Official Distributor
SKU
MPN
VAL-MS 120/3+1/FM-UD
Weight
0.387 kg
Series VAL-MS
VAL-MS 120/3+1/FM-UD - Type 2 surge protection device
Surge arrester consisting of base element with remote indicator contact and ground connectors, for mounting on NS 35/7.5, nominal voltage: 120 V AC, 3 + 1 circuit
Technical Specifications
Product properties
Product family | VALVETRAB MS |
IEC test classification | II |
IEC test classification | T2 |
EN type | T2 |
Type | DIN rail module, two-section, divisible |
Number of Positions | 4 |
Surge protection fault message | Optical, remote indicator contact |
Electrical properties
Nominal frequency fN | 50 Hz (60 Hz) |
Nominal voltage UN | 120 V AC (208 V AC) |
Nominal voltage UN | 120 V AC ... 208 V AC |
Indicator/remote signaling
Connection name | Remote fault indicator contact |
Switching function | Changeover contact |
Maximum operating voltage Umax. AC | 250 V AC |
Maximum operating voltage Umax DC | 30 V DC |
Max. operating current Imax | 0.75 A AC (250 V AC) |
Max. operating current Imax | 1.5 A DC (30 V DC) |
Min. permissible switching capacity | 0.12 VA (12 V, 10 mA) |
Connection data
Connection Method | Screw connection |
Screw thread | M5 |
Tightening torque, min | 4.5 Nm |
Stripping length | 14.5 mm |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 25 mm² |
Conductor cross section, rigid min. | 0.5 mm² |
Conductor cross section, rigid max. | 35 mm² |
Remote fault indicator contact
Connection Method | Screw connection |
Screw thread | M2 |
Tightening torque, min | 0.25 Nm |
Stripping length | 7 mm |
Conductor cross section flexible min. | 0.14 mm² |
Conductor cross section flexible max. | 1.5 mm² |
Conductor cross section, rigid min. | 0.14 mm² |
Conductor cross section, rigid max. | 1.5 mm² |
Dimensions
Width | 70.8 mm |
Height | 96.8 mm |
Depth | 65.5 mm |
Horizontal pitch | 4 Div. |
Material specifications
Flammability rating according to UL 94 | V0 |
Housing Material | PBT/PA |
Protective circuit
Direction of action | 3L-N & N-PE |
Nominal voltage UN | 120 V AC ... 208 V AC |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 150 V AC |
Maximum continuous operating voltage UC (L-N) | 150 V AC |
Maximum continuous operating voltage UC (N-PE) | 260 V AC |
Residual current IPE | ≤ 1 µA |
Standby power consumption PC | ≤ 150.00 mVA |
Nominal discharge current In (8/20) µs (L-N) | 20 kA |
Nominal discharge current In (8/20) µs (L-PE) | 20 kA |
Nominal discharge current In (8/20) µs (N-PE) | 20 kA |
Maximum discharge current Imax (8/20) µs | 40 kA |
Maximum discharge current Imax (8/20) µs (L-N) | 40 kA |
Maximum discharge current Imax (8/20) µs (L-PE) | 40 kA |
Maximum discharge current Imax (8/20) µs (N-PE) | 40 kA |
Follow current interrupt rating Ifi (N-PE) | 100 A (260 V) |
Voltage protection level Up (L-N) | ≤ 0.85 kV |
Voltage protection level Up (L-PE) | ≤ 1.05 kV |
Voltage protection level Up (N-PE) | ≤ 1.5 kV |
Response time tA (L-N) | ≤ 25 ns |
Response time tA (L-PE) | ≤ 100 ns |
Response time tA (N-PE) | ≤ 100 ns |
Max. backup fuse with branch wiring | 125 A (gL) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 80 °C |
Air clearances and creepage distances
Standards/regulations | DIN EN 60664-1 |
Standards
Standards/regulations | IEC 61643-1 |
Standards/regulations | EN 61643-11/A11 |
Standards/specifications | IEC 61643-1 |
Note | 2005 |
Standards/specifications | EN 61643-11/A11 |
Note | 2007 |
Mounting
Mounting Type | DIN rail: 35 mm |
Why Proax for Phoenix Contact 2856692?
Proax is an authorized distributor of Phoenix Contact 2856692 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |