Series QUINT-DIODE
QUINT-DIODE/48DC/2X20/1X40 - Redundancy module
DIN rail diode module 48 V DC/2x20 A or 1x40 A. Uniform redundancy up to the consumer.
- Flexible
- Rugged design
- Consistent redundancy up to the load
Technical Specifications
DC operation
Nominal input voltage range | 48 V DC |
Input voltage range | 30 V DC ... 56 V DC |
Voltage type of supply voltage | DC |
Reverse polarity protection | < yes120 V |
Nominal input current (IN) | 2x 20 A (-25 °C ... 60 °C) |
Nominal input current (IN) | 1x 40 A (-25 °C ... 60 °C) |
Maximum current Imax | 2x 30 A (-25 °C ... 40 °C) |
Maximum current Imax | 1x 60 A (-25 °C ... 40 °C) |
Transient surge protection | Varistor |
Voltage drop, input/output | 0.7 V |
Nominal input voltage range | 48 V DC |
Input voltage range | 30 V DC ... 56 V DC |
Input voltage range DC | 30 V DC ... 56 V DC |
Output data
Efficiency | > 97 % |
Nominal Output Voltage | UIn - 0,7 V |
Nominal output current (IN) | 40 A (Increasing power) |
Nominal output current (IN) | 20 A (Redundancy) |
Derating | 60 °C ... 70 °C (2.5 %/K) |
Power loss nominal load max. | 14 W (IOUT = 20 A) |
Connection in series | No |
Derating | 60 °C ... 70 °C 2.5 %/K |
Input
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 6 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 12 |
Conductor cross section AWG max. | 10 |
Stripping length | 8 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Output
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.5 mm² |
Conductor cross section, rigid max. | 16 mm² |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 16 mm² |
Conductor cross section AWG min. | 10 |
Conductor cross section AWG max. | 6 |
Stripping length | 10 mm |
Screw thread | M4 |
Tightening torque, min | 1.2 Nm |
Tightening torque max | 1.5 Nm |
Electrical properties
Insulation voltage input, output / housing | 1000 V |
Product properties
Product family | QUINT DIODE |
MTBF (IEC 61709, SN 29500) | 40000000 h |
LED | No |
Insulation characteristics
Protection class | III |
Degree of pollution | 2 |
Dimensions
Width | 50 mm |
Height | 130 mm |
Depth | 125 mm |
Horizontal pitch | 2.8 Div. |
Installation dimensions
Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
Material specifications
Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
Housing Material | Metal |
Housing Material | Steel sheet, zinc-plated |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 5000 m |
Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
Vibration (Operation) | 15 Hz ... 150 Hz, 2.3g, 90 min. |
Standards and Regulations
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204-1 (PELV) |
Standard - Safe isolation | DIN VDE 0100-410 |
Approvals
UL approvals | UL/C-UL listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
UL approvals | UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
Conformity/Approvals
ATEX | II 3 G Ex ec IIC T4 Gc |
ATEX | DEKRA 20ATEX0041 X |
IECEx | Ex ec IIC T4 Gc |
IECEx | IECEx DEK 20.0022X |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 2 kV (level 3 - asymmetrical: conductor to ground) |
Input | 1 kV (Level 2 - symmetrical: Conductor to conductor) |
Output | 2 kV (level 3 - asymmetrical: conductor to ground) |
Output | 1 kV (Level 2 - symmetrical: Conductor to conductor) |
Comments | Criterion A |
Surge current load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 2 kV (level 3 - asymmetrical: conductor to ground) |
Input | 1 kV (Level 2 - symmetrical: Conductor to conductor) |
Output | 2 kV (level 3 - asymmetrical: conductor to ground) |
Output | 1 kV (Level 2 - symmetrical: Conductor to conductor) |
Emitted interference
Standards/regulations | EN 61000-6-3 |
Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Accessories
Why Proax for Phoenix Contact 2320160?
Proax is an authorized distributor of Phoenix Contact 2320160 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- The redundancy set consists of two QUINT-PS/1AC/24DC/10 power supplies combined with the active QUINT-ORING/24DC/2X10/1X20 redundancy module, so as to guarantee maximum availability of your system.Primary-switched QUINT POWER supply for DIN rail mounting with SFB (selective fuse breaking) technology, input: 1-phase, output: 24 V DC/10 AActive QUINT redundancy module for DIN rail mounting with Auto Current Balancing ACB technology and monitoring functions, input: 24 V DC, output: 24 V DC/2 x 10 A or 1 x 20 A, including mounted UTA 107/30 universal DIN rail adapter