2866585
SKU
PHX2866585
MPN
QUINT-DIODE/48DC/40
Weight
0.679 kg
Series QUINT-DIODE
QUINT-DIODE/48DC/40 - Redundancy module, with protective coating
QUINT-DIODE/48DC/40 redundancy module
Technical Specifications
DC operation
| Input Voltage | 48 V DC (UN) |
| Input Voltage | < 60 V DC (Umax) |
| Input voltage range | 10 V DC ... 60 V DC |
| Input voltage range DC | 10 V DC ... 60 V DC |
| Voltage type of supply voltage | DC |
| Reverse polarity protection | < yes120 V |
| Nominal input current (IN) | 2x 20 A |
| Nominal input current (IN) | 1x 40 A |
| Maximum current Imax | 2x 19 A (6 mm² at 40°C) |
| Maximum current Imax | 1x 39 A (6 mm² at 40°C) |
| Maximum current Imax | 2x 16 A (6 mm² at 60°C) |
| Maximum current Imax | 1x 32 A (6 mm² at 60°C) |
| Maximum current Imax | 2x 27 A (10 mm² at 40°C) |
| Maximum current Imax | 1x 54 A (10 mm² at 40°C) |
| Maximum current Imax | 2x 21 A (10 mm² at 60°C) |
| Maximum current Imax | 1x 43 A (10 mm² at 60°C) |
| Maximum current Imax | 2x 30 A (16 mm² at 40 °C) |
| Maximum current Imax | 1x 60 A (16 mm² at 40 °C) |
| Maximum current Imax | 2x 24 A (16 mm² at 60°C) |
| Maximum current Imax | 1x 48 A (16 mm² at 60°C) |
| Nominal input current (IN) | 2x 20 A |
| Nominal input current (IN) | 1x 40 A |
| Maximum current Imax | 2x 17 A (6 mm² at 40°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
| Maximum current Imax | 1x 35 A (6 mm² at 40°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
| Maximum current Imax | 2x 14 A (6 mm² at 60°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
| Maximum current Imax | 1x 28 A (6 mm² at 60°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
| Maximum current Imax | 2x 24 A (10 mm² at 40°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
| Maximum current Imax | 1x 49 A (10 mm² at 40°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
| Maximum current Imax | 2x 19 A (10 mm² at 60°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
| Maximum current Imax | 1x 39 A (10 mm² at 60°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
| Maximum current Imax | 2x 27 A (16 mm² at 40°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
| Maximum current Imax | 1x 54 A (16 mm² at 40°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
| Maximum current Imax | 2x 22 A (16 mm² at 60°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
| Maximum current Imax | 1x 44 A (16 mm² at 60°C for potentially explosive areas: Class I, Div. 2, Groups A, B, C, D; T4) |
| Transient surge protection | Transil diode |
| Voltage drop, input/output | approx. 0.7 V |
Output data
| Efficiency | > 97 % |
| Nominal Output Voltage | 47.3 V DC (Input/output voltage drop of 48 V ... 0.7 V ) |
| Nominal output current (IN) | 40 A |
| Power loss nominal load max. | 28 W |
| Connection in series | No |
Input
| Connection Method | Screw connection |
| Conductor cross section, rigid min. | 0.5 mm² |
| Conductor cross section, rigid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 10 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
| Tightening torque, min | 1.2 Nm |
| Tightening torque max | 1.5 Nm |
Output
| Connection Method | Screw connection |
| Conductor cross section, rigid min. | 0.5 mm² |
| Conductor cross section, rigid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 10 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
| Tightening torque, min | 1.2 Nm |
| Tightening torque max | 1.5 Nm |
Electrical properties
| Insulation voltage output / PE | 1 kV |
| Insulation voltage input / PE | 1 kV |
Product properties
| Product family | QUINT DIODE |
| LED | No |
Insulation characteristics
| Protection class | II |
| Degree of pollution | 2 |
Dimensions
| Width | 62 mm |
| Height | 84 mm |
| Depth | 102 mm |
| Horizontal pitch | 3.4 Div. |
Installation dimensions
| Installation distance right/left | 5 mm / 5 mm |
| Installation distance top/bottom | 50 mm / 50 mm |
Mounting
| Mounting Type | DIN rail mounting |
| Assembly instructions | alignable: horizontal 20 mm, vertical 50 mm |
| Mounting Position | horizontal and vertical DIN rail NS 35, EN 60715 |
Material specifications
| Housing Material | Metal |
| Type of housing | AIMg (hood), GD-ZnAICu (cooling unit) |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -25 °C ... 70 °C (> 60 °C derating, -25 ... 60°C) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Shock | 30g, 18 ms in accordance with IEC 60068-2-27 |
| Vibration (Operation) | 3 Hz ... 15 Hz, amplitude ±2.5 mm; 15 Hz ... 100 Hz, 2.3g according to IEC 60068-2-6 |
Standards and Regulations
| Declaration of conformity in acc. with EN 60079-15 | II 3 G Ex nA II T4 X |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Approvals
| UL approvals | UL/C-UL listed UL 508 |
| UL approvals | UL/C-UL Recognized UL 60950-1 |
| UL approvals | UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D |
Conformity/Approvals
| ATEX | II 3 G Ex nA II T4 |
EMC data
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| EMC requirements for noise emission | EN 61000-6-3 |
| EMC requirements for noise emission | EN 61000-6-4 |
| EMC requirements for noise immunity | EN 61000-6-1 |
| EMC requirements for noise immunity | EN 61000-6-2 |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Noise emission | EN 55011 |
Why Proax for Phoenix Contact 2866585?
Proax is an authorized distributor of Phoenix Contact 2866585 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
The redundancy set consists of two QUINT-PS/1AC/24DC/10 power supplies combined with the active QUINT-ORING/24DC/2X10/1X20 redundancy module, so as to guarantee maximum availability of your system.Primary-switched QUINT POWER supply for DIN rail mounting with SFB (selective fuse breaking) technology, input: 1-phase, output: 24 V DC/10 AActive QUINT redundancy module for DIN rail mounting with Auto Current Balancing ACB technology and monitoring functions, input: 24 V DC, output: 24 V DC/2 x 10 A or 1 x 20 A, including mounted UTA 107/30 universal DIN rail adapter