |
Distance between live and grounded parts | 8 mm |
Installation location | Interior |
Installation location of the disconnect device | Internal |
Accessibility | Accessible |
Connection configuration | Y configuration |
SPD failure behavior | OCFM (Open-Circuit Failure Mode) |
Surge protection fault message | optical |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 |
Connection data
Connection Method | Screw connection |
Screw thread | M5 |
Tightening torque | 3 Nm (1.5 mm² ... 16 mm²) |
Tightening torque | 4.5 Nm (25 mm² ... 35 mm²) |
Stripping length | 16 mm |
Conductor cross section flexible | 1.5 mm² ... 25 mm² |
Conductor cross section rigid | 1.5 mm² ... 35 mm² |
Conductor cross section AWG | 15 ... 2 |
Connection Method | Fork-type cable lug |
Conductor cross section flexible | 1.5 mm² ... 16 mm² |
Dimensions
Width | 53.4 mm |
Height | 89.8 mm |
Depth | 65.7 mm |
Horizontal pitch | 3 Div. |
Material specifications
Color | black (RAL 9005) |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PA 6.6-FR |
Insulating material | PBT-FR |
Material group | I |
Housing Material | PA 6.6-FR |
Housing Material | PBT-FR |
Mechanical data
Open side panel | No |
Protective circuit
Mode of protection | (L+) - (L-) |
Mode of protection | (L+) - PE |
Mode of protection | (L-) - PE |
Direction of action | (L+)-PE & (L-)-PE & (L+)-(L-) |
Rated load current IL | 80 A |
Residual current IPE | ≤ 350 µA DC |
Residual current IPE | ≤ 600 µA AC |
Standby power consumption PC | ≤ 250.00 mVA |
Nominal discharge current In (8/20) µs | 15 kA |
Maximum discharge current Imax (8/20) µs | 30 kA |
Total discharge current Itotal (8/20) µs | 30 kA |
Voltage protection level Up | ≤ 5 kV |
Residual voltage Ures | ≤ 3.8 kV (at 3 kA) |
Residual voltage Ures | ≤ 4.1 kV (at 5 kA) |
Residual voltage Ures | ≤ 4.4 kV (at 10 kA) |
Residual voltage Ures | ≤ 5 kV (at 15 kA) |
Residual voltage Ures | ≤ 5.3 kV (at 20 kA) |
Residual voltage Ures | ≤ 5.7 kV (at 30 kA) |
Residual voltage Ures | ≤ 6 kV (at 40 kA) |
Response time tA | ≤ 25 ns |
PV protective circuit
Connection configuration | Y configuration |
SPD failure behavior | OCFM (Open-Circuit Failure Mode) |
Protective circuit DC voltage side (DC)
Open circuit voltage UOCSTC | ≤ 1250 V DC |
Maximum discharge current Imax (8/20) µs | 30 kA |
Response time tA | ≤ 25 ns |
Total discharge current Itotal (8/20) µs | 30 kA |
Nominal discharge current In (8/20) µs | 15 kA |
Rated load current IL | 80 A |
Continuous operating current ICPV | < 350 µA |
Maximum continuous operating voltage UCPV | 1500 V DC |
Short-circuit current rating ISCPV | 2000 A |
Residual voltage Ures | ≤ 3.8 kV (at 3 kA) |
Residual voltage Ures | ≤ 4.1 kV (at 5 kA) |
Residual voltage Ures | ≤ 4.4 kV (at 10 kA) |
Residual voltage Ures | ≤ 5 kV (at 15 kA) |
Residual voltage Ures | ≤ 5.3 kV (at 20 kA) |
Residual voltage Ures | ≤ 5.7 kV (at 30 kA) |
Residual voltage Ures | ≤ 6 kV (at 40 kA) |
Residual current IPE | ≤ 350 µA DC |
Residual current IPE | ≤ 600 µA AC |
Voltage protection level Up | ≤ 5 kV |
Standby power consumption PC | ≤ 250.00 mVA |
Additional technical data
Maximum discharge current Imax (8/20) µs | 40 kA |
Nominal discharge current In (8/20) µs | 20 kA (4x (5x In | 120 s) | 30 min)) |
Ambient conditions
Degree of Protection | IP20 (only when all terminal points are used) |
Ambient Temperature (Operation) | -40 °C ... 85 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 3000 m (amsl) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (Operation) | 5g (5-500 Hz/2.5 h/XYZ) |
UL specifications
Maximum continuous operating voltage MCOV | 1500 V DC |
Short-circuit current rating (SCCR) | 50 kA |
Voltage protection rating VPR | 4 kV |
Nominal discharge current In | 10 kA |
Mode of protection | (DC+) - (DC-) |
Mode of protection | (DC+) - G |
Mode of protection | (DC-) - G |
Nominal Voltage | 1500 V DC |
Power distribution system | DC PV |
SPD Type | 1CA |
UL connection data
Tightening torque | 30 lbf-in. |
Conductor cross section AWG | 14 ... 2 |
Standards and Regulations
Standards/specifications | EN 61643-31 |
Note | 2019 |
Standards/specifications | IEC 61643-31 |
Note | 2018 |
Mounting
Mounting Type | DIN rail: 35 mm |
Accessories
Why Proax for Phoenix Contact 1033708?
Proax is an authorized distributor of Phoenix Contact 1033708 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |