Official Distributor
SKU
MPN
VAL-MS 1000DC/2+V-FM-UD
Weight
0.368 kg
Series VAL-MS
VAL-MS 1000DC/2+V-FM-UD - Type 2 surge protection device
Surge arrester for 2-pos. isolated and grounded DC voltage systems 1000 V DC, for DIN rail mounting, 3-pos. base element (L+, L-, ground) with remote indication contact, three pluggable temperature-monitored varistors, status message on each connector.
Technical Specifications
Product properties
Product family | VALVETRAB MS |
IEC test classification | II |
IEC test classification | T2 |
EN type | T2 |
Type | DIN rail module, two-section, divisible |
Number of Positions | 3 |
Surge protection fault message | Optical, remote indicator contact |
Electrical properties
Nominal voltage UN | 1000 V DC (Open-circuit voltage UOC) |
Indicator/remote signaling
Switching function | Changeover contact, 1-pos. |
Maximum operating voltage Umax. AC | 250 V AC |
Max. operating current Imax | 1.5 A AC (250 V AC) |
Max. operating current Imax | 1 A DC (30 V DC) |
Connection data
Connection Method | Screw connection |
Screw thread | M5 |
Tightening torque, min | 4.5 Nm |
Stripping length | 16 mm |
Conductor cross section flexible min. | 1.5 mm² |
Conductor cross section flexible max. | 25 mm² |
Conductor cross section, rigid min. | 1.5 mm² |
Conductor cross section, rigid max. | 35 mm² |
Connection Method | MC 1,5/3 |
Screw thread | M2 |
Tightening torque, min | 0.25 Nm |
Stripping length | 7 mm |
Conductor cross section flexible min. | 0.14 mm² |
Conductor cross section flexible max. | 1.5 mm² |
Conductor cross section, rigid min. | 0.14 mm² |
Conductor cross section, rigid max. | 1.5 mm² |
Dimensions
Width | 53.4 mm |
Height | 99 mm |
Depth | 65.5 mm |
Material specifications
Flammability rating according to UL 94 | V0 |
Housing Material | PBT/PA |
Mechanical data
Open side panel | No |
Protective circuit
Direction of action | (L+)-PE & (L-)-PE & (L+)-(L-) |
Maximum continuous voltage UC | 1000 V DC |
Rated load current IL | ≤ 80 A DC |
Residual current IPE | ≤ 20 µA |
Standby power consumption PC | ≤ 20.00 mW |
Nominal discharge current In (8/20) µs | 15 kA |
Maximum discharge current Imax (8/20) µs | 30 kA |
Voltage protection level Up | ≤ 5 kV |
Voltage protection level Up (L+) - (L-) | ≤ 5 kV |
Voltage protection level Up (L+/L-) - PE | ≤ 5 kV |
Response time tA | ≤ 25 ns |
Protective circuit DC voltage side (DC)
Maximum discharge current Imax (8/20) µs | 30 kA |
Response time tA | ≤ 25 ns |
Nominal discharge current In (8/20) µs | 15 kA |
Rated load current IL | ≤ 80 A DC |
Short-circuit current rating ISCPV | 80 A |
Residual current IPE | ≤ 20 µA |
Voltage protection level Up | ≤ 5 kV |
Voltage protection level Up (L+) - (L-) | ≤ 5 kV |
Voltage protection level Up (L+/L-) - PE | ≤ 5 kV |
Standby power consumption PC | ≤ 20.00 mW |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 80 °C |
Air clearances and creepage distances
Standards/regulations | DIN EN 60664-1 / DIN EN 61643-11 |
Standards
Standards/regulations | DIN EN 61643-11 |
Standards/regulations | IEC 61643-1 |
Standards/regulations | IEC 60364-7-712 |
Standards/specifications | DIN EN 61643-11 |
Note | 2002 |
Standards/specifications | IEC 61643-1 |
Note | 2005 |
Standards/specifications | IEC 60364-7-712 |
Note | 2002 |
Mounting
Mounting Type | DIN rail: 35 mm |
Why Proax for Phoenix Contact 2805567?
Proax is an authorized distributor of Phoenix Contact 2805567 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience