QUINT-HP-UPS/120AC/2.5KVA/PT - Uninterruptible power supply

QUINT AC-USV, IQ Technology, Wall mounting, input: 120 V AC, output: 120 V AC / 2500 VA.

Technical Specifications

Input data

Input Voltage100 V AC -10 % / +20 %
Input Voltage110 V AC -10 % / +20 %
Input Voltage120 V AC -10 % / +15 %
Input Voltage130 V AC -15 % / +10 %
Voltage type of supply voltageAC
Frequency range (fN)47.5 Hz ... 52.5 Hz
Bypass fuse40 A T 250 V
Permissible backup fuse40 A (Listed breaker)
Current consumptionnom. 24 A (100 V AC)
Current consumptionnom. 23.3 A (110 V AC)
Current consumptionnom. 24 A (120 V AC)
Current consumptionnom. 23.4 A (130 V AC)
Current consumptionmax. 34.4 A (100 V AC)
Current consumptionmax. 31.2 A (110 V AC)
Current consumptionmax. 35.4 A (120 V AC)
Current consumptionmax. 34.6 A (130 V AC)
Rated short-time current carrying capacity Icw6 kA

Output data

Classification according to IEC 62040-3VFI-SS-111
Efficiency> 94 % (100% load, battery charged)
Efficiency> 90 % (100% load, battery charged)
Apparent power2500 VA
Real power2250 W
Power factor (cos phi)0.9
Crest factor2.5
Switch-over time0 ms
Connection in parallelyes
Connection in parallelmax. 3
Connection in seriesNo
Overload capability Mains operation120 % ... 150 % (20 s / 5 s, then switch to bypass operation)
Overload capability Battery operation120 % ... 150 % (20 s / 5 s, then shutdown)
Overload capability Bypass mode120 % ... 150 % (for a sustained period / 20 s, then shutdown)
Rated short-time current carrying capacity Icw6 kA

Mains operation

Output Voltage100 V AC ±2 %
Output Voltage110 V AC ±2 %
Output Voltage120 V AC ±2 %
Output Voltage130 V AC ±2 %
Form of output voltagePure sine
Output Currentnom. 20 A (100 V AC)
Output Currentnom. 18.2 A (110 V AC)
Output Currentnom. 20.8 A (120 V AC)
Output Currentnom. 19.2 A (130 V AC)
Maximum no-load power dissipation9 W
Power loss nominal load max.< 120 W (100% load, battery charged)
Nominal output frequency50 Hz
Nominal output frequency60 Hz
Nominal output frequency±0.5 % (Output frequency tolerance)
Electronic current limitation> 2 x Output: Current nom. (> 200 ms)

Battery operation

Maximum no-load power dissipation9 W
Power loss nominal load max.250 W (100% load, battery charged)
Nominal output frequency50 Hz
Nominal output frequency60 Hz
Nominal output frequency±0.5 % (Output frequency tolerance)
Total harmonic distortion factor (THD)< 3 % (linear load)
Total harmonic distortion factor (THD)< 8 % (non-linear load)
Electronic current limitation> 2 x Output: Current nom. (> 200 ms)

Input

Input Voltage48 V DC
Input Voltagemax. 60 V DC
Input Currentmax. 40 A
Nominal capacity range7 Ah ... 200 Ah
Charging currentmax. 10 A

Output

Short-circuit current650 A (< 1,5 ms)

General

Connection in parallelyes
Connection in parallelmax. 5 (per battery string)
Connection in seriesNo
IQ-Technologyyes
Permissible backup fuse40 A
Temperature sensoryes
Permissible backup fuse40 A

Interfaces

InterfaceBattery module communication interface
Number of interfaces1
Connection MethodRJ45
Position5.x
LockingLocking clip
Transmission physicsTwisted-Pair 4x2
InterfaceParallel operation communication interface
Number of interfaces2
Connection MethodRJ45
Position5.x
LockingLocking clip
Transmission physicsTwisted-Pair 4x2

Signal input Bat.-Start

Low signalConnection to SGnd with < 2.7 kΩ
High signalOpen (> 200 kΩ between Bat.-Start and SGnd)

Signal input Remote

Low signalConnection to SGnd with < 2.7 kΩ
High signalOpen (> 35 kΩ between Remote and SGnd)

Signal output Alarm

Position3.x
Signalization designationAlarm
Position marking3.1 (Alarm)
Switching outputTransistor output, active
Output Voltage24 V
Continuous load current≤ 20 mA

Signal output Battery mode

Position3.x
Signalization designationBat.-Mode
Position marking3.2 (Bat.-Mode)
Switching outputTransistor output, active
Output Voltage24 V
Continuous load current≤ 20 mA

Signal output Power Good

Position3.x
Signalization designationPower Good
Position marking3.3 (Power Good)
Switching outputTransistor output, active
Output Voltage24 V
Continuous load current≤ 20 mA

Signal output Ready

Position3.x
Signalization designationReady
Position marking3.4 (Ready)
Switching outputTransistor output, active
Output Voltage24 V
Continuous load current≤ 20 mA

Signal output P > PN

Position3.x
Signalization designationP>Pn
Position marking3.5 (P>Pn)
Switching outputTransistor output, active
Output Voltage24 V
Continuous load current≤ 20 mA

Signal output Service Required

Position3.x
Signalization designationService Required
Position marking3.6 (Service Required)
Switching outputTransistor output, active
Output Voltage24 V
Continuous load current≤ 20 mA

Signal ground SGnd

FunctionSignal ground
Reference potentialFor signal inputs and signal outputs

Product properties

Product familyQUINT AC-USV

Insulation characteristics

Protection classI
Overvoltage categoryII
Pollution degree3

Item dimensions

Width188 mm
Height240 mm
Depth143 mm

Drill hole

Diameter5.5 mm

Installation dimensions

Installation distance right/left0 mm / 0 mm
Installation distance top/bottom50 mm / 50 mm

Mounting

Mounting TypeWall mounting

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 60 °C (> 50 °C: 2,5 % / K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 4000 m (> 1000 m: 3 % / 1000 m)
Max. permissible relative humidity (operation)≤ 95 %
Shock30g in each direction, according to IEC 60068-2-27
Vibration (Operation)5 Hz ... 100 Hz, 0.7g (EN 60068-2-6)

UL

IdentificationUL/C-UL Recognized UL 1778

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
Interference emissionNoise emission
Noise immunityImmunity
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Conducted noise emissionEN 62040-02 (Class C2)

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Contact discharge± 6 kV
Discharge in air± 8 kV
CommentsCriterion A

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 6 GHz
Test field strength10 V/m
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input± 2 kV
Input± 2 kV
Output± 2 kV
Signal± 2 kV
Signal± 2 kV (Communication parallel operation, battery module)
CommentsCriterion A

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Signal1 kV (asymmetrical)
CommentsCriterion B
Input/Output± 1 kV (symmetrical)
Input/Output± 2 kV (asymmetrical)

Conducted interference

Standards/regulationsEN 61000-4-6
Frequency Range0.15 MHz ... 80 MHz
Signal10 V (asymmetrical)
CommentsCriterion A

Power frequency magnetic field

Standards/regulationsEN 61000-4-8
Frequency60 Hz
Signal30 A/m
CommentsCriterion A

Harmonic and interharmonic components

Standards/regulationsEN 61000-4-13
CommentsCriterion A

Criteria

Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.

Why Proax for Phoenix Contact QUINT-HP-UPS/120AC/2.5KVA/PT?

Proax is an authorized distributor of Phoenix Contact QUINT-HP-UPS/120AC/2.5KVA/PT and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesQUINTHPUPS120AC25KVAPT
Pack Size1
Recommended