MINI MCR-RTD-UI-SP-NC - Resistance thermometer measuring transducer

Temperature transducer for the connection of 2, 3, and 4-conductor resistance thermometers and resistance-type sensors. Configurable via DIP switch or software. Spring-cage connection, standard configuration. Replacement part: 2902052 MINI MCR-2-RTD-UI-PT.

Technical Specifications

Product properties

Product familyMINI Analog

Insulation characteristics

Overvoltage categoryII
Pollution degree2

Electrical properties

Rated Insulation Voltage50 V AC/DC
Electrical isolationBasic insulation in accordance with EN 61010
Test voltage, input/output/supply1.5 kV (50 Hz, 1 min.)
Protective circuitTransient protection
Step response (0–99%)200 ms (2-conductor)
Step response (0–99%)500 ms (3-conductor)
Step response (0–99%)500 ms (4-conductor)
Maximum temperature coefficient0.01 %/K
Transmission error resistance-type sensor2 Ω
Transmission error resistance thermometer0.1 % * 350 K / set measuring range; 0.1 % > 350 K (Pt/Ni)
Transmission error resistance thermometer0.3 % * 200 K / set measuring range; 0.3 % > 200 K (Cu)

Supply

Supply Voltage Range9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Typical current consumption< 27 mA (at 24 V DC)
Power consumption≤ 700 mW (at IOUT = 20 mA, 9.6 V DC, load 500 Ω)

Signal

Number of Inputs1
Input SignalTemperature
Input SignalResistor

Measurement

Configurable/programmableYes
Sensor types (RTD) that can be usedPt, Ni, Cu sensors: 2, 3, 4-wire
Temperature measuring range-200 °C ... 850 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 850°C via DIP switches)
Temperature measuring rangemin. 50 K
Sensor input currentapprox. 200 µA
Max. permissible overall conductor resistance≤ 25 Ω (Per cable)
Linear resistance measuring range0 Ω ... 4000 Ω (Minimum measuring span: 10% of the selected measuring range)
Connection technology2-, 3-, 4-conductor

Frequency:

Configurable/programmableno

Signal

Number of Outputs1
Configurable/programmableYes
Voltage output signal0 V ... 10 V
Voltage output signal10 V ... 0 V
Voltage output signal0 V ... 5 V
Voltage output signal1 V ... 5 V
Max. voltage output signalapprox. 12.3 V
Current Output Signal0 mA ... 20 mA
Current Output Signal4 mA ... 20 mA
Current Output Signal20 mA ... 0 mA
Current Output Signal20 mA ... 4 mA
Max. current output signal24.6 mA
Load/output load voltage output10 kΩ
Load/Output Load Current Output500 Ω (at 20 mA)
Ripple< 20 mVPP
Ripple< 20 mVPP (at 500 Ω)

Connection data

Connection MethodSpring-cage connection
Stripping length8 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 12

Data: IFS interface

Connection MethodS-PORT

Signaling

Status displayLED red

Dimensions

Width6.2 mm
Height93.1 mm
Depth102.5 mm

Material specifications

Colorgreen (RAL 6021)
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)

CE

CertificateCE-compliant

ATEX

Identification II 3 G Ex nA IIC T4 Gc X

UL, USA/Canada

IdentificationUL 508 Listed
IdentificationClass I, Div. 2, Groups A, B, C, D T4
IdentificationClass I, Zone 2, Group IIC

Shipbuilding approval

IdentificationD, EMC1
CertificateDNV GL 14085-15HH

EMC data

Noise immunityEN 61000-6-2
NoteWhen being exposed to interference, there may be minimal deviations.
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4

Electrostatic discharge

Standards/regulationsEN 61000-4-2
CommentsSafety measures must be taken to prevent electrostatic discharge.

Electromagnetic HF field

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value0.04 %

Fast transients (burst)

DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value0.1 %

Surge current load (surge)

Standards/regulationsEN 61000-4-5

Conducted interference

DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value0.02 %

Standards and Regulations

Electrical isolationBasic insulation in accordance with EN 61010

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsThe DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting Positionany
Accessories

Why Proax for Phoenix Contact MINI MCR-RTD-UI-SP-NC?

Proax is an authorized distributor of Phoenix Contact MINI MCR-RTD-UI-SP-NC and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesMINIMCRRTDUISPNC
Pack Size1
Recommended

Available for order