QUINT-DC-UPS/24DC/10 - Uninterruptible power supply
Uninterruptible power supply 24 V DC/10 A, with integrated 1.3 Ah battery module. In the download area, there is a clearly arranged selection table available with load currents and buffer times, as well as charging times after buffer mode.
Technical Specifications
DC operation
Input Voltage | 24 V DC |
Input voltage range | 22.5 V DC ... 30 V DC |
Wide-range input | no |
Input voltage range DC | 22.5 V DC ... 30 V DC |
Voltage type of supply voltage | DC |
Buffer period | 1.5 min. (10 A) |
Buffer period | 20 min. (2 A) |
Current consumption | approx. 0.1 A |
Current consumption | 0.5 A (charging process) |
Current consumption | 10.5 A (max.) |
Fixed backup threshold | < 22 V DC |
Variable connect threshold | (UIN - 1 V)/0.1 s |
Input fuse | 15 A (slow-blow, internal) |
Output data
Efficiency | > 91 % |
Nominal Output Voltage | 24 V DC (Normal operation: Uin- 0.5 V DC, buffer mode: 27.9 to 19.2 V DC) |
Nominal output current (IN) | 10 A |
Bridging time | 2 min. |
Short-circuit-proof | yes |
Output Power | 240 W |
Power dissipation | 20 W |
Power dissipation | 8 W |
Connection in parallel | no |
Connection in series | yes |
Mains operation
Nominal Output Voltage | 24 V DC |
Nominal output current (IN) | 10 A |
Battery operation
Nominal Output Voltage | 24 V DC |
Nominal output current (IN) | 10 A |
Signal
Output description | Power OK |
Signal: floating
Output description | Alarm |
Maximum Switching Voltage | ≤ 30 V AC/DC |
Continuous load current | ≤ 1 A |
Output description | Battery Charge |
Maximum Switching Voltage | ≤ 30 V AC/DC |
Continuous load current | ≤ 1 A |
Output description | Battery Mode |
Maximum Switching Voltage | ≤ 30 V AC/DC |
Continuous load current | ≤ 1 A |
Energy storage
Nominal capacity | 1.3 Ah |
Battery module service life | 6 Years (20 °C) |
Latest startup date (battery only) | 9 Months (20 °C ... 30 °C) |
Latest startup date (battery only) | 6 Months (30 °C ... 40 °C) |
Memory medium | internal, battery 1.3 Ah |
Network management | Yes |
Input
Connection Method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Output
Connection Method | Pluggable screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Signal
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signaling
Types of signaling | LED |
Operating voltage display | Green LED |
Signal output
Status display | LED "Power OK" green |
Note on status display | Power OK: LED permanently lit |
Signal output: floating
Status display | LED red |
Note on status display | Alarm: LED permanently lit |
Status display | LED flashing yellow |
Note on status display | Battery charge: LED flashing |
Status display | Yellow LED |
Note on status display | Battery mode: LED permanently lit |
Electrical properties
Insulation voltage input/output | 2 kV (routine test) |
Insulation voltage input/output | 4 kV (type test) |
Product properties
Disposal | Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. |
MTBF (IEC 61709, SN 29500) | > 500000 h |
Insulation characteristics
Protection class | II (in closed control cabinet) |
Dimensions
Width | 100 mm |
Height | 130 mm |
Depth | 125 mm |
Installation dimensions
Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
Material specifications
Housing Material | Metal |
Type of housing | AluNox (AlMg1) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | 0 °C ... 50 °C |
Ambient temperature (storage/transport) | 0 °C ... 40 °C |
Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
Standards and Regulations
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Standard - Electrical safety | EN 61558-2-17 |
Standard - Safe isolation | DIN VDE 0100-410 |
Standard - Safety of transformers | EN 61558-2-17 |
Approvals
Shipbuilding approval | DNV GL (EMC A), ABS |
UL approvals | UL/C-UL listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
UL approvals | UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D |
Conformity/Approvals
SIL in accordance with IEC 61508 | 0 |
Performance level according to ISO 13849 | without |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Noise immunity | EN 61000-6-2:2005 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Noise emission | EN 55011 (EN 55022) |
Why Proax for Phoenix Contact 2866226?
Proax is an authorized distributor of Phoenix Contact 2866226 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- The redundancy set consists of two QUINT-PS/1AC/24DC/10 power supplies combined with the active QUINT-ORING/24DC/2X10/1X20 redundancy module, so as to guarantee maximum availability of your system.Primary-switched QUINT POWER supply for DIN rail mounting with SFB (selective fuse breaking) technology, input: 1-phase, output: 24 V DC/10 AActive QUINT redundancy module for DIN rail mounting with Auto Current Balancing ACB technology and monitoring functions, input: 24 V DC, output: 24 V DC/2 x 10 A or 1 x 20 A, including mounted UTA 107/30 universal DIN rail adapter